English
106
WILO SE 03/2018
4.4.3.0
Software version of
motor controller
Display the software version of
the motor controller
5.0.0.0
Service
Service menus
5.1.0.0
Multi pump
Double pump
Only displayed when DP is
active (incl. sub-menus)
5.1.1.0
Operating mode
Main/standby operation
Only displayed for double
pump master
Parallel operation
Only displayed for double
pump master
5.1.2.0
Setting, MA/SL
Manual switching from master
to slave mode
Only displayed for double
pump master
5.1.3.0
Pump cycling
Only displayed for double
pump master
5.1.3.1 Manual pump
cycling
Carries out pump cycling
independent of the countdown
Only displayed for double
pump master
5.1.3.2 Internal/external
Internal pump cycling
Only displayed for double
pump master
External pump cycling
Only displayed for double
pump master, see “AUX”
terminal
5.1.3.3 Internal: Time
interval
Can be set between 8 h and 36 h
in 4 h steps
Displayed when internal
pump cycling is activated
5.1.4.0
Pump enabled/
disabled
Pump enabled
Pump disabled
5.1.5.0
SSM
Individual fault signal
Only displayed for double
pump master
Collective fault signal
Only displayed for double
pump master
5.1.6.0
SBM
Individual readiness signal
Is only displayed for double
pump master and SBM
function at readiness/
operation
Individual run signal
Only displayed for double
pump master
Collective readiness signal
Only displayed for double
pump master
Collective run signal
Only displayed for double
pump master
5.1.7.0
Extern off
Individual Extern off
Only displayed for double
pump master
Collective Extern off
Only displayed for double
pump master
5.2.0.0
BMS
Settings for Building
Management System (BMS) –
building automation
Incl. all sub-menus, only
displayed when BMS is active
No.
Designation
Type
Symbol Values/explanations
Display conditions
±
±
±
±
±
±
±
±
±