Installation and operating instructions Wilo-Control MS-L 2x4kW
41
APPENDIX English
LED lights up red
Cause:
Winding temperature monitoring has been
triggered
Solution:
Check pump and wiring (converter bridge
may be missing); check pump operating conditions
LED lights up red
Cause:
High-water alarm has been triggered.
Solution:
Check pump/unit operating conditions
and level settings
All LEDs light up simultaneously for 2 sec.
Cause:
Button lock active
Solution:
Deactivate the button lock by simulta-
neously pressing down the Manual Mode, Stop and
Automatic Mode buttons (for approx. 1 s).
All LEDs light up from right to left.
Cause:
Incorrect phase sequence in mains connec-
tion
Solution:
Swap over 2 phases in the switchgear's
mains connection
10.3. Fault memory
The switchgear has a fault memory. The last fault
is stored retentively in the fault memory.
Opening the fault memory
By pressing down the Stop and Automatic Mode
buttons simultaneously, the last fault is indicated
by the corresponding LED.
P
1
Deleting the fault memory
The fault memory is deleted by simultaneously
pressing and holding down (for approx. 1 s) the
pump 1 Manual Mode and Stop buttons.
10.4. Further steps for troubleshooting
If the points listed here do not rectify the fault,
contact Wilo Customer Service. They can help you
as follows:
• Telephone and/or written support from Wilo
Customer Service
• On-site support from Wilo customer service
• Inspection or repair of the switchgear at the
factory
Please note that you may be charged for some
services provided by our customer service.
For more details, please contact Wilo Customer
Service.
11. Appendix
11.1. System impedance tables
System impedances for 1~230 V, 2-pole, direct starting
Power
System impedance
Connections/h
kW
ohms
1.5
0.4180
6
2.2
0.2790
6
1.5
0.3020
24
2.2
0.1650
24
1.5
0.2720
30
System impedances for 1~230 V, 2-pole, direct starting
Power
System impedance
Connections/h
kW
ohms
2.2
0.1480
30
System impedances for 3~400 V, 2-pole, direct starting
Power
System impedance
Connections/h
kW
ohms
2.2
0.2788
6
3.0
0.2000
6
4.0
0.1559
6
2.2
0.2126
24
3.0
0.1292
24
4.0
0.0889
24
2.2
0.1915
30
3.0
0.1164
30
4.0
0.0801
30
System impedances for 3~400 V, 4-pole, direct starting
Power
System impedance
Connections/h
kW
ohms
3.0
0.2090
6
4.0
0.1480
6
2.2
0.2330
24
3.0
0.1380
24
4.0
0.0830
24
2.2
0.2100
30
3.0
0.1240
30
4.0
0.0740
30
11.2. Spare parts
Spare parts can be ordered from Wilo Customer
Service. To avoid return queries and incorrect or
-
ders, the serial and/or article number must always
be supplied.
Subject to change without prior notice!