Deployment
Wieland Electric GmbH | BA001269 | 09/2021 (Rev. A)
55
Write n words and Read m words 17h
Code 17h: This function allows to write n words to the master output area 4x and read m words from
the master input area 3x with one request.
Command telegram
Modbus/TCP-
Header
Slave ad-
dress
Function
code
Read
address
Read
number
words
Write
address
Write
number
words
Write
number
bytes
Write
data
1. word
Write
data
2. word
…
x x 0 0 0
6 byte
1 byte
1 byte
1 word 1 word 1 word 1 word
1 byte
1 word 1 word
max. 122 words
Respond telegram
Modbus/TCP-Header Slave ad-
dress
Function
code
Number of
read bytes
Data 1.
word
Data 2.
word
…
x x 0
6 byte
1 byte
1 byte
1 byte
1 word
1 word
max. 126 words