14
E SERIES INSTALLATION MANUAL
Fan Performance Data
ECM2
1
2
3
4
5
6
7
8
9
10
11
12
SW1
On
Off
A 12-position DIP switch package on the control allows the airflow levels to be set for low,
medium, and high speed when using the ECM2 blower motor. Only three of the DIP switches
can be in the "on" position.
The first "on" switch (the lowest position number) determines the low speed fan setting.
The second "on" switch determines the medium speed fan setting.
The third "on" switch determines the high speed fan setting.
The example to the right shows SW1 on the control board configured for the following E040
airflow settings.
Low Speed Fan: 850 CFM
Medium Speed Fan: 1050 CFM
High Speed Fan: 1325 CFM
•
•
•
MODEL
MAX
ESP
AIR FLOW DIP SWITCH SETTINGS
1
2
3
4
5
6
7
8
9
10
11
12
SINGLE SPEED
E024
0.50
300
400
500
L
600
M
700
L
800
E030
0.50
300
400
500
L
600
700
M
800
900
H
1000
E035
0.50
500
600
700
L
800
900
M
1000
1100
H
1175
1250
E040
0.50
650
750
850
L
950
1050
M
1150
1250
1325
H
1375
1475
E047
0.50
650
750
850
950
1050
L
1150
1250
M
1325
1375
1475
1550
H
1600
E040
w/ 1 HP*
0.75
800
L
1000
M
1100
1300
H
1500
E047
w/ 1 HP*
0.75
800
1000
L
1100
1300
M
1500
H
1600
1800
E058
0.75
750
900
1000
1200
L
1400
M
1600
1700
1850
H
2000
2200
2300
2400
E066
0.75
750
900
1000
1200
1400
L
1600
1700
M
1850
2000
2200
H
2300
2400
DUAL CAPACITY
E036
0.50
600
L
700
800
M
900
1000
1100
1200
H
1300
1400
1500
1550
1600
E048
0.50
600
L
700
800
900
1000
M
1100
1200
1300
1400
1500
H
1550
1600
E048
w/ 1 HP*
0.75
750
L
900
1000
M
1200
1400
1600
H
1700
1850
2000
2200
2300
2400
E060
0.75
750
L
900
1000
1200
M
1400
1600
1700
1850
2000
H
2200
2300
2400
E072
0.75
750
L
900
1000
1200
1400
M
1600
1700
1850
2000
2200
H
2300
2400
Notes
: * With optional 1 HP fan motor.
Factory settings are at recommended L-M-H DIP switch locations. M-H settings must be located within shaded CFM range. CFM is controlled
within ± 5% up to the maximum ESP. Max ESP includes allowance for wet coil and standard filter. Lowest and highest dip switch setting are as-
sumed to be L and H speed, respectively.