Basics and Assembly
Wieland Electric GmbH | BA000941 | 01/2014 (Rev. A)
17
3
4
•
Turn all the locking lever downward againg.
•
Plug againg the electronic module, which you have removed before.
5
3.5
Wiring
Terminals with spring clamp technology are used for wiring. The spring clamp technology
allows quick and easy connection of your signal and supply lines.
In contrast to screw terminal connections this type of connection is vibration proof.
10mm
U
max
: 240 V AC / 30 V DC
I
max
: 10 A
Cross section: 0,08 mm
2
… 1,5 mm
2
(AWG 28 … 16)
Stripping length: 10 mm
•
Insert a suited screwdriver at an angel into the square opening as shown (step 1).
Press and hold the screwdriver in the opposite direction to open the contact spring.
•
Insert the stripped end of wire into the round opening (step 2). You can use wires
with a cross section of 0.08 mm² to 1.5 mm².
•
By removing the screwdriver, the wire is securely fixed via the spring contact to the
terminal (step 3).
Connectors
Data
Wiring
procedure
Standard wiring
1
2
3