Digital Output
48
Wieland Electric GmbH | BA000941 | 01/2014 (Rev. A)
Certifications
UL508 certification
yes
5.6
ricos
FLEX 2xDO DC 30 V 3 A RELAY
The electronic module accepts binary control signals from the central bus system and
transfers them to the process level via relay outputs. It has 2 channels that operate as
switches and the status of each channel is monitored via LEDs.
•
2 relay outputs, isolated to the backplane bus
•
DC 30 V / AC 230 V, 3 A
•
Status indication of the channels via LEDs
1
3
5
4
6
7
8
9
2
[1] Locking lever terminal module
[2] Labeling strip
[3] Backplane bus
[4] LED status indication
[5] DC 24 V power section supply
[6] Electronic module
[7] Terminal module
[8] Locking lever electronic module
[9] Terminal
LED
Color
Description
RUN
green
RUN
MF
MF
red
●
○
Bus communication is OK
Module status is OK
●
●
Bus communication is OK
Module status reports an error
○
●
Bus communication is not possible
Module status reports an error
○
○
Error at bus power supply
☼
☼
Error in configuration (see Basics)
DO x
green
●
Relay output is set
on:
●
off:
○
blinks with 2 Hz:
☼
When using inductive load please take a suitable protector (see installation guidelines).
For wires with a cross section of 0,08 mm
2
up to 1,5 mm
2
.
2
6
3
7
4
8
1
5
1
2
3
4
5
6
7
8
DC 24V
0V
4
8
3
7
0
2
6
1
5
DO
1
..AC 230V
..DC 30V
3A
..AC 230V
..DC 30V
3A
Description
Properties
Structure
Status
indication
RUN
MF
DO 0
DO 1
NOTE
Pin assignment