en
28
Installation and operating instructions • Wilo-Control EC-L • Ed.04/2022-09
Level measurement with level sensor or dynamic pressure bell
5
2
1
3
4
6
7*
8*
Fig. 25:
Illustration of the switching points
with a level sensor in the “drain” operating
mode using the example of two pumps
1
Pump 1 On
2
Pump 1 Off
3
Pump 2 On
4
Pump 2 Off
5
Dry-running level
6
High water level
7
High water level*
8
Dry-running level*
* Also implemented via a separate float switch for increased operational reliability.
A level sensor or dynamic pressure bell can be connected. This can be used to control three
pumps:
•
Pump 1 On/Off
•
Pump 2 On/Off
•
Pump 3 On/Off
•
Dry-running level
•
High water level
7.2.2
“Fill” operating mode
The reservoir is filled up, for instance, to pump water into a rainwater storage tank. The
pumps are activated when the level falls and switched off when the level rises. This control
is mainly used for
water supply
.
Level control for float switch or electrodes
Extern OFF
4
5
3
1
2
Fig. 26:
Illustration of the switching points
with a float switch or electrodes in the “fill”
operating mode using the example of one
pump
1
Pump On
2
Pump OFF
3
High water level
4
Min. water level
5
Dry-running level in the well
Up to a maximum of six float switches or electrodes can be connected. This can be used to
control two pumps:
•
Pump 1 On
•
Pump 2 On
•
Pump 1 and 2 Off
•
Min. water level in the tank to be filled
•
High water level
•
Dry-running level in the well (separate float switch at the “Extern OFF” input)
The float switch should be equipped with a NO contact: Once the switching point has been
reached, the contact is closed.