4 Mounting
WIKA Operating Instructions - Differential pressure transmitter DPT-20
Note:
Follow the mounting instructions of the respective manufacturer and
seal the thread, e.g. with PTFE tape.
Valve blocks are used for initial shut-off when connecting the differ
-
ential pressure transmitter to the process. They are also used for pres
-
sure compensation of the measuring chambers during adjustment.
3-fold and 5-fold valve blocks are available (see chapter "
Mounting
and connection instructions
").
Free openings on the process assembly must be closed by ventilation
valves or closing screws. Required torque see chapter "
Technical
data
".
Note:
Use the supplied parts and seal the thread with four layers of PTFE
tape.
4.4 Mounting and connection instructions
When connecting DPT-20 to the measuring point, take note of the
high/low pressure side of the process component.
1)
.
The "
H
" identifies the high pressure side, the low pressure side due
to an "
L
" on the process component next to the oval flanges.
Note:
The static pressure is measured on the low pressure side "
L
".
2
1
H L
Fig. 9: Marking for high/low pressure side on the process component
1 H = High pressure side
2 L = Low pressure side
Valve blocks
Ventilation valves, closing
screws
Connection high/low
pressure side
1)
The pressure effective on "H" is considered as positive, the pressure effec
-
tive on "L" as negative in the calculation of the pressure difference.