E SERIES INSTALLATION MANUAL
Figure 13: Line Voltage 208-230/60/1 Control Box
(Single Speed Units)
Electrical Connections
General
Be sure the available power is the same voltage and phase as that shown on the unit serial plate. Line and low voltage
wiring must be done in accordance with local codes or the National Electric Code, whichever is applicable.
Unit Power Connection
Connect the incoming line voltage wires to L1 and L2, or L1,L2, and
L3 of the contactor as shown in Figure 13 for single-phase unit and in
Figure 15 for three-phase units.
All 460/60/3 units with an ECM fan
motor must pull a neutral wire to complete the unit wiring
. Consult the
Unit Electrical Data in the Specification Catalog for correct fuse sizes.
Accessory Relay
A set of “dry” contacts has been provided to control accessory devices,
such as water solenoid valves on open loop installations, electronic air
cleaners, humidifiers, etc. This relay contact should be used only with
24 volt signals and not line voltage power. The relay has both normally
open and normally closed contacts and can operate with either the fan
or the compressor. Use DIP switch SW2-3 to cycle the relay with fan or
compressor. The relay contacts are available on terminals #2 and #3 of
P3.
208 Volt Operation
All E Series 208/230 units are factory wired for 230 volt operation. A
switch located on the control box, allows the installer to select 208 volt
unit operation. (Refer to Figure 13.)
Compressor
Capacitor
Transformer
External Loop Pump(s)
208-230/60/1
1/2 HP Max
Voltage
Selection
Rocker Switch
PS
PB1
Ground
Lugs
Unit Control
Board
208-230/60/1
Service with
Ground
L1
L2
D
C
A
Compressor
Contactor
Figure 14: Line Voltage 208-230/60/1 Control Box
(Dual Capacity Units)
External Loop
Pumps
208-230v/60/1
1/2 H.P. Max
208-230v/60/1
Service with
Ground
Stage 1
D
Blk
Blu
C
B
A
START CAP
PB2
CCL
CCH
PB-1
TRANS
PCB
L1
L2
Stage 2
Figure 15: Line Voltage Three Phase Control Box
(460 volt units with ECM blowers use power block.)
Transformer
PS
Ground
Lugs
Unit Control
Board
Three-phase Unit
Service with Ground
L1
L2
D
C
A
L3
Compressor
Contactor