5
Feeding into a power bus segment and power tapping
26
Wieland Electric GmbH | BA000369 (Rev. B) | 02/2016
5.4
Connection modules
The permanently connected
podis
®
CON connection module is used for both feeding into the power bus
and as a tap for supplying permanently connected devices. Furthermore, the connection module is used
for connection of two power bus segments. The module is electrically connected to the flat cable through
insulation-piercing termination. All 7 cores are connected through so that all voltage levels are available.
The coding of the cable avoids twisting.
The permanent connection of the connection module and the flat cable via the inserted seal also provides
strain relief.
Item No.
Image
Description
75.018.0051.2
Connecting module FCS 4 7 SI FK
Connection module, 7-pin, 20A; 277/480V 4kV/3 (VDE); protection class IP65;
insulation-piercing termination, connection of 1.5…6 mm² finely stranded/solid
through spring terminals; 4 predetermined breaking points (2xM20, 2xM25); black.
99.801.4866.1
Connecting module FCS 4 7 SI FK FM
with rapid assembly panel for mounting inside basket trays; 7-pin, 20 A; 277/480 V
4 kV/3 (VDE); 600 V (UL, CSA); protection class IP65; insulation-piercing termina-
tion; connection of 1.5…6 mm² finely stranded/single-wire through spring termi-
nals.
75.010.0053.1
Distributor module FCS 4 7 SA SA SW
Distributor module FCS 4 7 SA SA; 7-pin 32 A; 7 x 32 A (VDE) and/or 7 x 30 A
(UL/CSA); 500 V 6 kV/3 (VDE) and/or 600 V (UL/CSA) with double level terminal
strips, 5 predetermined breaking points, 3 x
podis
®
-
flat cable, 2 x round conduc-
tors M20/M25; black.
The distributor module 75.010.0053.1 is used for feeding into the flat cable, but also for distributing the
power to multiple flat cables. The distributor module is equipped with connection options for three flat
cables and one round conductor. Two round conductors can be routed through the housing, for example
for one 5-core 400 V cable through cable gland M25 and one 2-core 24V cable through cable gland M20.
Flat cables and round conductors are connected to the distributor module with screw terminals.
The cable bushing Z5.563.6553.1, see accessories, is available for routing the flat cable to the distributor
module.
5.5
Flat cable outlet, pluggable (power tap)
The
podis
®
CON flat cable outlet is the connection interface (power tap) on the power bus for supplying
the pluggable devices. The flat cable outlet is electrically connected to the flat cable through insulation-
piercing termination. All 7 cores are connected through so that all voltage levels are available. This allows
for the insertion of motor starters, CEE sockets, grounded sockets and LED lights on a socket. Functional
modules and plugs can be connected in a powered state. The coding of the cable and connector makes
twisting of the flat cable outlet impossible. The permanent connection of the connection module and the
flat cable via the inserted seal also provides strain relief.
DANGER
•
Contact between the connection module and the cable must be established in an unpowered state.
DANGER
•
Contact between the connection module and the cable must be established in an unpowered state.