Installation and Assembly
Location:
Before you install a new unit, there are a few important things you should take into account.
Select the exact location to install the units.
Leave at least a 500 mm free space between the units, for easy maintenance and service
purposes.
Place rubber gaskets or iso-mode pad type material to support units so to avoid
transmission of noise and vibration.
Check the level unevenness of the surface on which the unit will be installed, which must not
exceed 5 mm, as this will cause problems with the regulation of the doors and it may also
cause the overflow of condensate from the tray.
Checking of equipment upon receipt
Upon receiving the units, carefully inspect them to verify that they were not damaged during transportation and also
that there are not missing parts. Notify the company in writing of any damage that might have been caused during
transportation.
Check that all items supplied with the units are included in the packaging as well as the items needed for
installation.
Bolts, nuts, cables, silicone sealant, etc. (Not provided)
Special supports for lifting. (Not provided)
Power supply connection
Make sure the voltage to be supplied to the unit is the one required for this model, check this using a
voltmeter.
The power supply is made directly to the Main Switch, located in the power board of the unit.
The unit has a
neutral
terminal separated from the Main Switch.
IMPORTANT
:
NOTE
: If power supply is three-phase with neutral, it must be identified beyond any doubt; then check the required
380V between phases, and 220VAC between each phase and neutral.
STANDARD COLORS FOR CABLES:
NAME COLOR
"R"
Phase
Brown
"S"
Phase
Black
"T"
Phase
Red
Neutral
Light
blue
Ground
Yellow / Green
For safety reasons, the power board should be grounded through the corresponding ground terminal.
Содержание DW Series
Страница 1: ......
Страница 2: ...76 1002 00 Page 2 of 48 ...
Страница 4: ...76 1002 00 Page 4 of 48 ...
Страница 5: ...76 1002 00 Page 5 of 48 ...
Страница 8: ...76 1002 00 Page 8 of 48 Dimensions of Indoor Units Top Air Outlet ...
Страница 9: ...76 1002 00 Page 9 of 48 Dimensions of Indoor Units Bottom Air Outlet Front Return ...
Страница 10: ...76 1002 00 Page 10 of 48 Dimensions of DW 008 UE DW 010 UE Outdoor Unit ...
Страница 11: ...76 1002 00 Page 11 of 48 Dimensions of DW 012 UE Outdoor Unit ...
Страница 39: ...76 1002 00 Page 39 of 48 ...
Страница 44: ...76 1002 00 Page 44 of 48 Power Electrical Circuit Remote Compressor With Humidifier 15 2336 05 ...
Страница 45: ...76 1002 00 Page 45 of 48 Power Electrical Circuit Remote Compressor Without Humidifier 15 2493 01 ...
Страница 47: ...76 1002 00 Page 47 of 48 Power Electrical Circuit With Humidifier 15 2291 01 ...
Страница 48: ...76 1002 00 Page 48 of 48 Power Electrical Circuit Without Humidifier 15 2394 02 ...