22
E SERIES INSTALLATION MANUAL
Lockout Conditions (continued)
High Pressure
This lockout mode occurs when the normally closed safety switch is opened momentarily (set at 600 PSI).
Low Pressure
This lockout mode occurs when the normally closed low pressure switch is opened for 30 continuous seconds (set at
40 PSI). A low pressure fault may also be indicated when the current sensor is activated by a failure in the compressor
startup.
Freeze Protection (Water Flow)
This lockout mode occurs when the freeze thermistor temperature is at or below the selected freeze protection point
(well 30°F or loop 15°F) for 30 continuous seconds.
Condensate Overflow
This lockout mode occurs when the condensate overflow level has been reached for 30 continuous seconds.
Fan RPM
The control board monitors fan RPM to sense operation. This lockout mode occurs if the fan RPM falls below the low
RPM limit (100 RPM) for 30 continuous seconds.
OPERATION LOGIC
HEATING
COOLING
FAN ON SL1 - IN
ON
SL2 - IN
ON
STG1
STG2
STG3
EMERG
STG1
STG2
SINGLE SPEED UNITS
Compressor
On
On
On
Off
On
On
-
-
-
ECM2 Normal
Med
High
High
High
Med
High
Low
-
-
ECM2 Dehumidify
Med
High
High
High
85% Med 85% High
Low
-
-
Rev Valve
Off
Off
Off
Off
On
On
-
-
-
Loop Pump
On
On
On
Off
On
On
-
On
-
DHW Pump
On
Off
Off
Off
On
On
-
-
-
Aux Heater
Off
Off
Staged
Staged
Off
Off
-
-
-
Secondary 1- Out
On
On
On
Off
On
On
-
-
-
Emerg LED
Off
Off
Off
On
Off
Off
Off
-
-
T-Stat Signal
Y1
Y1, Y2
Y1, Y2, W
W
Y1, O
Y1, Y2, O
G
-
-
DUAL CAPACITY UNITS
Compressor-Lo
On
Off
Off
Off
On
Off
-
-
-
Compressor-Hi
Off
On
On
Off
Off
On
-
-
-
ECM2 Normal
Med
High
High
High
Med
High
Low
-
-
ECM2 Dehumidify
Med
High
High
High
85% Med 85% High
Low
-
-
Rev Valve
Off
Off
Off
Off
On
On
-
-
-
Loop Pump-Stg 1
On
On
On
Off
On
On
-
On
-
Loop Pump-Stg 2
Off
On
On
Off
Off
On
-
-
On
DHW Pump
On
On
Off
Off
On
On
-
-
-
Aux Heater
Off
Off
Staged
Staged
Off
Off
-
-
-
Secondary 1- Out
On
On
On
Off
On
On
-
-
-
Secondary 2- Out
Off
On
On
Off
Off
On
-
-
-
Emerg LED
Off
Off
Off
On
Off
Off
-
-
-
T-Stat Signal
Y1
Y1, Y2
Y1, Y2, W
W
Y1, O
Y1, Y2, O
G
-
-
Operation Logic Data