Fig. 61:
Menu 1.14
Menu no.
1.14
Software version: All
Description
Level peak-load pump 1 on
Value range
0.06 ... 12.5 m (
NOTICE! The actual value range is dependent
on the setting in menu 5.09.)
Factory setting
0.42 m
Explanation
“Drain” operating mode: The value must be 0.03 m
higher
than
the “Peak-load pump 1 On” level (menu 1.15). The switch-on
level must be
greater than/equal to
the switch-on level of the
base-load pump (menu 1.12).
“Fill” operating mode: The value must be 0.03 m
lower
than the
“Peak-load pump 1 Off” level (menu 1.15). The switch-on level
must be
lower than/equal to
the switch-on level of the base-
load pump (menu 1.12).
NOTICE! The menu item is only visible if the value “Level” or
“Bell” have been set in menu 5.07.
Fig. 62:
Menu 1.15
Menu no.
1.15
Software version: All
Description
Peak-load pump 1 Off level
Value range
0.06 ... 12.5 m (
NOTICE! The actual value range is dependent
on the setting in menu 5.09.)
Factory setting
0.25 m
Explanation
“Drain” operating mode: The value must be 0.03 m
lower
than
the “Peak-load pump 1 On” level (menu 1.14). The switch-off
level must be
greater than/equal to
the switch-on level of the
base-load pump (menu 1.13).
“Fill” operating mode: The value must be 0.03 m
higher
than
the “Peak-load pump 1 On” level (menu 1.14). The switch-off
level must be
lower than/equal to
the switch-off level of the
base-load pump (menu 1.13).
NOTICE! The menu item is only visible if the value “Level” or
“Bell” have been set in menu 5.07.
Fig. 63:
Menu 1.16
Menu no.
1.16
Software version: All
Description
Peak-load pump 2 On level
Value range
0.06 ... 12.5 m (
NOTICE! The actual value range is dependent
on the setting in menu 5.09.)
Factory setting
0.42 m
Explanation
“Drain” operating mode: The value must be 0.03 m
higher
than
the “Peak-load pump 2 Off” level (menu 1.17). The switch-on
level must be
greater than/equal to
the switch-on level of the
peak-load pump (menu 1.14).
“Fill” operating mode: The value must be 0.03 m
lower
than the
“Peak-load pump 2 Off” level (menu 1.17). The switch-on level
must be
lower than/equal to
the switch-on level of the peak-
load pump (menu 1.14).
NOTICE! The menu item is only visible if the value “Level” or
“Bell” have been set in menu 5.07.