TROUBLESHOOTING GUIDE
PROBLEMS OR
SYMPTOMS
CAUSES TROUBLESHOOTING
Unit does not
work
1. - Power supply problem.
1. - Main Switch shut down (Off).
Switches and/or or actuated external fuses.
Loose cables and/or terminals.
Missing phase or bad neutral wiring, or two equal
phases.
2. - Room temperature lower than set-
point adjustment of Controller.
2 Add charge to the room or wait until room temperature
increases
3. - Shut down due to low pressure
switch.
3. - Check for cooling gas leaks.
Change clogged air filters
Check evaporator motor: burnt or locked.
4. - Shut down due to high pressure
switch
4. - Condenser motor locked or burnt.
Dirty condenser coil or with lumps
Excess gas, added in previous repair.
5. - Electrical wiring error
5. - Check electric wiring of assembly again
6. - No supply voltage reaches the
Controller
6. - Transformer is burnt or if DC to controller, key
switched off.
System
operates
continuou
sly and
insufficie
ntly.
1. - The unit is not enough to cool the
room.
1. - Make a heat balance, determine capacity to be
added.
2.- Damaged component malfunction.
2. - Replace damaged switches, adjust loose blowers,
clean dirty coils.
3 - Gas leaks
3. - Repair gas leaks, install and/or adjust service valve
caps and nuts. Charge additional gas.
4. - Defective compressor
4. - Replace compressor.
5. - Clogged air filter, low performance
(lack of air)
5. - Replace air filter.
Thermal
relays
of contactors
are actuated
1. - Inappropriate wiring for power
consumption
1. - Replace cable section.
2. - Defective motors and/or compressors
3.- Replace them
3.-Low voltage (10% lower than nominal
voltage)
4. - Manage troubleshooting.
Water inside
unit.
1. Condensate tube clogged and
overflowing into water collection tray.
1.- Unblock condensate drain pipe.
Failure outputs are two relays which are always connected (on). Upon a failure, they change their status. If the PLC
is switched off, they also change their status because they are disconnected (off).
"
Not Urgent
" output is switched off with any failure.
"
Urgent
" output is switched off when two or more units have an alarm.
Содержание DW Series
Страница 1: ......
Страница 2: ...76 1002 00 Page 2 of 48 ...
Страница 4: ...76 1002 00 Page 4 of 48 ...
Страница 5: ...76 1002 00 Page 5 of 48 ...
Страница 8: ...76 1002 00 Page 8 of 48 Dimensions of Indoor Units Top Air Outlet ...
Страница 9: ...76 1002 00 Page 9 of 48 Dimensions of Indoor Units Bottom Air Outlet Front Return ...
Страница 10: ...76 1002 00 Page 10 of 48 Dimensions of DW 008 UE DW 010 UE Outdoor Unit ...
Страница 11: ...76 1002 00 Page 11 of 48 Dimensions of DW 012 UE Outdoor Unit ...
Страница 39: ...76 1002 00 Page 39 of 48 ...
Страница 44: ...76 1002 00 Page 44 of 48 Power Electrical Circuit Remote Compressor With Humidifier 15 2336 05 ...
Страница 45: ...76 1002 00 Page 45 of 48 Power Electrical Circuit Remote Compressor Without Humidifier 15 2493 01 ...
Страница 47: ...76 1002 00 Page 47 of 48 Power Electrical Circuit With Humidifier 15 2291 01 ...
Страница 48: ...76 1002 00 Page 48 of 48 Power Electrical Circuit Without Humidifier 15 2394 02 ...