Hardware description
Wieland Electric GmbH | BA001269 | 09/2021 (Rev. A)
18
PWR
green
SF
red
MT
yellow
SB
green
MB
green
SPD
green
L/A(1/2)
green
Description
Operating modes (see 6.2 Operating modes, p. 37)
x
x
x
Init
x
2 Hz
2 Hz
x
x
x
DHCP discovery
x
2 Hz
x
x
x
Update config
x
x
x
Run
1 Hz
x
x
x
Commissioning
x
x
x
x
Maintenance
1 Hz
1 Hz
x
x
x
Firmware update
1
2 Hz
x
x
x
Error
Operation
x
x
x
x
x
x
The Ethernet coupler is power supplied.
x
x
2 Hz
The Ethernet coupler communicates without error
via Ethernet.
x
x
x
x
x
The Ethernet coupler is ready for Modbus/TCP com-
munication.
x
x
x
x
x
No Modbus/TCP communication is possible.
x
x
2 Hz
x
x
x
BASP (
B
efehls-
A
usgabe-
S
perre i.e. command output
disable) is activated
x
x
There is no physical connection to Ethernet.
x
x
x
2 Hz
x
x
Configuration is in progress.
x
5 Hz
x
x
x
x
Ethernet coupler is located, the identification was in-
itiated by the user and takes 10 s.
x
x
x
x
x
Speed: 100 Mbit/s
Error: Power OFF-ON required
x:
not relevant
off