background image

2

IMPORTANT: The United States Environmental Protection 
Agency (EPA) has issued various regulations regarding the 
introduction and disposal of refrigerants in this unit. Failure to 
follow these regulations may harm the environment and can lead 
to the imposition of substantial fines. These regulations may vary 
by jurisdiction. A certified technician must perform the installation 
and service of this product. Should questions arise, contact your 
local EPA office.

This product is designed and manufactured to permit installation 
in accordance with national codes. It is the installer’s 
responsibility to install this unit in accordance with national codes 
and/or prevailing local codes and regulations.

INSTALLATION REQUIREMENTS

These instructions are intended as a general guide only for use by 
qualified persons and do not supersede any national or local 
codes in any way. Compliance with all local, state, or national 
codes pertaining to this type of equipment should be determined 
prior to installation.

Read this entire instruction manual, as well as the instructions 
supplied in separate equipment, before starting the installation.

All models are designed for indoor installation only.

The installation of the air handler, field wiring, warm air ducts, etc. 
must conform to the requirements of the National Electrical 
Code, ANSI/NFPA No. 70 (latest edition) in the United States, and 
any state laws, and local ordinances (including plumbing or 
wastewater codes). Local authorities having jurisdiction should 
be consulted before installation is made. Such applicable 
regulations or requirements take precedence over the general 
instructions in this manual.

Install the conditioned air plenum, ducts and air filters (not 
provided) in accordance with NFPA 90B Standard for the 
Installation of Warm Air Heating and Air-Conditioning Systems 
(latest edition).

The air handler is provided with flanges for the connection of the 
plenum and ducts.

Air filters (not provided) must be listed as Class 2 furnace air 
filters.

The air handler can be used with R-410A from the factory.

The air handler is shipped from the factory completely 
assembled. Some models are configured for upflow air discharge 
only, and some models are configured for upflow or horizontal 
left-hand air discharge. The air handler cabinet conforms to 
2 percent or less air leakage.

Goodman 34

WARNING

To avoid property damage, personal injury or death due to 
electrical shock, this unit MUST have an uninterrupted, 
unbroken electrical ground. The electrical ground circuit 
may consist of an appropriately sized electrical wire 
connecting the ground lug in the unit control box to the 
building electrical service panel.
Other methods of grounding are permitted if performed
in accordance with the National Electric Code (NEC) 
/American National Standards Institute (ANSI) /National 
Fire Protection Association (NFPA) 70 and local/state 
codes. In Canada, electrical grounding is to be in 
accordance with the Canadian Electric Code (CSA) C22.1.

Goodman 35

When installing or servicing this equipment, safety
clothing, including hand and eye protection, is strongly 
recommended. If installing in an area that has special 
safety requirements (hard hats, etc.), observe these 
requirements.

CAUTION

Goodman 36

WARNING

Do not connect to or use any device that is not design-
certified for use with this unit. Serious property damage, 
personal injury, reduced unit performance and/or hazardous 
conditions may result from the use of such non-approved 
devices.

Goodman 37

WARNING

To prevent the risk of property damage, personal injury, or
death, do not store combustible materials or use gasoline 
or other flammable liquids or vapors in the vicinity of this 
unit.

Goodman 38

CARBON MONOXIDE POISONING HAZARD

Special Warning for Installation of Furnace or Air Handling 
Units in Enclosed Areas such as Garages, Utility Rooms or 
Parking Areas. 

Carbon monoxide producing devices (such as an 
automobile, space heater, gas water heater, etc.) should 
not be operated in enclosed areas such as unventilated 
garages, utility rooms or parking areas because of the 
danger of carbon monoxide (CO) poisoning resulting from 
the exhaust emissions. If a furnace or air handler is 
installed in an enclosed area such as a garage, utility room 
or parking area and a carbon monoxide producing device is 
operated therein, there must be adequate, direct outside
ventilation.
This ventilation is necessary to avoid the danger of CO 
poisoning which can occur if a carbon monoxide producing 
device continues to operate in the enclosed area. Carbon 
monoxide emissions can be (re)circulated throughout the 
structure if the furnace or air handler is operating in any
mode.

CO can cause serious illness including permanent brain 
damage or death.

