13
E SERIES INSTALLATION MANUAL
Electronic Thermostat
Position the thermostat subbase against the wall so that it is
level and the thermostat wires protrude through the middle of the
subbase. Mark the position of the subbase mounting holes and
drill holes with a 3/16-inch bit. Install supplied anchors and secure
base to the wall. Thermostat wire must be 8-conductor, 18-AWG
wire. Strip the wires back 1/4-inch (longer strip lengths may
cause shorts) and insert the thermostat wires into the connector
as shown. Tighten the screws to insure secure connections. The
thermostat has the same type connectors, requiring the same
wiring. See instructions enclosed in the thermostat for detailed
installation and operation information.
Note:
DIP switch SW2-#8 is required to be in the OFF position
for the control to recognize the 24VAC thermostat inputs. The
second stage compressor wire must be installed between the
unit and the thermostat for proper control operation.
Setting Fan Speed
ECM2 fan motors have a 12-speed selector dip switch on the logic
board (SW1) and are factory set for optimum performance. To change
speeds, select the appropriate speeds on dip switch SW1. Consult the
ECM2 fan performance table on page 14 for specific airflow and switch
information.
PSC fan motors have 3 speeds. To change speeds, remove one of
the blower access panels. Change the position of the wire on the mo-
tor terminals to any other two speed terminals. Refer to Figure 17 for
changing speed on a 460 volt PSC fan motor.
High - L1 to white side of capacitor, L2 to H on
motor.
Med - L1 to white side of capacitor, L2 to M on
motor, orange wire to M1 on motor.
Low - L1 to white side of capacitor, L2 to L on
motor, Yellow wire to L1 on motor,
Orange to M1 on motor.
Figure 17: Speed Change - 460 Volt
PSC Fan Motor
CAUTION: Disconnect all power before performing this operation.
Figure 16: Thermostat Wiring
R
Y1
C
W
O
G
L
24VAC (Hot)
24VAC (Common)
Compressor (1st Stage)
Aux. Heat
Reversing Valve
Blower Relay
System Monitor
M
icr
op
ro
ce
ss
or
C
on
tro
lle
r
Th
er
m
os
ta
tC
on
ne
ct
io
n
Y2
Compressor (2nd Stage)