background image

18

Have all cabinet openings and wiring been sealed?

Is the indoor coil orifice sized correct?

Have all unused orifice replacement parts and packaging 
been disposed of/recycled?

Is the filter clean, in place, and of adequate size?

Is the wiring neat, correct, and in accordance with the wiring 
diagram?

Is the air handler properly grounded and fused?

Is the thermostat correctly wired and in a good location?

Are all access panels in place and secure?

Check Blower Operation

1. Set the thermostat to FAN ON.

2. The indoor blower should come on.

Check Electric Heater (If Used)

1. Set the thermostat to call for auxiliary heat (approximately 5°F 

above ambient temperature). The indoor blower and auxiliary 
heat should come on together. Allow a minimum of 3 minutes 
for all sequencers to cycle on.

2. Set the thermostat so it does not call for heat. Allow up to 

5 minutes for all sequencers to cycle off.

Check Airflow

Cooling Blower Speed

For proper cooling operation, the airflow through the indoor 
coil should be between 350 and 450 CFM per ton of cooling 
capacity (or 350 to 450 CFM per 12,000 Btu/h) based on the 
rating of the outdoor unit.

The cooling blower speed is factory-configured to provide the 
correct airflow for an outdoor unit that matches the maximum 
cooling capacity rating of the air handler. 

If the outdoor unit is smaller than the maximum cooling 
capacity rating for the air handler, the cooling blower speed 
may need to be changed. Refer to the Blower Performance 
Chart.

IMPORTANT: The cooling blower speed must be set to provide a 
minimum of 350 CFM airflow per ton (1,200 Btu/h) of outdoor 
cooling capacity.

WVAHM/WAHMS Motor

Motor Speed Adjustment

The motors in all WVAHM and WAHMS motors are multi-speed 
PSC motors. The color of the wire coming from the motor to the 
“COM” terminal on the control board defines in which speed the 
motor will operate. The black wire represents high speed, the red 
wire represents low speed and the blue wire (select models only) 
represents medium speed.

To change speeds, remove the wire attached to the COM 
terminal on the control board, and swap it with the wire on 
terminal M1 or M2 with the color that will give the desired speed.

NOTE: On some models, not all speed taps are allowable for 
certain electric heat applications. Refer to the air handler series 
and ratings plate for minimum speed.

Goodman 6

HIGH VOLTAGE!

WARNING

Disconnect ALL power before servicing.

Multiple power sources may be present.

Failure to do so may cause property damage, 
personal injury or death.

CFM Delivered Against External 
Static Pressure

Model

Speed

0.1"

0.2"

0.3"

0.4"

0.5"

WVAHM182416

WAHMS18241

Medium

875

830

790

750

715

Low

640

610

570

535

490

WVAHM193116

WAHMS19331

High

1,155 1,090 1,025 950

895

Medium

875

830

790

750

715

Low

640

610

570

535

490

WVAHM303016

WAHMS30301

High

1,135 1,085 1,025 965

915

Medium

860

825

780

750

680

Low

600

570

545

500

465

WVAHM363616

WAHMS36361

High

1,345 1,290 1,230 1,150 1,070

Medium

1,270 1,210 1,140 1,075 980

Low

1,045 1,005 955

885

805

WVAHM364216

WAHMS36421

High

1,700 1,680 1,645 1,610 1,535

Medium

1,500 1,480 1,440 1,380 1,325

Low

1,345 1,320 1,275 1,230 1,195

WVAHM374316

WAHMS37431

High

2,065 2,000 1,925 1,860 1,780

Medium

1,685 1,635 1,550 1,470 1,410

Low

1,490 1,425 1,345 1,280 1,205

WVAHM486016

WAHMS48601

WVAHM496116

WAHMS49611

High

2,135 2,080 1,985 1,900 1,805

Medium

1,975 1,935 1,875 1,775 1,675

Low

1,715 1,670 1,650 1,590 1,530

Содержание WAHME

Страница 1: ... Heating Electric Heat Only 19 Heating Heat Pump 19 AIR HANDLER MAINTENANCE 19 ASSISTANCE OR SERVICE 20 Accessories 20 Whirlpool Models WAHMS WAHME WPIO 355B Goodman 1 Hazards or unsafe practices could result in property damage product damage severe personal injury or death Hazards or unsafe practices may result in property damage product damage personal injury or death WARNING CAUTION Goodman 9 H...

Страница 2: ...he air handler cabinet conforms to 2 percent or less air leakage Goodman 34 WARNING To avoid property damage personal injury or death due to electrical shock this unit MUST have an uninterrupted unbroken electrical ground The electrical ground circuit may consist of an appropriately sized electrical wire connecting the ground lug in the unit control box to the building electrical service panel Oth...

Страница 3: ...r plenum or be installed with a return air plenum under the air handler Louvers or return air grilles are field supplied Local codes may limit the application of systems without a duct return to single story buildings For an air handler installed in a closet with a louvered return opening the minimum open area for the louvers will be as shown below If the free area is not known assume a 25 free ar...

Страница 4: ...should be the same size as the flanged opening provided around the blower outlet and should extend ideally at least 36 91 4 cm from the air handler before turning or branching off plenum into duct runs The plenum forms an extension of the blower housing and minimizes air expansion losses from the blower INSTALLATION INSTRUCTIONS InspectShipment These air handlers are completely factory assembled a...

Страница 5: ...ary drain is clogged See Install Condensate Drain When an evaporator coil is installed in an attic or above a finished ceiling an auxiliary drain pan should be provided under the air handler as specified by most local building codes Suspended Cabinet Installation NOTE Air handlers cannot be installed horizontally lying on or suspended from either the front or back of the air handler It must be pos...

Страница 6: ... channel bracket 11 To avoid possible condensate blow off the insulation retainers are to be laid into the evaporator coil pan as shown in the Evaporator Coil Pan illustration Evaporator Coil Pan To complete the conversion slide the evaporator coil into the chassis and attach the 3 access panels Evaporator Coil NOTE When the air handler is converted to the downflow position the coil may protrude a...

Страница 7: ...al drain hole cover is required InstallCondensateDrain The air handler is provided with 1 9 cm NPT condensate drain connections A field fabricated secondary drain pan with a drainpipe to the outside of the building is required in all installations over a finished living space or in any area that may be damaged by overflow from the main drain pan In some localities local codes may require a seconda...

Страница 8: ...it has the correct orifice installed 2 If a change of the orifice is required loosen the brass hex nut and separate the orifice extension stub from the brass hex fitting 3 Remove the orifice with an orifice extractor tool 4 Insert the proper orifice into the fitting seal end first Make sure the orifice is free to move in the fitting 5 Replace the brass hex nut NOTE Overtightening the brass hex nut...

Страница 9: ... Heat trap or wet rags should be used to protect heat sensitive components such as service valves and TXV valves 1 Loosen the nut one turn only to allow high pressure tracer gas to escape No gas indicates a possible leak 2 After the gas has escaped remove the nut and discard the black or brass cap 3 Remove the check piston to verify it is correct and then replace the piston See the piston kit char...

Страница 10: ...ature Rise tables to determine the temperature rise ºF ºC Temperature Rise Table ºF 230 1 60 Supply Voltage Goodman 34 WARNING To avoid property damage personal injury or death due to electrical shock this unit MUST have an uninterrupted unbroken electrical ground The electrical ground circuit may consist of an appropriately sized electrical wire connecting the ground lug in the unit control box t...

Страница 11: ...4 32 0 48 8 9 1 200 8 13 3 13 10 6 17 8 3 20 6 7 27 2 8 40 4 4 53 11 7 59 15 1 400 7 13 9 11 11 7 14 10 17 8 3 23 5 34 1 1 46 7 8 51 10 6 1 600 6 14 4 10 12 2 13 10 6 15 9 4 20 6 7 30 1 1 40 4 4 44 6 7 1 800 6 14 4 9 12 8 11 11 7 13 10 6 18 7 8 27 2 8 36 2 2 39 3 9 2 000 5 15 8 13 3 10 12 2 12 11 1 16 8 9 24 4 4 32 0 35 1 7 CFM Heat Kit Nominal kW ºF ºC 3 16 1 5 15 6 14 4 8 13 3 10 12 2 15 9 4 20 ...

Страница 12: ...se property damage personal injury or death Room Thermostat W Y G R R G W Y R To Condensing Unit 24V Connections 18 Gauge 2 Wires Blue White Green Red Unit 18 Gauge 4 Wires With Cooling 3 Wires Without Cooling Contactor Coil To Comfort Alert Module If Used W2 W Y G R R G Y W Room Thermostat 18 Gauge 4 Wire With Cooling 3 Wire Without Cooling Outdoor Thermostat Optional Unit Red Green White Brown B...

Страница 13: ... ALL power before servicing Multiple power sources may be present Failure to do so may cause property damage personal injury or death C W2 O Y R R BR G W R Y W Y O C W2 G R E Heat Pump Conventional Room Thermostat 18 Gauge 7 Wire Unit Red Green White Blue BU 18 Gauge 5 Wire BU OR See Note 3 Outdoor Thermostat Optional Closed on Temperature Fall 18 Gauge 6 Wire Needed When Outdoor Thermostat Is Use...

Страница 14: ...nnecting Y1 will result in 1st stage cooling blower speed and may cause the contactor to chatter NOTES 1 Outdoor Thermostat 1 OT 1 should be the first to close and the last to open 2 Jumper W1 and W2 together if OT 2 is not used 3 Remove this wire when using an outdoor thermostat 4 EHR Emergency heat relay optional 5 OT Outdoor thermostat optional Goodman 6 Long HIGH VOLTAGE WARNING Disconnect ALL...

Страница 15: ...connect ALL power before servicing Multiple power sources may be present Failure to do so may cause property damage personal injury or death Y G W W2 R C W1 W2 Y2 Y1 O G R TB Y BU BU Y G R W Y BR BR BR Y Outdoor Thermostat Optional Close on Temperature Fall Condensing Unit 24V Connection Contactor Coil Room Thermostat ASPF Unit See Note 18 Gauge 5 Wire With Cooling 4 Wire Without Cooling To Comfor...

Страница 16: ...l Goodman 6 Long HIGH VOLTAGE WARNING Disconnect ALL power before servicing Multiple power sources may be present Failure to do so may cause property damage personal injury or death G C R C W1 W2 Y2 Y1 O G R TB 18 Gauge 7 Wire O Y C W2 R Y O W2 E R G BU OR Y Y BU OR W BR W BU W W R BR R W G Y OR OR R OR Heat Pump Room Thermostat ASPF Unit 18 Gauge 5 Wire 18 Gauge 7 Wire Needed When 2 Outdoor Therm...

Страница 17: ... instructions for system start up instructions and refrigerant charging instructions Pre Start Check Is the air handler properly located level secure and serviceable Has an auxiliary pan been provided under the air handler with a separate drain for the air handlers installed above a finished ceiling or in any installation where condensate overflow could cause damage Have all the webs been removed ...

Страница 18: ...apacity WVAHM WAHMS Motor Motor Speed Adjustment The motors in all WVAHM and WAHMS motors are multi speed PSC motors The color of the wire coming from the motor to the COM terminal on the control board defines in which speed the motor will operate The black wire represents high speed the red wire represents low speed and the blue wire select models only represents medium speed To change speeds rem...

Страница 19: ...uit R and G energizes the blower relay starting the indoor blower motor If the room temperature should continue to fall the circuit between R and W 1 is completed by the 2nd stage heat room thermostat Circuit R W 1 energizes a heat sequencer relay The completed circuit will energize supplemental electric heat if available Units with a second heat sequencer relay can be connected with the first seq...

Страница 20: ...rive Jacksonville FL 32258 Please include a daytime phone number in your correspondence Accessories To order accessories contact your Whirlpool Home Cooling and Heating dealer WPIO 355B 2009 All rights reserved Registered Trademark TM Trademark of Whirlpool U S A Manufactured under license by Tradewinds Distributing Company LLC Jacksonville Florida 8 09 Printed in U S A ...

Отзывы: