33740-9-1015
Page 21
33740-9-1015
Page 20
Begin the vent system installation by selecting the type of venting
to be installed and the path that it will take. Verify that clearances
are met throughout the path of the venting system.
Determine how the vent system will be terminated out the side of
the house or through the roof. Verify clearances for the termination.
When selecting a vent system for use with the fireplace, refer to the
“Vent Fireplace” section in this manual to determine what systems
are acceptable. Check all clearances and venting components.
Identify problems existing in the vent system, if any. Use pages 20
to 27 for venting to eliminate issues after installation. Check pipe
diameter on vent system and fireplace to verify the size is the same.
NOTICE
: All outer connection joints must be sealed with
aluminum tape, screws or silicone sealant rated above
300°F/149°C. The inner flue joints do not require any sealant.
Figure 29
FLASHING
STORM
COLLAR
VERTICAL
TERMINATION
(THREE 90°
ELBOWS MAX)
WALL
THIMBLE
HORIZONTAL
TERMINATION
(THREE 90°
ELBOWS MAX)
90° ELBOW
OR
45° ELBOW
90° ELBOW
CEILING
FIRE STOP
WALL STRAP
PIPE LENGTH
VENT SYSTEM IDENTIFICATION
VENT SYSTEMS
The following vent systems are acceptable:
Simpson Duravent® GS 5” - 8”
American Metal Products 5” - 8”
Selkirk Direct-Temp® 5” - 8”
Security Secure Vent® 5” - 8”
Excel DV Venting 5” - 8”
BDM 5”-8”
VENTING FIREpLACE
HARD ELBOW DIMENSIONS
A1
B
C
D
57-1/2”
5-5/16”
7-5/16”
10-5/8”
Figure 30
NOTE: THE A1 HOLE LOCATION DIMENSION IS FOR THROUGH
THE WALL HORIZONTAL INSTALLATIONS WITH 90
°
ELBOW
AND 12 INCH RISE OFF TOp OF FIREpLACE
Allowable A2 and E dimensions to be determined by consult-
ing the venting graph and horizontal venting termination
examples on pages 22 and 23.
positioning the Fireplace
Determine the exact position of the appliance so the direct vent
termination will be centered (if possible) between two studs. This
will avoid any extra framing. All vent kit pipes should be assembled
on the unit after the unit is moved into the final position.
Cutting the Hole
After the fireplace has been positioned in its permanent location,
the hole through the exterior wall of the house can be cut. This hole
must be 12-5/8 inches high x 10-5/8 inches wide with its location
determined by the amount of vertical rise and horizontal run of the
termination.
See Figure 30.
When locating the hole it must be noted
that the bottom of the cap must be 12 inches minimum above the
ground level, or average snowfall, and top of the cap must be no
less than 18 inches below a combustible projection and no closer
than 9 inches to any wall running parallel to vent termination.
Below Grade Installation
When it is not possible to meet the required vent termination clearances
of 12 inches above grade level, a snorkel kit is recommended. It
allows installation depth down to 7 inches below grade level. The
7 inches is measured from the center of the horizontal vent pipe as
it penetrates through the wall.
Ensure the sidewall venting clearances are observed. If venting
system is installed below ground, we recommend a window
well with adequate and proper drainage to be installed around
the termination area.
TYpICAL BASEMENT INSTALLATION
Figure 31