Installation and operating instructions Wilo-Control MS-L 2x4kW

 39

DECOMMISSIONING/DISPOSAL English

• Pump cycling between the base-load and the 

peak-load pump is carried out after each pump-

ing procedure.

NOTE 

High-water protection is active in automatic 

mode. When the switch-on level for high-water 

protection is reached, the following occurs:

•   forced switch-on of the pumps.
• 

a

 visual warning, the High water LED, lights up 

constantly.

• 

an

 audible warning is emitted via a constant 

tone.

• 

a

 collective fault signal contact (SSM) is acti-

vated.

• 

an

 external high water alarm.

7.6.  Behaviour during operation

When operating the switchgear, always follow the 

locally applicable laws and regulations for work 

safety, accident prevention and handling electri-

cal products.

To help to ensure safe working practice, the 

responsibilities of employees should be clearly set 

out by the operator. All personnel are responsible 

for ensuring that regulations are observed.

Check the settings at regular intervals as to 

whether they meet the current requirements. 

The settings may need to be adjusted.

8.  Decommissioning/disposal

All work must be carried out with the greatest 

care.

8.1.  Deactivating automatic mode on the unit

1. 

Press the "Stop" button on the control panel.

2. 

The "Pump operation" LED goes out.

3. 

The "auto" LED flashes

4.  The switchgear is in stand-by mode.

NOTE 

High-water protection is 

not

 active in standby 

mode. When the switch-on level for high-water 

protection is reached, the following occurs:

•   forced switch-on of the pumps.
• 

a

 visual and audible warning

• 

The

 collective fault signal contact (SSM) is 

activated.

• 

an

 external high water alarm.

8.2.  Temporary shutdown

For temporary deactivation, the control is 

switched off and switchgear is switched off via 

the main switch.

The switchgear and the unit are now ready for 

operation at any time. The defined settings are 

stored retentively in the switchgear and are not 

discarded.

Make sure that the ambient conditions are ob-

served accordingly:

• 

Ambient/operating temperature: -30 ... +60 °C

• 

Air humidity: 40...50 %

Prevent formation of condensate!

BEWARE of moisture! 

Ingress of moisture will result in damage to 

the switchgear. During standstill time, pay 

attention to the permissible air humidity and 

ensure the switchgear is stored so it is over-

flow-proof.

1. 

Press the "Stop" button.

2. 

Wait until the "Pump operation" LED goes out.

3. 

The "auto" LED flashes.

4.  Switch off the switchgear using the main switch 

("OFF" position).

5. 

The "On" LED goes out.

8.3.  Final shutdown

POTENTIALLY fatal danger due to electrical 

voltage! 

Incorrect procedures can cause fatal electric 

shocks. This work may only be carried out by 

a qualified electrician approved by the local 

power supplier, in accordance with locally 

applicable regulations.

1. 

Press the "Stop" button.

2. 

Wait until the "Pump operation" LED goes out.

3. 

The "auto" LED flashes.

4.  Switch off the switchgear using the main switch 

("OFF" position). On switchgears with a plug, 

remove the plug from the socket.

5. 

The "On" LED goes out.

6.  Switch off the entire unit so it is voltage-free and 

secure it against accidental activation.

7.  If the terminal for the collective fault signal is oc-

cupied, the external voltage source present there 

must also be switched so it is voltage-free.

8. 

If the terminal for the external SSM alarm is oc

-

cupied, the external voltage source present there 

must also be switched so it is voltage-free.

9.  Disconnect all power supply cables and pull these 

out of the threaded cable connections.

10. 

Connect the ends of the power supply cables so 

that no moisture can enter into the cable.

11.  Dismount the switchgear by undoing the screws 

on the substructure.

8.3.1.  Return delivery/storage

For shipping purposes, the switchgear must be 

packaged so it is protected against knocks and 

waterproof.

Please also refer to the “Transport and storage” 

section.

8.4.  Disposal

Proper disposal of this product avoids damage to 

the environment and risks to personal health.

• Use the services of public or private waste dis-

posal companies, or consult them for the disposal 

of the product or parts thereof.

• More information about proper disposal can be 

obtained from the municipal authorities, the 

Содержание Control MS-L 2x4kW Series

Страница 1: ...e manutenzione pt Manual de Instala o e funcionamento nl Inbouw en bedieningsvoorschriften da Monterings og driftsvejledning sv Monterings och sk tselanvisning fi Asennus ja k ytt ohje el hr Upute za...

Страница 2: ...Fig 1 1 2 3...

Страница 3: ...SSM Alarm GL WSK P2 WSK P1 SL 10 16 15 14 13 12 11 9 8 7 6 5 4 3 2 1 HW T1 1 3 5 13 A1 2 4 6 14 A2 T2 T3 L1 L2 L3 NO L1 L2 L3 N WSK M 3 WSK M 1 T1 1 3 5 13 A1 2 4 6 14 A2 T2 T3 L1 L2 L3 NO ON DIP 1 2...

Страница 4: ...50Hz U brown yellow green pink grey brown black grey blue V W white P1 P2 ON OFF ON NW 16 black brown black grey blue brown 30 15 0 Seconds ON 100 K DIP 1 2 3 4 5 6 7 SSM Alarm GL WSK P2 WSK P1 SL 10...

Страница 5: ...N 100 K DIP 1 2 3 4 5 6 7 SSM Alarm GL WSK P2 WSK P1 SL 10 16 15 14 13 12 11 9 8 7 6 5 4 3 2 1 HW T1 1 3 5 13 A1 2 4 6 14 A2 T2 T3 L1 L2 L3 NO L1 L2 L3 N WSK M 3 WSK M 1 T1 1 3 5 13 A1 2 4 6 14 A2 T2...

Страница 6: ...ry 32 5 Installation 32 5 1 General 32 5 2 Types of installation 32 5 3 Installation 32 5 4 Electrical connection 33 6 Operation and function 36 6 1 Controls 36 6 2 Button lock 37 7 Commissioning 37 7...

Страница 7: ...refers to the switchgear indicated on the title page 1 5 Warranty In general the specifications in the current gen eral terms and conditions apply for the warranty You can find these here www wilo co...

Страница 8: ...les and or insulation the switchgear must be shut down immediately by the operator Tools and other objects should be kept in their designated places so that they can be found quickly The switchgear ma...

Страница 9: ...with buttons 2 LED indicators The switchgear comprises the following main components Main switch for switching the switchgear on off NOTE The S version has no main switch A plug is pre assembled inste...

Страница 10: ...ns connection Installation and operating instructions Variant S Switchgear with connected cable and plug 1 230 V Shockproof plug 3 400 V CEE phase inverter plug with phase inverter Installation and op...

Страница 11: ...must be clean dry and free of vibrations Avoid exposing the switchgear to direct sunlight The customer must provide the power supply cables These must be of sufficient length so that connection to the...

Страница 12: ...by an electrician authorised by the local energy supply company Observe the installation and operating in structions for the connected pump and signal transmitters The mains connection current and vo...

Страница 13: ...ct ed to the earth terminal NOTE With the S version the pump is connected at terminals 2 T1 L 4 T2 N Pump connection 3 400 V Terminals 2 T1 U 4 T2 V 6 T3 W The protective ground conductor PE is con ne...

Страница 14: ...inals 11 12 and 13 of the termi nal strip DANGER due to electrical voltage An external voltage is applied at the terminals for this function This is also present at the terminals when the main switch...

Страница 15: ...ill be emitted independent of the electricity network on power failure An audible constant tone will be emitted as an alarm 1 Place the rechargeable battery in the holder Pay attention to the correct...

Страница 16: ...fault signal relay deactivated during an alarm signal with the Buzzer OFF Reset button Faults cannot be acknowledged nor can the control be released 7 Commissioning POTENTIALLY fatal danger due to ele...

Страница 17: ...direction of rotation and set Observe the wire designations on the wiring diagram when connecting the switchgear and the connected pumps 7 4 1 Checking the direction of rotation The rotation control o...

Страница 18: ...rdingly Ambient operating temperature 30 60 C Air humidity 40 50 Prevent formation of condensate BEWARE of moisture Ingress of moisture will result in damage to the switchgear During standstill time p...

Страница 19: ...ectrician or Wilo Customer Service 9 3 Repair work Prior to repair work the switchgear must be switched off as described under Final shutdown and all power supply cables dismantled Repair work must be...

Страница 20: ...ooting If the points listed here do not rectify the fault contact Wilo Customer Service They can help you as follows Telephone and or written support from Wilo Customer Service On site support from Wi...

Страница 21: ...ung folgenden einschl gigen Bestimmungen entspricht in its delivered state complies with the following relevant provisions est conforme aux dispositions suivants dont il rel ve Niederspannungsrichtlin...

Страница 22: ...Pioneering for You WILO SE Nortkirchenstra e 100 44263 Dortmund Germany T 49 0 231 4102 0 F 49 0 231 4102 7363 wilo wilo com www wilo com...

Отзывы: