Installation and operating instructions • Wilo-Control EC-L • Ed.04/2022-09
43
To use the ModBus interface, the settings must be changed in the following menus:
Fig. 65:
Menu 2.01
Menu no.
2.01
Description
ModBus RTU interface On/Off
Value range
on, off
Factory setting
off
Fig. 66:
Menu 2.02
Menu no.
2.02
Description
Baud rate
Value range
9600; 19200; 38400; 76800
Factory setting
19200
Fig. 67:
Menu 2.03
Menu no.
2.03
Description
Slave address
Value range
1 … 254
Factory setting
10
Fig. 68:
Menu 2.04
Menu no.
2.04
Description
Parity
Value range
none, even, odd
Factory setting
even
Fig. 69:
Menu 2.05
Menu no.
2.05
Description
Number of stop bits
Value range
1; 2
Factory setting
1
8.5.5
Menu 3: Enable pumps
To operate the system, the operating mode must be set for each pump and the pumps en-
abled:
•
Every pump is set to the “auto” operating mode as the factory setting.
•
Automatic mode starts after the pumps have been enabled in menu 3.01.
NOTICE! Required settings for the initial configuration.
During the initial configuration, a direction of rotation check must be performed on the
pumps and the motor current monitoring set exactly. Use the following settings to perform
the initial configuration:
•
Switch off the pumps: Set menu 3.02 to 3.04 to “off”.