Installation and operating instructions • Wilo-Control EC-L • Ed.04/2022-09
37
Fig. 46:
Menu 5.58
Menu no.
5.58
Software version: All
Description
Collective run signal (SBM) function
Value range
on, run
Factory setting
run
Explanation
A run signal for the switchgear or attached pump can sent via a
separate output:
•
“on”: Switchgear ready for operation
•
“run”: At least one pump is running.
Fig. 47:
Menu 5.59
Menu no.
5.59
Software version: All
Description
Collective fault signal (SSM) function
Value range
fall, raise
Factory setting
raise
Explanation
In case of an error, a general fault message can be sent via a
separate output:
•
“fall”: The relay drops out.
Optionally, this function can be used for controlling the
mains voltage supply.
•
“raise”: The relay picks up.
Fig. 48:
Menu 5.62
Menu no.
5.62
Software version: All
Description
Dry-running protection delay
Value range
0 … 180 s
Factory setting
0 s
Explanation
Time until the pump are deactivated after reaching the dry run
level.
Fig. 49:
Menu 5.64
Menu no.
5.64
Software version: All
Description
Ex-mode On/Off (only available in the “drain” operating mode!)
Value range
on, off
Factory setting
off
Explanation
The following functions are adjusted when the Ex-mode is ac-
tivated (on):
•
Follow-up times
All follow-up times are ignored and the pumps switched off
immediately!
•
Dry-running level (by level sensor or dynamic pressure bell)
The following actions are only possible once the “All pumps
off” fill level has been exceeded:
–
Reactivation of the pumps
–
Resetting the error message
•
Alarm dry-running protection (via float switch)
Alarm manual reset (anti-reactivation lock)!
•
Alarm thermal motor monitoring
Alarm manual reset (anti-reactivation lock)!
Observe the additional requirements in the chapter on explos-
ive atmospheres in the appendix!