Deployment
Wieland Electric GmbH | BA001269 | 09/2021 (Rev. A)
42
Parameters
Here you can change the current parameters of the
ricos
FLEX BC MODBUS.
Parameters
Data type Range
Default
value
Description
Link monitoring
BOOL
TRUE/FALSE
FALSE
Link monitoring Ethernet
Communication
timeout [ms]
UINT_32
•
0 … 30000
0
Timeout Ethernet communication
Socket timeout
[ms]
UNIT 32
•
0 … 30000
0
Timeout Modbus socket connection
IO cycle [µs]
UINT_32
•
0
•
1000
•
2000
•
4000
•
8000
•
10000
1000
ricos
FLEX bus cycle
•
Link monitoring
o
As soon as both Ethernet cables are pulled with enabled
Link monitoring
, the com-
munication is finished by the
ricos
FLEX BC MODBUS, BASP (
B
efehls-
A
usgabe-
S
perre, i.e. command output disable) is activated and this is indicated with flash-
ing SB LED.
Link monitoring
reacts only when both Ethernet cables are pulled.
•
Communication timeout
o
At
Communication Timeout [ms]
you can specify a timeout value for Ethernet com-
munication in ms.
o
If there is no Modbus communication for the specified time, BASP is set on the
ri-
cos
FLEX bus.
o
With the value 0, you can deactivate the time monitoring.
•
IO cycle
o
With
IO cycle
, you can specify the cycle for the
ricos
FLEX bus within which the I/O
image is to be refreshed.
o
With the value 0 you can set the maximum possible cycle time (no delay).
•
Socket timeout
o
At Socket Timeout [ms] you can specify a timeout value for the Modbus socket
connection in ms.
o
If there is no Modbus communication on a specific Modbus socket connection for
the specified time, the corresponding socket is closed.
o
With the value 0, you can deactivate the time monitoring.
Diagnosis
•
Configuration State: Deviations between the setpoint and actual configuration are shown
here (OK: no deviation).
•
Diagnosis Entries: Here all pending diagnostic messages are shown.
•
Diagnosis Buffer: Here the content of the diagnostics buffer is listed.
Security
All functions for the writing access to the Ethernet coupler can be secured by a password.
IP
Here you may assign to your Ethernet coupler IP address data. For valid IP address data please con-
tact your system administrator.
Firmware
Information about the firmware.