DANGER

Содержание WAHME

Страница 1: ... Heating Electric Heat Only 19 Heating Heat Pump 19 AIR HANDLER MAINTENANCE 19 ASSISTANCE OR SERVICE 20 Accessories 20 Whirlpool Models WAHMS WAHME WPIO 355B Goodman 1 Hazards or unsafe practices could result in property damage product damage severe personal injury or death Hazards or unsafe practices may result in property damage product damage personal injury or death WARNING CAUTION Goodman 9 H...

Страница 2: ...he air handler cabinet conforms to 2 percent or less air leakage Goodman 34 WARNING To avoid property damage personal injury or death due to electrical shock this unit MUST have an uninterrupted unbroken electrical ground The electrical ground circuit may consist of an appropriately sized electrical wire connecting the ground lug in the unit control box to the building electrical service panel Oth...

Страница 3: ...r plenum or be installed with a return air plenum under the air handler Louvers or return air grilles are field supplied Local codes may limit the application of systems without a duct return to single story buildings For an air handler installed in a closet with a louvered return opening the minimum open area for the louvers will be as shown below If the free area is not known assume a 25 free ar...

Страница 4: ...should be the same size as the flanged opening provided around the blower outlet and should extend ideally at least 36 91 4 cm from the air handler before turning or branching off plenum into duct runs The plenum forms an extension of the blower housing and minimizes air expansion losses from the blower INSTALLATION INSTRUCTIONS InspectShipment These air handlers are completely factory assembled a...

Страница 5: ...ary drain is clogged See Install Condensate Drain When an evaporator coil is installed in an attic or above a finished ceiling an auxiliary drain pan should be provided under the air handler as specified by most local building codes Suspended Cabinet Installation NOTE Air handlers cannot be installed horizontally lying on or suspended from either the front or back of the air handler It must be pos...

Страница 6: ... channel bracket 11 To avoid possible condensate blow off the insulation retainers are to be laid into the evaporator coil pan as shown in the Evaporator Coil Pan illustration Evaporator Coil Pan To complete the conversion slide the evaporator coil into the chassis and attach the 3 access panels Evaporator Coil NOTE When the air handler is converted to the downflow position the coil may protrude a...

Страница 7: ...al drain hole cover is required InstallCondensateDrain The air handler is provided with 1 9 cm NPT condensate drain connections A field fabricated secondary drain pan with a drainpipe to the outside of the building is required in all installations over a finished living space or in any area that may be damaged by overflow from the main drain pan In some localities local codes may require a seconda...

Страница 8: ...it has the correct orifice installed 2 If a change of the orifice is required loosen the brass hex nut and separate the orifice extension stub from the brass hex fitting 3 Remove the orifice with an orifice extractor tool 4 Insert the proper orifice into the fitting seal end first Make sure the orifice is free to move in the fitting 5 Replace the brass hex nut NOTE Overtightening the brass hex nut...

Страница 9: ... Heat trap or wet rags should be used to protect heat sensitive components such as service valves and TXV valves 1 Loosen the nut one turn only to allow high pressure tracer gas to escape No gas indicates a possible leak 2 After the gas has escaped remove the nut and discard the black or brass cap 3 Remove the check piston to verify it is correct and then replace the piston See the piston kit char...

Страница 10: ...ature Rise tables to determine the temperature rise ºF ºC Temperature Rise Table ºF 230 1 60 Supply Voltage Goodman 34 WARNING To avoid property damage personal injury or death due to electrical shock this unit MUST have an uninterrupted unbroken electrical ground The electrical ground circuit may consist of an appropriately sized electrical wire connecting the ground lug in the unit control box t...

Страница 11: ...4 32 0 48 8 9 1 200 8 13 3 13 10 6 17 8 3 20 6 7 27 2 8 40 4 4 53 11 7 59 15 1 400 7 13 9 11 11 7 14 10 17 8 3 23 5 34 1 1 46 7 8 51 10 6 1 600 6 14 4 10 12 2 13 10 6 15 9 4 20 6 7 30 1 1 40 4 4 44 6 7 1 800 6 14 4 9 12 8 11 11 7 13 10 6 18 7 8 27 2 8 36 2 2 39 3 9 2 000 5 15 8 13 3 10 12 2 12 11 1 16 8 9 24 4 4 32 0 35 1 7 CFM Heat Kit Nominal kW ºF ºC 3 16 1 5 15 6 14 4 8 13 3 10 12 2 15 9 4 20 ...

Страница 12: ...se property damage personal injury or death Room Thermostat W Y G R R G W Y R To Condensing Unit 24V Connections 18 Gauge 2 Wires Blue White Green Red Unit 18 Gauge 4 Wires With Cooling 3 Wires Without Cooling Contactor Coil To Comfort Alert Module If Used W2 W Y G R R G Y W Room Thermostat 18 Gauge 4 Wire With Cooling 3 Wire Without Cooling Outdoor Thermostat Optional Unit Red Green White Brown B...

Страница 13: ... ALL power before servicing Multiple power sources may be present Failure to do so may cause property damage personal injury or death C W2 O Y R R BR G W R Y W Y O C W2 G R E Heat Pump Conventional Room Thermostat 18 Gauge 7 Wire Unit Red Green White Blue BU 18 Gauge 5 Wire BU OR See Note 3 Outdoor Thermostat Optional Closed on Temperature Fall 18 Gauge 6 Wire Needed When Outdoor Thermostat Is Use...

Страница 14: ...nnecting Y1 will result in 1st stage cooling blower speed and may cause the contactor to chatter NOTES 1 Outdoor Thermostat 1 OT 1 should be the first to close and the last to open 2 Jumper W1 and W2 together if OT 2 is not used 3 Remove this wire when using an outdoor thermostat 4 EHR Emergency heat relay optional 5 OT Outdoor thermostat optional Goodman 6 Long HIGH VOLTAGE WARNING Disconnect ALL...

Страница 15: ...connect ALL power before servicing Multiple power sources may be present Failure to do so may cause property damage personal injury or death Y G W W2 R C W1 W2 Y2 Y1 O G R TB Y BU BU Y G R W Y BR BR BR Y Outdoor Thermostat Optional Close on Temperature Fall Condensing Unit 24V Connection Contactor Coil Room Thermostat ASPF Unit See Note 18 Gauge 5 Wire With Cooling 4 Wire Without Cooling To Comfor...

Страница 16: ...l Goodman 6 Long HIGH VOLTAGE WARNING Disconnect ALL power before servicing Multiple power sources may be present Failure to do so may cause property damage personal injury or death G C R C W1 W2 Y2 Y1 O G R TB 18 Gauge 7 Wire O Y C W2 R Y O W2 E R G BU OR Y Y BU OR W BR W BU W W R BR R W G Y OR OR R OR Heat Pump Room Thermostat ASPF Unit 18 Gauge 5 Wire 18 Gauge 7 Wire Needed When 2 Outdoor Therm...

Страница 17: ... instructions for system start up instructions and refrigerant charging instructions Pre Start Check Is the air handler properly located level secure and serviceable Has an auxiliary pan been provided under the air handler with a separate drain for the air handlers installed above a finished ceiling or in any installation where condensate overflow could cause damage Have all the webs been removed ...

Страница 18: ...apacity WVAHM WAHMS Motor Motor Speed Adjustment The motors in all WVAHM and WAHMS motors are multi speed PSC motors The color of the wire coming from the motor to the COM terminal on the control board defines in which speed the motor will operate The black wire represents high speed the red wire represents low speed and the blue wire select models only represents medium speed To change speeds rem...

Страница 19: ...uit R and G energizes the blower relay starting the indoor blower motor If the room temperature should continue to fall the circuit between R and W 1 is completed by the 2nd stage heat room thermostat Circuit R W 1 energizes a heat sequencer relay The completed circuit will energize supplemental electric heat if available Units with a second heat sequencer relay can be connected with the first seq...

Страница 20: ...rive Jacksonville FL 32258 Please include a daytime phone number in your correspondence Accessories To order accessories contact your Whirlpool Home Cooling and Heating dealer WPIO 355B 2009 All rights reserved Registered Trademark TM Trademark of Whirlpool U S A Manufactured under license by Tradewinds Distributing Company LLC Jacksonville Florida 8 09 Printed in U S A ...

Отзывы: