1. Basic Information

The MR-Lift device is intended to control a 

pump’s work, depending on the liquid level. The 

main fields of application include:

• Water pumping

• Sewage pumping

• Adjacent sewage pumping stations

• Pressure sewer system

Level can be measured by the use of hydrostat-

ic pressure, external sensor (4–20mA) or float 

switches. The pump is turned on directly by a 

contactor.

States of failure are signalled by the use of three 

relay contacts, a built-in sound alarm, and a con-

trol light on the front panel. The device is set up 

and operated by the use of keys situated on the 

front panel.

The design and specification of the device will 

ensure long and non-failure operation in any 

conditions. All the components used in the 

construction of the electronic system have been 

adjusted to operate in temperatures below zero. 

As a result, the possibility of parameters going 

out of adjustment, even in freezing temperatures, 

has been reduced to a minimum. A high-perfor-

mance switching power supply has been applied 

for powering the electronic system, which allows 

the minimization of the intake of energy required 

for powering the device from the network. The 

use of surface assembly technology allowed the 

creation of a device of compact construction 

which is highly ergonomic in the course of instal-

lation works.

1.1.  General properties

LCD display 2 x 16

• Forced pump operation

• Built-in sound alarm

• Non-potential alarm of high level

Collective failure signalling:

 

potential and non-potential

• Overload protection

• Dry run protection

• Phase detection sensor

• Pump’s current indication

• Indication of liquid level in the tank

• Pump’s work-time meter

• Pump’s start up meter

• Saving failure messages after cutting power 

supply off

• Wireless communication

1.2.  Copyright

This operating and maintenance manual has been 

copyrighted by the manufacturer. The operating 

and maintenance manual is intended for use by 

installation, operating and maintenance person-

nel. It contains technical regulations and drawings 

which may not be reproduced or distributed, 

either in whole or in part, used for purposes of 

competition or shared with third parties. Illustra-

tions may differ from the original and serve only 

as an example illustrations.

1.3. 

Rights of modification

The manufacturer reserves the right to make 

technical modifications to systems or compo

-

nents.

1.4. 

Technical specification

Power consumption:

1.8W

Overvoltage category:

III

Protection rate:

IP 65

Range of work 

temperatures:

-30°C to +50°C

Range of pressure:

0 - 1m of water column

Work voltage

- three-phase work:

- monophase work:

3/N/PE AC 400/230V 50Hz 

1/N/PE AC 230V 50Hz

Max. switched power AC-3

- three-phase work:

- monophase work:

5.0kW

2.7kW

Relay contacts 

load-carrying capacity

- non-potential 

alarm contacts:

- alarm contact 12V DC:

AC1 - 8A / 230V AC 

DC1 - 8A / 24V DC

1.2A

Wireless communication

- standard:

- system transmission 

power: 

ISM 868MHz

25mW e.r.p. 

(ETSI EN 300 220)

Dimensions:

250 x 220 x 118 mm

(W x H x D)

Dimensions with antenna:

265 x 366 x 118 mm

(W x H x D)

1.5.  Control elements

1.5.1.  Control keys

“MANUAL OPERATION” Key

Turns on and off the pump regardless of the level 

of liquid in the tank, in the case of the setting in 

“Work waterless – allowed”. If “Work waterless - 

disallowed” level must be higher than the STOP 

level, otherwise the pump will not start, and the 

display shows the message “Manual operation not 

allowed”. 

The maximum possible operation time in manual 

mode is 2 minutes. After this time, or after a 

power failure the unit will return to the previous 

mode: “0” or “Automatic operation”.

“AUTOMATIC OPERATION” Key

The pump is controlled automatically depending 

on the level of liquid in the tank and the control 

settings. If you press the key again, the pump will 

be switched to the “0” mode.

Содержание Control MR-Lift

Страница 1: ...o nl Inbouw en bedieningsvoorschriften da Monterings og driftsvejledning sv Monterings och sk tselanvisning fi Asennus ja k ytt ohje el hr Upute za ugradnju i uporabu sr Uputstvo za ugradnju i upotreb...

