17
E SERIES INSTALLATION MANUAL
Fan Speed Control
A DIP switch on the E Series control allows field selection of 15% reduced fan speeds for cooling in the dehumidification
mode or medium and high fan speeds for cooling in the normal mode.
Note:
Fan speed can change automatically only with an ECM Motor.
ECM2 Airflow Selection DIP Switches (SW1)
A 12-position DIP switch package on the E Series control allows the airflow levels to be set for low, medium and high
speed. (Refer to the ECM Blower Table on page 14.)
Only three of the DIP switches can be in the “on” position. The first “on” switch (the lowest position number) determines
the “low speed fan” setting. The second “on” switch determines the “medium speed fan” setting, and the third “on” switch
determines the “high speed fan” setting, (see page 14).
Standard Microprocessor Control Features