English

Additional 

work

0 - 120 s

After the liquid level falls 

below the set value “STOP 

Level”, the pump will work 

for a period of time speci-

fied here.

Wait time 

comm.

1 - 30 min No communication time. 

Time after which the 

device enters automatic 

operation when no com-

munication is present.

24h-5s work

enabled

After 24 hours standby 

the pump is automatically 

turned on for 5 seconds in 

order to lubricate bearings.

disabled

Sound alarm

enabled

Failure is reported by an 

internal sound signalling 

device.

disabled

Pulsing alarm

enabled

The failure report relay is 

turned on every second. It 

can be used for supplying 

power to an external signal 

lamp.

disabled

In the case of failure the 

relay is switched on perma-

nently.

Therm.protect1 enabled

Set to “disabled” if thermal 

protection contacts have 

not been connected to 

terminals 20, 21.

disabled

Work waterless allowed

The pump can be start-

ed even if the liquid level 

in the tank is below the 

value at which the pump is 

turned off.

disallowed The pump cannot be start-

ed if the liquid level in the 

tank is below the value at 

which the pump is turned 

off. This parameter should 

be set in case of hazard of 

explosion.

Phase control

enabled

The phase monitoring 

system protects the pump 

against non-uniform volt-

age or incorrect order of 

phases, and detects con-

tactor failure. In the case of 

a single-phase pump, set 

to “disabled”.

disabled

Language

polish, english, german, czech

2.6.  Additional information

2.6.1.  Setting level values

The MR-Lift prevents the setting of unacceptable 

levels values, e.g. the value of the level at which 

the pump is turned off higher than the respec-

tive level of turning it on. Minimum difference 

between level settings is 3 cm.

2.6.2.  Setting current values

The MR-Lift prevents the setting of unacceptable 

current values, e.g. minimum current value higher 

than maximum current value.

2.6.3.  LCD contrast setting

The default contrast setting is optimum, and 

there is usually no need to change it. However, 

if such a necessity occurs, the following action 

should be taken:

1. Turn off the device.

2. Press and hold the keys “

MANUAL OPERATION

” 

and 

“AUTOMATIC OPERATION”

 at the same time.

3.

Turn on the device – the message “Contrast” will 

be displayed.

4. Set required value with navigation keys.

5. Release the pressed keys 

“MANUAL OPERATION”

and 

“AUTOMATIC OPERATION”

.

2.6.4.  Calibration of internal level sensor

After long use the indications of the internal level 

sensor may stop being accurate.  In such a case, 

even if there is no pressure, indication of level 

may be other than zero. In order to calibrate the 

sensor proceed as follows:

1. Turn off the device.

2. Press and hold the keys 

“MANUAL OPERATION”

and “

AUTOMATIC OPERATION

” at the same time.

3.

Turn on the device – the message “Contrast” will 

be displayed.

4. Press the acceptance key 

“OK”

 - the message 

“Internal sensor calibrated” will be displayed.

5. Release the pressed keys “

MANUAL OPERATION

” 

and “

AUTOMATIC OPERATION

”.

It is recommended to calibrate the sensor at each 

technical review.

NOTE!

Before you start to calibrate the level sensor, 

raise the bell over the water surface.

2.6.5.  Settings lock

To avoid making changes to the settings by unau-

thorized persons, the MR-Lift is equipped with a 

lock function. 

If the settings lock is on, when you try to change 

settings, the display shows the message “Settings 

locked”. 

To activate the settings lock, press and hold the 

“OK”

 key and press “

MANUAL OPERATION

” 

key (the display shows the message „Settings 

locked”). To disable the lock must repeat the 

above procedure (the display shows the message 

„Settings unlocked”).

Locking and unlocking can be activated only in 

the home screen mode.

2.6.6.  Wireless communication

MR-Lift operation is controlled by means of a 

radio communication system in ISM 868MHz 

standard. The system consists of controlling soft-

Содержание Control MR-Lift

Страница 1: ...o nl Inbouw en bedieningsvoorschriften da Monterings og driftsvejledning sv Monterings och sk tselanvisning fi Asennus ja k ytt ohje el hr Upute za ugradnju i uporabu sr Uputstvo za ugradnju i upotreb...

Страница 2: ......

Страница 3: ......

Страница 4: ......

Страница 5: ...fication 6 1 5 Control elements 6 2 Assembly and operation 7 2 1 Assembly 7 2 2 Wiring 7 2 3 Level measurement 8 2 4 Test run without pump 8 2 5 Settings 9 2 6 Additional information 10 3 Troubleshoot...

Страница 6: ...ht This operating and maintenance manual has been copyrighted by the manufacturer The operating and maintenance manual is intended for use by installation operating and maintenance person nel It conta...

Страница 7: ...ly should be turned off Power supply can be turned on after connecting the wires and replacing the terminal cover During operation employees authorized to operate the device can have access to connect...

Страница 8: ...bbles generated by the membrane pump 2 3 1 2 External pressure sensor 4 20mA External two wire sensor must be connected to terminals 30 i 31 The sensor is powered by stabilized voltage of 20V 2 3 2 Fl...

Страница 9: ...o communication High level 9 100 cm When the set level value is exceeded relay contacts of the collective failure report system and high level relay are switched on Minimum current 0 12 A When the pum...

Страница 10: ...values e g minimum current value higher than maximum current value 2 6 3 LCD contrast setting The default contrast setting is optimum and there is usually no need to change it However if such a necess...

Страница 11: ...k exceeded value set in menu Check if the device works in automatic mode or if the pump is not turned off as a result of over temperature overcurrent or a dry run After all check if the delivery pipel...

Страница 12: ...he pump is ready to work again Thermal fault 1 Signal of failure The pump is stopped After the fault is removed the state of failure is deleted au tomatically Acceptable temperature for the pump has b...

Страница 13: ...ing checks at intervals of 6 month 1 Check the state of electrical connections and if necessary tight connection terminals 2 Check the state and sealing of the pressure line 3 If a sparge pipe compres...

Страница 14: ...rev01 Wilopark 1 D 44263 Dortmund DECLARATION OF CONFORMITY KONFORMIT TSERKL RUNG We the manufacturer declare under our sole responsibility that these electronic control panel types of the series Als...

Страница 15: ...EU BASSE TENSION 2014 30 EU COMPATIBILITE ELECTROMAGNETIQUE 2014 53 EU EQUIPEMENTS RADIOELECTRIQUES 2011 65 EU 2015 863 LIMITATION DE L UTILISATION DE CERTAINES SUBSTANCES DANGEREUSES EN 60730 1 2016...

Страница 16: ...altuudet koota tekninen tiedosto on noudattamaan my s seuraavia asiaankuuluvia standardeja WILO SE Group Quality Wilopark 1 D 44263 Dortmund uppfylla einnig eftirfarandi vi eigandi sta la WILO SE Grou...

Страница 17: ...visse farlige stoffer EN 60730 1 2016 EN 60730 2 15 2010 EN 61000 6 2 2005 EN 61000 6 3 2007 A1 2011 EN 300 220 1 V3 1 1 EN 300 220 2 V3 1 1 EN IEC 63000 2018 Vedkommendesom er autorisert til sammens...

Страница 18: ...Smjernica o niskom naponu 2014 30 EU Elektromagnetna kompatibilnost smjernica 2014 53 EU Radio oprema 2011 65 EU 2015 863 ograni enju uporabe odre enih opasnih tvari EN 60730 1 2016 EN 60730 2 15 2010...

Страница 19: ...6 3 2007 A1 2011 EN 300 220 1 V3 1 1 EN 300 220 2 V3 1 1 EN IEC 63000 2018 Oseba poobla ena za sestavo tehni ne datoteke je Mi kot proizvajalci z polno odgovornostjo izjavljamo da te vrste elektronski...

Страница 20: ...Pioneering for You WILO SE Nortkirchenstra e 100 44263 Dortmund Germany T 49 0 231 4102 0 F 49 0 231 4102 7363 wilo wilo com www wilo com...

Отзывы: