English
Installation and operating instructions Wilo-FLA Compact
35
10 Faults, causes and remedies
Faults, particularly those affecting the pumps or
the control system, should only be remedied by
Wilo’s customer service or a specialist company.
NOTICE!
The general safety instructions must be observed
during any maintenance or repair work. Also fol-
low the installation and operating instructions of
the pumps and the control device!
Fault
Cause
Remedy
Pump does not start
No mains voltage
Check the fuses, cables and connections
Main switch “OFF”
Switch on the main switch
Water level in break tank too low, i.e.
low-water level reached (fault only
occurs in test operation)
Check the break tank’s inlet valve/supply line
Low-water signal transmitter is defective
(fault only occurs in test operation)
Check and, if necessary, replace the
low-water signal transmitter
Shut-off device closed at pressure
sensor/pressure switch
Check and open the shut-off device if
necessary
Start-up pressure is set too low
Check the setting and correct it if necessary
Switch-on/off pressures for pressure
switch are not coordinated
Check the setting and correct it if necessary
Motor protection has triggered
(fault only occurs in test operation)
Check the default values against the pump or
motor data, measure the current values and
correct the setting if necessary. Check the
motor for defects and replace it if necessary
Power contactor is defective
Check it and replace it if necessary
Turn-to-turn fault in the motor
Check and, if necessary, replace the motor or
have it repaired
Pump does not shut down
Connection pipe between VBH and pump
blocked or shut off
Check the connection pipe, if necessary,
remove the clogging or open the shut-off
device
Air in the connection pipe between VBH
and pump
Check and shut off the piping and vent the
pumps if necessary
Impellers are blocked
Check the pump and replace it or have it
repaired if necessary
Non-return valve is leaking
Check and replace the seal or non-return
valve if necessary
Non-return valve is blocked
Check and remove the blockage or replace
the non-return valve if necessary
Gate valve in the system is closed or not
sufficiently open
Check and open the shut-off device
completely if necessary
Flow rate is too high
Check the pump data and default values and
correct them if necessary
Shut-off device is closed at pressure
sensor
Check and open the shut-off device if
necessary
Switch-off pressure is set too high
Check the setting and correct it if necessary
Pressure switch or cable are defective
Check pressure switch or cable and replace if
necessary
Incorrect direction of rotation of the
motors
Check direction of rotation and correct by
changing over phases if necessary
Switching frequency is too high or
fluttering
Connection pipe between VBH and pump
blocked or shut off
Check the connection pipe, if necessary,
remove the clogging or open the shut-off
device
Shut-off device is closed at pressure
switch
Check and open the shut-off device if
necessary
Incorrect supply pressure at diaphragm
expansion tank
Check the supply pressure and correct it if
necessary
Valve at diaphragm expansion tank is
closed
Check the valve and open it if necessary
Switching difference is set too low
Check the setting and correct it if necessary
Содержание FLA Compact-1 Helix V16
Страница 2: ...Fig 1a Fig 1b...
Страница 3: ...Fig 2a Fig 2b...
Страница 4: ...Fig 3...
Страница 5: ...Fig 4a...
Страница 6: ...Fig 4b C Fig 5...
Страница 7: ...Fig 6a Fig 6b...
Страница 8: ...Fig 7a Fig 7b...
Страница 9: ...Fig 8a...
Страница 10: ...Fig 8b...
Страница 11: ...Fig 9a Fig 9b...
Страница 12: ...Fig 10a Fig 10b...
Страница 13: ...Fig 10c Fig 10d...
Страница 14: ...Fig 11...
Страница 55: ...Fran ais Notice de montage et de mise en service Wilo FLA Compact 41...
Страница 73: ...Fran ais Notice de montage et de mise en service Wilo FLA Compact 59...