Digital Output
Wieland Electric GmbH | BA000941 | 01/2014 (Rev. A)
47
Total current per group, horizontal
configuration, 40°C
4 A
Total current per group, horizontal
configuration, 60°C
4 A
Total current per group, vertical
configuration
4 A
Output current at signal "1", rated value
0.5 A
Output delay of "0" to "1"
30 µs
Output delay of "1" to "0"
175 µs
Minimum load current
--
Lamp load
10 W
Parallel switching of outputs for redundant
control of a load
not possible
Parallel switching of outputs for increased
power
not possible
Actuation of digital input
Switching frequency with resistive load
max. 1000 Hz
Switching frequency with inductive load
max. 0.5 Hz
Switching frequency on lamp load
max. 10 Hz
Internal limitation of inductive shut-off
voltage
L+ (-52 V)
Short-circuit protection of output
yes, electronic
Trigger level
1 A
Number of operating cycle of relay outputs
--
Switching capacity of contacts
--
Output data size
8 Bit
Status information, alarms, diagnostics
Status display
green LED per channel
Interrupts
no
Process alarm
no
Diagnostic interrupt
no
Diagnostic functions
no
Diagnostics information read-out
none
Module state
green LED
Module error display
red SF LED
Channel error display
none
Isolation
Between channels
--
Between channels of groups to
--
Between channels and backplane bus
Insulation tested with
DC 500 V
Safety
Safety protocol
--
Safety requirements
--
Secure user address
--
Watchdog
--
Two channels
--
Test pulse outputs
--
Circuit monitoring
--
Datasizes
Input bytes
0
Output bytes
1
Parameter bytes
0
Diagnostic bytes
0
Housing
Material
PPE / PPE GF10
Mounting
Profile rail 35 mm
Mechanical data
Dimensions (WxHxD)
12.9 x 109 x 76.5 mm
Weight
60 g
Environmental conditions
Operating temperature
0 °C to 60 °C
Storage temperature
-25 °C to 70 °C