Страница 2: ......

Страница 3: ......

Страница 4: ......

Страница 5: ...fication 6 1 5 Control elements 6 2 Assembly and operation 7 2 1 Assembly 7 2 2 Wiring 7 2 3 Level measurement 8 2 4 Test run without pump 8 2 5 Settings 9 2 6 Additional information 10 3 Troubleshoot...

Страница 6: ...ht This operating and maintenance manual has been copyrighted by the manufacturer The operating and maintenance manual is intended for use by installation operating and maintenance person nel It conta...

Страница 7: ...ly should be turned off Power supply can be turned on after connecting the wires and replacing the terminal cover During operation employees authorized to operate the device can have access to connect...

Страница 8: ...bbles generated by the membrane pump 2 3 1 2 External pressure sensor 4 20mA External two wire sensor must be connected to terminals 30 i 31 The sensor is powered by stabilized voltage of 20V 2 3 2 Fl...

Страница 9: ...o communication High level 9 100 cm When the set level value is exceeded relay contacts of the collective failure report system and high level relay are switched on Minimum current 0 12 A When the pum...

Страница 10: ...values e g minimum current value higher than maximum current value 2 6 3 LCD contrast setting The default contrast setting is optimum and there is usually no need to change it However if such a necess...

Страница 11: ...k exceeded value set in menu Check if the device works in automatic mode or if the pump is not turned off as a result of over temperature overcurrent or a dry run After all check if the delivery pipel...

Страница 12: ...he pump is ready to work again Thermal fault 1 Signal of failure The pump is stopped After the fault is removed the state of failure is deleted au tomatically Acceptable temperature for the pump has b...

Страница 13: ...ing checks at intervals of 6 month 1 Check the state of electrical connections and if necessary tight connection terminals 2 Check the state and sealing of the pressure line 3 If a sparge pipe compres...

Страница 14: ...rev01 Wilopark 1 D 44263 Dortmund DECLARATION OF CONFORMITY KONFORMIT TSERKL RUNG We the manufacturer declare under our sole responsibility that these electronic control panel types of the series Als...

Страница 15: ...EU BASSE TENSION 2014 30 EU COMPATIBILITE ELECTROMAGNETIQUE 2014 53 EU EQUIPEMENTS RADIOELECTRIQUES 2011 65 EU 2015 863 LIMITATION DE L UTILISATION DE CERTAINES SUBSTANCES DANGEREUSES EN 60730 1 2016...

Страница 16: ...altuudet koota tekninen tiedosto on noudattamaan my s seuraavia asiaankuuluvia standardeja WILO SE Group Quality Wilopark 1 D 44263 Dortmund uppfylla einnig eftirfarandi vi eigandi sta la WILO SE Grou...

Страница 17: ...visse farlige stoffer EN 60730 1 2016 EN 60730 2 15 2010 EN 61000 6 2 2005 EN 61000 6 3 2007 A1 2011 EN 300 220 1 V3 1 1 EN 300 220 2 V3 1 1 EN IEC 63000 2018 Vedkommendesom er autorisert til sammens...

Страница 18: ...Smjernica o niskom naponu 2014 30 EU Elektromagnetna kompatibilnost smjernica 2014 53 EU Radio oprema 2011 65 EU 2015 863 ograni enju uporabe odre enih opasnih tvari EN 60730 1 2016 EN 60730 2 15 2010...

Страница 19: ...6 3 2007 A1 2011 EN 300 220 1 V3 1 1 EN 300 220 2 V3 1 1 EN IEC 63000 2018 Oseba poobla ena za sestavo tehni ne datoteke je Mi kot proizvajalci z polno odgovornostjo izjavljamo da te vrste elektronski...

Страница 20: ...Pioneering for You WILO SE Nortkirchenstra e 100 44263 Dortmund Germany T 49 0 231 4102 0 F 49 0 231 4102 7363 wilo wilo com www wilo com...

Отзывы: