US English INSTALLATION

pump at a slight angle (if installed as a portable 

pump). Protect the pump from frost.

5.2.  Installation methods

• Vertical stationary wet well installation with guide 

system

• Vertical portable wet well installation with pump 

foot

• Vertical stationary dry well installation

5.3.  Installation

DANGER: from falling!

When installing the pump and its accessories, 

work is sometimes performed directly at the 

edge of the basin or sump. Carelessness or 

wearing inappropriate clothing could result in a 

fall. There is a risk of fatal injury! Take all neces-

sary safety precautions to prevent this.

The following information should be taken into 

consideration when installing the pump:

• 

This work must be carried out by a qualified person 

and electrical work must be carried out by an elec-

trician.

• The operating space must be clean, free of coarse 

solids, dry, frost-free and, if necessary, decontami-

nated. It must also be suitable for the particular 

pump.

• When working in sumps, a second person must be 

present for safety reasons. If there is a risk of toxic 

or asphyxiating gases building up, the necessary 

precautions must be taken.

• 

The system planner should select the sump size and 

motor cooling time according to the ambient condi-

tions in operation.

• Ensure that lifting equipment can be set up without 

any trouble, since this is required for assembly and 

removal of the pump. It must be possible to reach 

the pump safely in its operating and storage loca-

tions using the lifting equipment. The machine must 

be positioned on a firm bearing surface. For trans

-

porting the pump, the lifting gear must be secured 

to the lifting eyelets or handle provided. When using 

chains, they must be connected with a shackle to 

the lifting eyelets or the handle. Lifting gear must 

be technically approved.

• Power supply cables must be laid out in such a way 

that safe operation and trouble-free assembly/dis-

mantling are possible at all times. The pump must 

never be carried or dragged by the power supply 

cable. Check whether the cable present is adequate 

for the type of installation selected, in terms of its 

cross-section and its length.

• When using switchgear, the corresponding protec-

tion class must be observed. In general, switchgear 

is to be installed outside potentially explosive areas 

in such a way that it is protected from submersion.

• When used in an explosive atmosphere, it must be 

ensured that the pump and all accessories are ap-

proved for this purpose.

• Structural components and foundations must be of 

sufficient stability in order to allow the product to 

be fixed securely and functionally. The end user or 

the supplier is responsible for the provision of the 

foundations and their suitability in terms of dimen-

sions, stability, and strength.

• 

If the motor housing is to be taken out of the fluid 

during operation, the operating mode for non-

immersed operation should be applied.

To keep glanded motors sufficiently cooled in S3 

mode, they must be flooded completely before 

being switched back on if the motor has been 

taken out of the fluid!

• Never let the pump run dry. The water level must 

never fall below the minimum. Therefore, we rec-

ommend installing a level control system or a dry-

running protection system where there are great 

variations in the level. 

• 

Use guide and deflector plates for the fluid intake. 

If the water jet reaches the surface of the water, air 

will be introduced into the fluid, which can accumu

-

late in the pipe system. This can result in inadmis-

sible operating conditions and to deactivation of 

the entire system.

• Check that the available planning documentation 

(installation plans, layout of the operating space, 

intake ratios) is complete and correct.

• Also observe all regulations, rules, and legal require-

ments for working with and underneath heavy sus-

pended loads. Wear appropriate protective clothing/

equipment.

• Please also observe the applicable national accident 

prevention regulations and trade association safety 

provisions.

5.3.1.  Maintenance work

After a storage period of more than 6 months, the 

following maintenance work must be carried out 

before installation:

• Rotate impeller

• Check oil level in the sealing chamber

Rotate impeller

1. 

Position the pump horizontally on a firm surface.

Make sure that the pump cannot fall over and/or 

slip.

2.  Carefully and slowly reach into the hydraulics hous-

ing from below and rotate the impeller.

WARNING: sharp edges!
Sharp edges can form on the impellers and 

hydraulic opening. There is a risk of injury! Wear 

the necessary protective clothing, such as pro-

tective gloves.

Содержание Rexa PRO Series

Страница 1: ...Pioneering for You Wilo Rexa PRO 6065992 Ed 04 07 2015 WH US Installation and operating instructions fr Notice de montage et de mise en service es Instrucciones de instalaci n y funcionamiento...

Страница 2: ...Fig 3 Fig 2 Fig 1 1 5 7 6 3 4 2 1 5 6 6 3 3 4 2 S1 S1 S2 S3 7a 7b 1 1 5 9 6 3 4 2 S1 S1 S2 S3 8 7b 7a d A A min 1 x d A d min 0 3 x d B...

Страница 3: ...Fig 5 Fig 6 Fig 4 1 4 8 3 3 6 5 2 7 U1 Z1 3 U2 4 Cr Z2 5 C S M 1 gn ye L N PE 1 2 6 3 4 gn ye 1 2 6 21 20 DK 5 1 2 4 3 M 3 gn ye W V 21 20 U PE 6 DK 5 1 2 4 3 M 3 gn ye W V 11 10 U PE 6 DK...

Страница 4: ...M 3 gn ye W V 20 21 U PE 6 22 5 1 2 4 3 M 3 gn ye W V 10 11 U PE 6 12 max C min C Fig 8 5 4 3 W1 V1 U1 5 4 3 W2 V2 U2 1 max C min C 2 M 3 gn ye 20 21 PE 6 22 5 1 2 4 3 M 3 gn ye W1 V1 10 11 U1 5 4 3 W...

Страница 5: ...Fig 9 1...

Страница 6: ...port and storage 16 4 1 Delivery 16 4 2 Transport 16 4 3 Storage 16 4 4 Return delivery 17 5 Installation 17 5 1 General 17 5 2 Installation methods 18 5 3 Installation 18 5 4 Dry running protection 2...

Страница 7: ...reserves the right to make tech nical modifications to units or components This operating and maintenance manual refers to the pump shown on the title page 1 5 Warranty In general the specifications i...

Страница 8: ...e directives and regulations Safety information that refers only to material dam age is printed in gray without safety symbols 2 2 General safety When installing or removing the pump never work alone...

Страница 9: ...connection may only be made if the switch gear complies with the harmonized EU standards Cellphones and other mobile radio equipment may cause malfunctions in the system WARNING electromagnetic radiat...

Страница 10: ...nt general safety and health requirements of the European Union as well as the published European standards and internationally recognized German standards Since this product was not intended to be so...

Страница 11: ...als if there is water ingress into the sealing cham ber through the mechanical seal on the fluid side 3 2 4 Seal The seal for the fluid and the motor compart ment is made via two mechanical seals The...

Страница 12: ...mersed is not possible with all motors Observe the information on the rating plate Operating mode S3 50 is permissible if the necessary motor cooling is guaranteed by complete immersion for at least 1...

Страница 13: ...plug Installation and operating instructions 3 8 Accessories Cable lengths up to 160 ft 50 m in fixed length increments of 40 ft 12 5 m or customized cable lengths on request Guide system Pump foot E...

Страница 14: ...act coating fulfills its intended purpose Please note that elastomer parts and coatings be come brittle over time If the product is to be stored for longer than 6 months we recommend checking these pa...

Страница 15: ...orresponding protec tion class must be observed In general switchgear is to be installed outside potentially explosive areas in such a way that it is protected from submersion When used in an explosiv...

Страница 16: ...nd operating instructions for the guide system 2 Preparing the pump for operation on a guide sys tem about 1 3 h see the installation and operating instructions for the guide system 3 Installing the p...

Страница 17: ...pipe system on the suction and pressure sides must be self supporting i e it may not be sup ported by the pump In addition the pump connec tion to the pipe system must be free of stress and vibration...

Страница 18: ...qualified electrician ap proved by the local energy supply company in accordance with locally applicable regulations DANGER from incorrect connection With Ex rated pumps the power supply cable must be...

Страница 19: ...inding 2 3 L U1 Z1 4 N U2 5 Z2 Connection for start and operating capacitor 6 DK Leakage detection for motor com partment green yellow gn ye PE Ground Connection WITHOUT capacitor switchgear If the un...

Страница 20: ...oring When the low threshold is reached a preliminary warning may be issued when the high threshold is reached the motor must switch off When used outside potentially explosive areas the bimetallic st...

Страница 21: ...injury when commissioning the pump the following points must be observed Commissioning of the pump may only be carried out by qualified and trained personnel in accordance with the safety instruction...

Страница 22: ...an be vented by suitable venting devices in the system or if available using vent screws on the pressure port Check switching points of level control and dry running protection systems Check to ensure...

Страница 23: ...at the temperature of the fluid and in the operating space does not fall below 37 F 3 C This ensures that the pump is always ready for op eration For extended downtime a regular monthly to quarterly 5...

Страница 24: ...tenance or repair work the pump must be installed and connected as described in the In stallation section The pump must be switched on as described in the Commissioning section Note the following All...

Страница 25: ...ng conditions 2 years Visual inspection of the power supply cable Visual inspection of accessories Visual inspection of the coating and housing for wear Functional inspection of all safety and monitor...

Страница 26: ...e are relatively large deviations consult the manufacturer 8 3 5 Inspection of the switchgear relays used See the relevant installation and operating instruc tions for a description of the individual...

Страница 27: ...free the impeller or clear the suction port 7 The fluid is too dense Consult the manufacturer Fault unit is running but not pumping 1 No fluid available Open inlet for tank or slide valve 2 Inlet bloc...

Страница 28: ...ider the flow rate in the pipe The slower the flow rate the greater the risk of solids depositing in the pump and piping We therefore recommend a minimum flow rate of 2 3 ft s 0 7 m s at a pumping pre...

Страница 29: ...the Electrical connection section the following points must be observed for Ex rated pumps The power supply cable must be connected outside the potentially explosive area or inside a housing with an...

Страница 30: ...lowing points for Ex rated pumps The end user is responsible for defining the poten tially explosive area Only pumps with Ex approval may be used within a potentially explosive area Ex rated pumps mus...

Страница 31: ...IL 60018 USA Phone 888 954 6872 Fax 888 945 6783 Manufacturing Facility 86 Genesis Parkway Thomasville Georgia 31792 USA Phone 229 584 0097 Fax 229 584 0234 WILO Canada Inc Bay 7 2915 10th Ave N E Cal...

Отзывы: