background image

3

Do not remove the cabinet knockouts until it has been 
determined which knockouts will need to be removed for the 
installation. 

Select the final installation position which best suits the site 
conditions. Consider required clearances, space, routing 
requirements for refrigerant line, condensate disposal, filters, 
ductwork, wiring, and accessibility for service. Refer to the air 
handler rating plate on the air handler for specific information. 

Tools and Parts

Gather the required tools and parts before starting installation. 
Read and follow the instructions provided with any tools listed 
here.

Tools Needed

Parts Needed

Check local codes, check existing electrical supply, and read 
“Ductwork Requirements” and “Electrical Requirements” before 
purchasing parts.

System Requirements

The air handler is designed to match, and must be used with 
outdoor units as rated. The indoor units are manufactured with an 
interchangeable refrigerant metering orifice to provide optimum 
refrigerant control and system performance with a variety of 
different capacities of outdoor units.

In some cases, the rating of the outdoor unit may require that the 
air handler coil assembly orifice be changed to obtain rated 
performance.

Location Requirements

NOTE: When used on cooling applications, excessive sweating 
may occur when the air handler is installed in a very humid 
space.

If the air handler is installed in an unconditioned space, 
sealant should be applied around the electrical wires, 
refrigerant tubing, and condensate lines where they enter the 
cabinet.

Electrical wires should be sealed on the inside where they exit 
the conduit opening. Sealant is required to avoid air leakage 
and condensate from forming inside the air handler, control 
box, and on the electrical controls.

The air handler must be installed in such a way as to allow 
free access to the coil/filter compartment and blower/control 
compartment.

The air handler must be installed in a level position to ensure 
proper condensate drainage.

Installation Clearances

Non-Duct Return Closet Installation

The air handler can be installed in a closet with a false bottom to 
form a return air plenum or be installed with a return air plenum 
under the air handler.

Louvers or return air grilles are field supplied. Local codes may 
limit the application of systems without a duct return to single-
story buildings.

For an air handler installed in a closet with a louvered return 
opening, the minimum open area for the louvers will be as 
shown below.

If the free area is not known, assume a 25% free area for 
wood louvers or a 75% free area for metal louvers or grilles.

Using the louver dimensions and the 25% or 75% 
assumption, determine if the louver open area meets the 
minimum open area listed in the previous chart.

If the return air plenum is used, the return air grille should be 
immediately in front of the opening in the plenum to allow for 
the free flow of return air.

When the air handler is not installed in front of the opening, 
there must be adequate clearance around the air handler to 
allow for the free flow of return air.

The unit clearance from a combustible surface may be 0". 

Allow a minimum of 24" (61 cm) in front of the unit for service 
clearance.

Do not install the air handler in a location that violates the 
instructions provided with the condenser.

If the unit is located in an area with high ambient temperature 
and/or high humidity, the air handler may have condensation 
on the casing. On these installations, a wrap of 2" (5.1 cm) 
fiberglass insulation with a vapor barrier is recommended.

Consult all appropriate regulatory codes prior to determining 
final clearances. 

When installing this unit in an area that may become wet, 
elevate the unit with a sturdy, non-porous material.

In installations that may lead to physical damage (for 
example. in a garage) it is recommended that a barrier be 
installed to avoid such damage.

¹⁄₄

" nut driver

Level

Screwdriver

Adjustable wrench

Tape measure

Hammer

Sealant

UL-Listed wire connectors

Replacement orifice (if needed). See “Verify Orifice Size.” The 
correct orifice size may be contained in the replacement 
orifice package located inside the control box of the outdoor 
unit. If this package does not contain the correct orifice for 
your air handler, you must purchase the correct orifice size. 

18" and 24" (45.7 cm and 
61 cm) models

320 sq. in. (2,065 cm

2

)

30" and 36" (76.2 cm and 
91.4 cm) models

360 sq. in. (2,323 cm

2

)

42", 48" and 60" (106.7 cm, 
121.9 cm and 152.4 cm) models

450 sq. in. (2,903 cm

2

)

Содержание WAHME

Страница 1: ... Heating Electric Heat Only 19 Heating Heat Pump 19 AIR HANDLER MAINTENANCE 19 ASSISTANCE OR SERVICE 20 Accessories 20 Whirlpool Models WAHMS WAHME WPIO 355B Goodman 1 Hazards or unsafe practices could result in property damage product damage severe personal injury or death Hazards or unsafe practices may result in property damage product damage personal injury or death WARNING CAUTION Goodman 9 H...

Страница 2: ...he air handler cabinet conforms to 2 percent or less air leakage Goodman 34 WARNING To avoid property damage personal injury or death due to electrical shock this unit MUST have an uninterrupted unbroken electrical ground The electrical ground circuit may consist of an appropriately sized electrical wire connecting the ground lug in the unit control box to the building electrical service panel Oth...

Страница 3: ...r plenum or be installed with a return air plenum under the air handler Louvers or return air grilles are field supplied Local codes may limit the application of systems without a duct return to single story buildings For an air handler installed in a closet with a louvered return opening the minimum open area for the louvers will be as shown below If the free area is not known assume a 25 free ar...

Страница 4: ...should be the same size as the flanged opening provided around the blower outlet and should extend ideally at least 36 91 4 cm from the air handler before turning or branching off plenum into duct runs The plenum forms an extension of the blower housing and minimizes air expansion losses from the blower INSTALLATION INSTRUCTIONS InspectShipment These air handlers are completely factory assembled a...

Страница 5: ...ary drain is clogged See Install Condensate Drain When an evaporator coil is installed in an attic or above a finished ceiling an auxiliary drain pan should be provided under the air handler as specified by most local building codes Suspended Cabinet Installation NOTE Air handlers cannot be installed horizontally lying on or suspended from either the front or back of the air handler It must be pos...

Страница 6: ... channel bracket 11 To avoid possible condensate blow off the insulation retainers are to be laid into the evaporator coil pan as shown in the Evaporator Coil Pan illustration Evaporator Coil Pan To complete the conversion slide the evaporator coil into the chassis and attach the 3 access panels Evaporator Coil NOTE When the air handler is converted to the downflow position the coil may protrude a...

Страница 7: ...al drain hole cover is required InstallCondensateDrain The air handler is provided with 1 9 cm NPT condensate drain connections A field fabricated secondary drain pan with a drainpipe to the outside of the building is required in all installations over a finished living space or in any area that may be damaged by overflow from the main drain pan In some localities local codes may require a seconda...

Страница 8: ...it has the correct orifice installed 2 If a change of the orifice is required loosen the brass hex nut and separate the orifice extension stub from the brass hex fitting 3 Remove the orifice with an orifice extractor tool 4 Insert the proper orifice into the fitting seal end first Make sure the orifice is free to move in the fitting 5 Replace the brass hex nut NOTE Overtightening the brass hex nut...

Страница 9: ... Heat trap or wet rags should be used to protect heat sensitive components such as service valves and TXV valves 1 Loosen the nut one turn only to allow high pressure tracer gas to escape No gas indicates a possible leak 2 After the gas has escaped remove the nut and discard the black or brass cap 3 Remove the check piston to verify it is correct and then replace the piston See the piston kit char...

Страница 10: ...ature Rise tables to determine the temperature rise ºF ºC Temperature Rise Table ºF 230 1 60 Supply Voltage Goodman 34 WARNING To avoid property damage personal injury or death due to electrical shock this unit MUST have an uninterrupted unbroken electrical ground The electrical ground circuit may consist of an appropriately sized electrical wire connecting the ground lug in the unit control box t...

Страница 11: ...4 32 0 48 8 9 1 200 8 13 3 13 10 6 17 8 3 20 6 7 27 2 8 40 4 4 53 11 7 59 15 1 400 7 13 9 11 11 7 14 10 17 8 3 23 5 34 1 1 46 7 8 51 10 6 1 600 6 14 4 10 12 2 13 10 6 15 9 4 20 6 7 30 1 1 40 4 4 44 6 7 1 800 6 14 4 9 12 8 11 11 7 13 10 6 18 7 8 27 2 8 36 2 2 39 3 9 2 000 5 15 8 13 3 10 12 2 12 11 1 16 8 9 24 4 4 32 0 35 1 7 CFM Heat Kit Nominal kW ºF ºC 3 16 1 5 15 6 14 4 8 13 3 10 12 2 15 9 4 20 ...

Страница 12: ...se property damage personal injury or death Room Thermostat W Y G R R G W Y R To Condensing Unit 24V Connections 18 Gauge 2 Wires Blue White Green Red Unit 18 Gauge 4 Wires With Cooling 3 Wires Without Cooling Contactor Coil To Comfort Alert Module If Used W2 W Y G R R G Y W Room Thermostat 18 Gauge 4 Wire With Cooling 3 Wire Without Cooling Outdoor Thermostat Optional Unit Red Green White Brown B...

Страница 13: ... ALL power before servicing Multiple power sources may be present Failure to do so may cause property damage personal injury or death C W2 O Y R R BR G W R Y W Y O C W2 G R E Heat Pump Conventional Room Thermostat 18 Gauge 7 Wire Unit Red Green White Blue BU 18 Gauge 5 Wire BU OR See Note 3 Outdoor Thermostat Optional Closed on Temperature Fall 18 Gauge 6 Wire Needed When Outdoor Thermostat Is Use...

Страница 14: ...nnecting Y1 will result in 1st stage cooling blower speed and may cause the contactor to chatter NOTES 1 Outdoor Thermostat 1 OT 1 should be the first to close and the last to open 2 Jumper W1 and W2 together if OT 2 is not used 3 Remove this wire when using an outdoor thermostat 4 EHR Emergency heat relay optional 5 OT Outdoor thermostat optional Goodman 6 Long HIGH VOLTAGE WARNING Disconnect ALL...

Страница 15: ...connect ALL power before servicing Multiple power sources may be present Failure to do so may cause property damage personal injury or death Y G W W2 R C W1 W2 Y2 Y1 O G R TB Y BU BU Y G R W Y BR BR BR Y Outdoor Thermostat Optional Close on Temperature Fall Condensing Unit 24V Connection Contactor Coil Room Thermostat ASPF Unit See Note 18 Gauge 5 Wire With Cooling 4 Wire Without Cooling To Comfor...

Страница 16: ...l Goodman 6 Long HIGH VOLTAGE WARNING Disconnect ALL power before servicing Multiple power sources may be present Failure to do so may cause property damage personal injury or death G C R C W1 W2 Y2 Y1 O G R TB 18 Gauge 7 Wire O Y C W2 R Y O W2 E R G BU OR Y Y BU OR W BR W BU W W R BR R W G Y OR OR R OR Heat Pump Room Thermostat ASPF Unit 18 Gauge 5 Wire 18 Gauge 7 Wire Needed When 2 Outdoor Therm...

Страница 17: ... instructions for system start up instructions and refrigerant charging instructions Pre Start Check Is the air handler properly located level secure and serviceable Has an auxiliary pan been provided under the air handler with a separate drain for the air handlers installed above a finished ceiling or in any installation where condensate overflow could cause damage Have all the webs been removed ...

Страница 18: ...apacity WVAHM WAHMS Motor Motor Speed Adjustment The motors in all WVAHM and WAHMS motors are multi speed PSC motors The color of the wire coming from the motor to the COM terminal on the control board defines in which speed the motor will operate The black wire represents high speed the red wire represents low speed and the blue wire select models only represents medium speed To change speeds rem...

Страница 19: ...uit R and G energizes the blower relay starting the indoor blower motor If the room temperature should continue to fall the circuit between R and W 1 is completed by the 2nd stage heat room thermostat Circuit R W 1 energizes a heat sequencer relay The completed circuit will energize supplemental electric heat if available Units with a second heat sequencer relay can be connected with the first seq...

Страница 20: ...rive Jacksonville FL 32258 Please include a daytime phone number in your correspondence Accessories To order accessories contact your Whirlpool Home Cooling and Heating dealer WPIO 355B 2009 All rights reserved Registered Trademark TM Trademark of Whirlpool U S A Manufactured under license by Tradewinds Distributing Company LLC Jacksonville Florida 8 09 Printed in U S A ...

Отзывы: