NOTE: The DPIH insulation kit is not supplied with this product 
and should be purchased separately. See the following chart for 
the correct DPIH kit.

The following describes converting to “Horizontal Left-Hand.” 
Conversion to downflow must be performed in an area that 
allows access to all sides prior to placing the air handler in its 
final location.

Horizontal Left-Hand Conversion

1. Remove the 3 air handler access panels.

2. Remove the “J” shaped bracket that retains the evaporator 

coil.

3. Remove the flowrator from the lower left side access panel 

and slide out the evaporator coil and horizontal drain pan.

4. Remove the gasket from the horizontal pan drain 

connections.

5. Remove the oval shaped plastic plug from the left side 

access panel. 

6. Remove the oval shaped rubber gasket seal from the lower 

right side access panel.

7. The drain connections for the horizontal pan are sealed with a 

thin coating of plastic. Knock out this plastic seal with a 
screwdriver and hammer. 

NOTE: The upper drain will become the secondary drain 
which is mandatory in many municipalities.

8. Install the plastic plug removed in Step 5 to the right side 

lower access panel and the oval shaped rubber gasket to the 
lower left access panel.

9. Reinstall the evaporator coil with the horizontal panel on the 

left side. 

NOTE: Push the assembly completely to the rear to ensure 
the engagement of the upflow pan with the rear channel 
bracket.

10. Install the “J” bracket removed in Step 2 to support the 

upflow pan to the tie channel.

11.  Attach all panels and the metering device.

Achieving 2% Low Leakage Rate

Ensure that the Neoprene gasket with PSA remains intact on all 
surfaces that the access panels are secured to. These surfaces 
are the entire length of the wrapper and areas between the upper 
tie plate, upper and lower access panels. Check that the upper 
access panel breaker insert gasket is intact and that the flowrator 
gasket is installed on the lower access panel. An additional drain 
hole cover is required.

Install Condensate Drain

The air handler is provided with 

³⁄₄

" (1.9 cm) NPT condensate 

drain connections.

A field-fabricated secondary drain pan, with a drainpipe to the 
outside of the building, is required in all installations over a 
finished living space or in any area that may be damaged by 
overflow from the main drain pan. In some localities, local codes 
may require a secondary drain pan for any horizontal installation.

Make sure the air handler is level so that the drain pan will empty 
completely.

1. Remove the appropriate drain knockouts. See “Installation 

Configurations.” You may need to remove the indoor coil 
assembly from the cabinet.

2. Remove any web from inside any threaded drain pan hole to 

which a drain line is to be connected. Gently remove the web 
so as not to damage the coil.

3. Connect the primary drain line connection to the primary 

drain pan connection. The primary drain connection is flush 
with the bottom of the inside of the pan. The secondary 
connection is raised above the bottom of the inside of the 
pan. 

NOTE: When making drain fitting connections to the drain 
pan, hand tighten. Using a sealant is recommended. 
Overtightening the fittings can split connections on the drain 
pan.

4. Secondary drain connections, if used, should be connected 

to a separate drainage system. Run the secondary drain line 
to a place where the occupant would notice water coming 
from the secondary drain.

5. Install a 3" (7.6 cm) trap in both the primary and secondary 

drain lines as close to the unit as practical. Make sure the top 
of the trap is below the connection to the drain pan to allow 
complete drainage of the pan.

NOTE: Horizontal runs must also have an anti-siphon air vent 
(standpipe) installed ahead of the horizontal run. See “Typical 
Condensate Drain Connection” in this section. An extremely 
long horizontal run may require an oversized drain line to 
eliminate the trapping of air.

WVAHM or WAHMS Model

Insulation Kit

1824

DPI18-32

3030/1931/3636

DPI36-42

3642/3743/4860/4961

DPI48-61

A. DPIH kit
B. Secondary drain

C. Primary drain

A B C

Goodman 2

If secondary drain is not installed, the secondary access 
must be plugged.

CAUTION

Содержание WAHME

Страница 1: ... Heating Electric Heat Only 19 Heating Heat Pump 19 AIR HANDLER MAINTENANCE 19 ASSISTANCE OR SERVICE 20 Accessories 20 Whirlpool Models WAHMS WAHME WPIO 355B Goodman 1 Hazards or unsafe practices could result in property damage product damage severe personal injury or death Hazards or unsafe practices may result in property damage product damage personal injury or death WARNING CAUTION Goodman 9 H...

Страница 2: ...he air handler cabinet conforms to 2 percent or less air leakage Goodman 34 WARNING To avoid property damage personal injury or death due to electrical shock this unit MUST have an uninterrupted unbroken electrical ground The electrical ground circuit may consist of an appropriately sized electrical wire connecting the ground lug in the unit control box to the building electrical service panel Oth...

Страница 3: ...r plenum or be installed with a return air plenum under the air handler Louvers or return air grilles are field supplied Local codes may limit the application of systems without a duct return to single story buildings For an air handler installed in a closet with a louvered return opening the minimum open area for the louvers will be as shown below If the free area is not known assume a 25 free ar...

Страница 4: ...should be the same size as the flanged opening provided around the blower outlet and should extend ideally at least 36 91 4 cm from the air handler before turning or branching off plenum into duct runs The plenum forms an extension of the blower housing and minimizes air expansion losses from the blower INSTALLATION INSTRUCTIONS InspectShipment These air handlers are completely factory assembled a...

Страница 5: ...ary drain is clogged See Install Condensate Drain When an evaporator coil is installed in an attic or above a finished ceiling an auxiliary drain pan should be provided under the air handler as specified by most local building codes Suspended Cabinet Installation NOTE Air handlers cannot be installed horizontally lying on or suspended from either the front or back of the air handler It must be pos...

Страница 6: ... channel bracket 11 To avoid possible condensate blow off the insulation retainers are to be laid into the evaporator coil pan as shown in the Evaporator Coil Pan illustration Evaporator Coil Pan To complete the conversion slide the evaporator coil into the chassis and attach the 3 access panels Evaporator Coil NOTE When the air handler is converted to the downflow position the coil may protrude a...

Страница 7: ...al drain hole cover is required InstallCondensateDrain The air handler is provided with 1 9 cm NPT condensate drain connections A field fabricated secondary drain pan with a drainpipe to the outside of the building is required in all installations over a finished living space or in any area that may be damaged by overflow from the main drain pan In some localities local codes may require a seconda...

Страница 8: ...it has the correct orifice installed 2 If a change of the orifice is required loosen the brass hex nut and separate the orifice extension stub from the brass hex fitting 3 Remove the orifice with an orifice extractor tool 4 Insert the proper orifice into the fitting seal end first Make sure the orifice is free to move in the fitting 5 Replace the brass hex nut NOTE Overtightening the brass hex nut...

Страница 9: ... Heat trap or wet rags should be used to protect heat sensitive components such as service valves and TXV valves 1 Loosen the nut one turn only to allow high pressure tracer gas to escape No gas indicates a possible leak 2 After the gas has escaped remove the nut and discard the black or brass cap 3 Remove the check piston to verify it is correct and then replace the piston See the piston kit char...

Страница 10: ...ature Rise tables to determine the temperature rise ºF ºC Temperature Rise Table ºF 230 1 60 Supply Voltage Goodman 34 WARNING To avoid property damage personal injury or death due to electrical shock this unit MUST have an uninterrupted unbroken electrical ground The electrical ground circuit may consist of an appropriately sized electrical wire connecting the ground lug in the unit control box t...

Страница 11: ...4 32 0 48 8 9 1 200 8 13 3 13 10 6 17 8 3 20 6 7 27 2 8 40 4 4 53 11 7 59 15 1 400 7 13 9 11 11 7 14 10 17 8 3 23 5 34 1 1 46 7 8 51 10 6 1 600 6 14 4 10 12 2 13 10 6 15 9 4 20 6 7 30 1 1 40 4 4 44 6 7 1 800 6 14 4 9 12 8 11 11 7 13 10 6 18 7 8 27 2 8 36 2 2 39 3 9 2 000 5 15 8 13 3 10 12 2 12 11 1 16 8 9 24 4 4 32 0 35 1 7 CFM Heat Kit Nominal kW ºF ºC 3 16 1 5 15 6 14 4 8 13 3 10 12 2 15 9 4 20 ...

Страница 12: ...se property damage personal injury or death Room Thermostat W Y G R R G W Y R To Condensing Unit 24V Connections 18 Gauge 2 Wires Blue White Green Red Unit 18 Gauge 4 Wires With Cooling 3 Wires Without Cooling Contactor Coil To Comfort Alert Module If Used W2 W Y G R R G Y W Room Thermostat 18 Gauge 4 Wire With Cooling 3 Wire Without Cooling Outdoor Thermostat Optional Unit Red Green White Brown B...

Страница 13: ... ALL power before servicing Multiple power sources may be present Failure to do so may cause property damage personal injury or death C W2 O Y R R BR G W R Y W Y O C W2 G R E Heat Pump Conventional Room Thermostat 18 Gauge 7 Wire Unit Red Green White Blue BU 18 Gauge 5 Wire BU OR See Note 3 Outdoor Thermostat Optional Closed on Temperature Fall 18 Gauge 6 Wire Needed When Outdoor Thermostat Is Use...

Страница 14: ...nnecting Y1 will result in 1st stage cooling blower speed and may cause the contactor to chatter NOTES 1 Outdoor Thermostat 1 OT 1 should be the first to close and the last to open 2 Jumper W1 and W2 together if OT 2 is not used 3 Remove this wire when using an outdoor thermostat 4 EHR Emergency heat relay optional 5 OT Outdoor thermostat optional Goodman 6 Long HIGH VOLTAGE WARNING Disconnect ALL...

Страница 15: ...connect ALL power before servicing Multiple power sources may be present Failure to do so may cause property damage personal injury or death Y G W W2 R C W1 W2 Y2 Y1 O G R TB Y BU BU Y G R W Y BR BR BR Y Outdoor Thermostat Optional Close on Temperature Fall Condensing Unit 24V Connection Contactor Coil Room Thermostat ASPF Unit See Note 18 Gauge 5 Wire With Cooling 4 Wire Without Cooling To Comfor...

Страница 16: ...l Goodman 6 Long HIGH VOLTAGE WARNING Disconnect ALL power before servicing Multiple power sources may be present Failure to do so may cause property damage personal injury or death G C R C W1 W2 Y2 Y1 O G R TB 18 Gauge 7 Wire O Y C W2 R Y O W2 E R G BU OR Y Y BU OR W BR W BU W W R BR R W G Y OR OR R OR Heat Pump Room Thermostat ASPF Unit 18 Gauge 5 Wire 18 Gauge 7 Wire Needed When 2 Outdoor Therm...

Страница 17: ... instructions for system start up instructions and refrigerant charging instructions Pre Start Check Is the air handler properly located level secure and serviceable Has an auxiliary pan been provided under the air handler with a separate drain for the air handlers installed above a finished ceiling or in any installation where condensate overflow could cause damage Have all the webs been removed ...

Страница 18: ...apacity WVAHM WAHMS Motor Motor Speed Adjustment The motors in all WVAHM and WAHMS motors are multi speed PSC motors The color of the wire coming from the motor to the COM terminal on the control board defines in which speed the motor will operate The black wire represents high speed the red wire represents low speed and the blue wire select models only represents medium speed To change speeds rem...

Страница 19: ...uit R and G energizes the blower relay starting the indoor blower motor If the room temperature should continue to fall the circuit between R and W 1 is completed by the 2nd stage heat room thermostat Circuit R W 1 energizes a heat sequencer relay The completed circuit will energize supplemental electric heat if available Units with a second heat sequencer relay can be connected with the first seq...

Страница 20: ...rive Jacksonville FL 32258 Please include a daytime phone number in your correspondence Accessories To order accessories contact your Whirlpool Home Cooling and Heating dealer WPIO 355B 2009 All rights reserved Registered Trademark TM Trademark of Whirlpool U S A Manufactured under license by Tradewinds Distributing Company LLC Jacksonville Florida 8 09 Printed in U S A ...

Отзывы: