6 Set up the sensor with the display and adjustment module
WIKA Operating Instructions - Differential pressure transmitter DPT-20
Caution:
During simulation, the simulated value is output as digital signal.
The status message along with the Asset Management function is "
Maintenance
".
Note:
Without manual deactivation, the sensor terminates the simulation
automatically after 60 minutes.
6.5.4 Additional adjustments
In this menu item, you adjust the internal clock of the sensor. There is
no adjustment for summer/winter (daylight saving) time.
After a reset, certain parameter adjustments made by the user are
reset.
The following reset functions are available:
Delivery status:
Restores the parameter settings at the time of
shipment from the factory, incl. the order-specific settings. Any user-
defined linearisation curve as well as the measured value memory are
deleted.
Basic settings:
Resets the parameter settings, incl. special param
-
eters, to the default values of the respective instrument. Any pro
-
grammed linearisation curve as well as the measured value memory
are deleted.
Totalizer 1 and 2:
Reset of the summarized flow volumes with ap
-
plication "Flow"
The following table shows the default values of the instrument. De
-
pending on the instrument version or application, all menu items may
not be available or some may be differently assigned:
Setup
Menu item
Parameter
Default value
Application
Application
Level
Slave for electronic differ
-
ential pressure
Deactivated
Units
Unit of measurement
mbar (with nominal measuring range ≤ 400 mbar)
bar (with nominal measuring ranges ≥ 1 bar)
Temperature unit
°C
Position correction
0.00 bar
Date/Time
Reset