Basics and Assembly
Wieland Electric GmbH | BA000941 | 01/2014 (Rev. A)
15
1
2
3
•
For mounting turn the locking lever of the module to be mounted upwards.
•
To mount the module put it to the gap between the both modules and push it,
guided by the stripes at both sides, to the mounting rail.
•
Turn the locking lever downward again.
•
Plug again the electronic module, which you have removed before.
4
5
6
Bus interface and power module of a head module may not be separeted! Here you may
only exchange the electronic module!
•
Remove if exists the wiring of the head module. More about this may be found at
"Wiring".
•
Press the unlocking lever at the lower side of the just mounted right module and
pull it forward.
•
Turn all the locking lever of the head module to be exchanged upwards.
•
Pull the head module forward.
1
2
•
For mounting turn all the locking lever of the head module to be mounted upwards.
Exchange of a head
module (e. g. bus
coupler)