11

English

ware, a gate and MR-Lift devices. The controlling 

software can be operated from any computer 

connected to the Internet.  

If there is no signal between MR-Lft and the 

central unit, MR-Lift enters automatic operation 

mode independent from the wireless system and 

the following recurring message appears on the 

display: “No radio communication”. The time du

-

ration after which the device enters the automat-

ic operation mode can be set in the menu. 

If the MR-Lift device is locked by the system 

administrator, the message “Blocked by

administrator” flashes on the display. Unlocking 

can only be done by radio. During the lock, the 

pump can not be started from the panel.

NOTE! 

The sim card used in the gateway must be 

configured in such a way that no PIN code is 

required. In order to configure the sim card cor

-

rectly, please insert it into a mobile phone, go 

to security settings in the mobile phone menu 

and disable prompting for PIN code. The card is 

now ready to be inserted into the gateway.

3.  Troubleshooting

Displayed 

message

Additional 

information

Cause

Solution

High level

• Signal of 

failure

• High level 

relay turned 

on

• Automatic 

deletion of 

the state of 

failure after 

the liquid 

level falls

Level of 

liquid in 

the tank 

exceeded 

value set in 

menu.

Check if the 

device works 

in automatic 

mode or if 

the pump is 

not turned 

off as a 

result of over 

temperature, 

overcurrent 

or a dry 

run. After 

all, check if 

the delivery 

pipeline is 

clogged.

Float switch

High level

• Signal of 

failure

• High level 

relay turned 

on

• Automatic 

deletion of 

the state of 

failure after 

the liquid 

level falls

Level of 

liquid in the 

tank caused 

switching 

on the high 

level float.

If the float 

switch 

has been 

connected 

as additional 

protection to 

the standard 

control sys-

tem, check if 

the message 

“High level” 

is displayed 

at the same 

time. If 

not, check 

how high 

the float 

is hung in 

the tank. In 

other cases 

proceed as in 

the case of 

“High level” 

status.

Float 

switches

Wrong se-

quence

• Signal of 

failure

• State of 

failure saved

Float 

switches 

work in 

the wrong 

sequence.

Check float 

connection, 

then check 

how high 

they are 

hung in the 

tank and if 

they are tan-

gled. Check 

if they are 

not dam-

aged and if 

they switch 

on correctly. 

Delete fail-

ure with the 

“OK”

 key.

Sensor 

4-20mA

disconnect-

ed

• Signal of 

failure

• Automatic 

deletion of 

the state of 

failure after 

the sensor is 

connected

External 

sensor cur-

rent is lower 

than 3mA.

Check ex

-

ternal sensor 

and its 

connecting 

wire.

Overcurrent • A message 

displayed

• The pump 

works

Pump cur-

rent is higher 

than the 

value set for 

“Maximum 

current”.

Turn off the 

pump, check 

the value of 

“Maximum 

current” and 

look for the 

cause of the 

overcurrent.

Содержание Control MR-Lift

Страница 1: ...o nl Inbouw en bedieningsvoorschriften da Monterings og driftsvejledning sv Monterings och sk tselanvisning fi Asennus ja k ytt ohje el hr Upute za ugradnju i uporabu sr Uputstvo za ugradnju i upotreb...

Страница 2: ......

Страница 3: ......

Страница 4: ......

Страница 5: ...fication 6 1 5 Control elements 6 2 Assembly and operation 7 2 1 Assembly 7 2 2 Wiring 7 2 3 Level measurement 8 2 4 Test run without pump 8 2 5 Settings 9 2 6 Additional information 10 3 Troubleshoot...

Страница 6: ...ht This operating and maintenance manual has been copyrighted by the manufacturer The operating and maintenance manual is intended for use by installation operating and maintenance person nel It conta...

Страница 7: ...ly should be turned off Power supply can be turned on after connecting the wires and replacing the terminal cover During operation employees authorized to operate the device can have access to connect...

Страница 8: ...bbles generated by the membrane pump 2 3 1 2 External pressure sensor 4 20mA External two wire sensor must be connected to terminals 30 i 31 The sensor is powered by stabilized voltage of 20V 2 3 2 Fl...

Страница 9: ...o communication High level 9 100 cm When the set level value is exceeded relay contacts of the collective failure report system and high level relay are switched on Minimum current 0 12 A When the pum...

Страница 10: ...values e g minimum current value higher than maximum current value 2 6 3 LCD contrast setting The default contrast setting is optimum and there is usually no need to change it However if such a necess...

Страница 11: ...k exceeded value set in menu Check if the device works in automatic mode or if the pump is not turned off as a result of over temperature overcurrent or a dry run After all check if the delivery pipel...

Страница 12: ...he pump is ready to work again Thermal fault 1 Signal of failure The pump is stopped After the fault is removed the state of failure is deleted au tomatically Acceptable temperature for the pump has b...

Страница 13: ...ing checks at intervals of 6 month 1 Check the state of electrical connections and if necessary tight connection terminals 2 Check the state and sealing of the pressure line 3 If a sparge pipe compres...

Страница 14: ...rev01 Wilopark 1 D 44263 Dortmund DECLARATION OF CONFORMITY KONFORMIT TSERKL RUNG We the manufacturer declare under our sole responsibility that these electronic control panel types of the series Als...

Страница 15: ...EU BASSE TENSION 2014 30 EU COMPATIBILITE ELECTROMAGNETIQUE 2014 53 EU EQUIPEMENTS RADIOELECTRIQUES 2011 65 EU 2015 863 LIMITATION DE L UTILISATION DE CERTAINES SUBSTANCES DANGEREUSES EN 60730 1 2016...

Страница 16: ...altuudet koota tekninen tiedosto on noudattamaan my s seuraavia asiaankuuluvia standardeja WILO SE Group Quality Wilopark 1 D 44263 Dortmund uppfylla einnig eftirfarandi vi eigandi sta la WILO SE Grou...

Страница 17: ...visse farlige stoffer EN 60730 1 2016 EN 60730 2 15 2010 EN 61000 6 2 2005 EN 61000 6 3 2007 A1 2011 EN 300 220 1 V3 1 1 EN 300 220 2 V3 1 1 EN IEC 63000 2018 Vedkommendesom er autorisert til sammens...

Страница 18: ...Smjernica o niskom naponu 2014 30 EU Elektromagnetna kompatibilnost smjernica 2014 53 EU Radio oprema 2011 65 EU 2015 863 ograni enju uporabe odre enih opasnih tvari EN 60730 1 2016 EN 60730 2 15 2010...

Страница 19: ...6 3 2007 A1 2011 EN 300 220 1 V3 1 1 EN 300 220 2 V3 1 1 EN IEC 63000 2018 Oseba poobla ena za sestavo tehni ne datoteke je Mi kot proizvajalci z polno odgovornostjo izjavljamo da te vrste elektronski...

Страница 20: ...Pioneering for You WILO SE Nortkirchenstra e 100 44263 Dortmund Germany T 49 0 231 4102 0 F 49 0 231 4102 7363 wilo wilo com www wilo com...

Отзывы: