English
102
WILO SE 03/2018
• Set DIP switch 1 to the “ON” position.
Service mode is activated. The symbol shown here flashes on the
status page.
The sub-elements of menu <5.0.0.0> switch from the “Information”
element type to the “Selection/setting” element type, and the stand-
ard “access disable” symbol (see symbol) is hidden for the respective
elements (except for <5.3.1.0>).
The values and settings for these elements can now be edited.
• To deactivate, return the switch to its starting position.
8.6.7
Activating/deactivating access
disable
In order to prevent impermissible changes to the pump settings, all
functions can be disabled.
When access is disabled, this is shown on the status page by the
default “access disable” symbol.
To activate or deactivate this, proceed as follows:
• Set DIP switch 2 to the “ON” position.
Menu <7.0.0.0> is displayed.
• Turn the operating button to activate or deactivate the disable.
• To confirm the change, press the operating button.
The current state of the disable is represented on the symbol display
by the symbols shown here.
Disable active
No changes can be made to setpoints or settings. Read access to all
of the menu elements is maintained.
Disable inactive
The elements of the basic menu can be edited
(menu elements <1.0.0.0>, <2.0.0.0> and <3.0.0.0>).
NOTICE:
To edit the sub-elements of menu <5.0.0.0>, service mode must
also be activated.
• Reset DIP switch 2 to the “OFF” position.
The display returns to the status page.
NOTICE:
Errors can be acknowledged after a waiting period despite the “access
disable” being active.
8.6.8
Activating/deactivating termination
In order to establish a definite communication connection between
the electronic modules, it is necessary to terminate both ends of the
cable.
In a double pump, the electronic modules are already prepared for
double pump communication at the factory.
To activate or deactivate this, proceed as follows:
• Set DIP switches 3 and 4 to the “ON” position.
Termination is activated.
NOTICE:
Both DIP switches must always be in the same position.
• To deactivate, return the switches to the starting position.
8.7
Menu elements reference
The following table gives an overview of the available elements of all
menu levels. The menu number and the element type are designated
separately, and the function of the element is explained. If applicable,
there is information about the setting options of the individual ele-
ments.
ON
1
ON
1
ON
2
ON
2
ON
2
ON
2
Содержание STRATOS GIGA
Страница 2: ......
Страница 3: ...Fig 1 IF Modul Fig 2 L3 L2 L1 1 x M40 1 x M20 1 x M16 2 x M12...
Страница 4: ...Fig 3...
Страница 8: ......
Страница 195: ......