background image

relay  pickup  (3  to  5  ms)  and  operate  time  of the 
ojc  unit  (3  to  8  ms). 

The range  of adjustment  is a  m inimum  of 1 00 

ms  ( 1 50  to  250  ms). 

The  control  timer  must  be  set  at  least  1 6  ms 

longer than the breaker failure timer. The control 
timer  acts  essentially  as  a  pulse  stretcher  on  the 

B FI  input  and  then resets.  Since the  overcurrent 
unit  never  picks  up on successful clearing,  it can­

not  be  used  as  a  cutoff  for  the  breaker  failure 
timer. 

BF 

T I M E R  

A  calibrated scale  located  o n  the  front  o f  the 

timer module permits setting  the time delay  from 

1 8  to  1 75 milliseconds. The scale is calibrated in 25 

ms  increments.  If  more  accurate  settings  are 

desired an  oscilloscope or electronic timer  may be 
connected  between  the  upper  red  test  jack  on  the 
timer  module  and  terminal  8  of the  relay  (Com­

mon N egative). Jumpering test point TP6 and TP7 

on  the  timer  module  prevents  the  control  timer 

from  resetting  the  B F   timer and  will  help  in set­

ting  the  B F   timer. Remember that  if the  control 
timer is set shorter than the B F  timer, the B F  timer 
will  not  be  able  to  operate  the  reed  relay  (RR). 

A locking  tab is provided to hold the B F  timer 

setting  from  being  accidentally  changed. 

The  breaker  failure  timer should  be  set  to ex­

ceed  the  breaker  normal  clearing  time  by  an  ap­
propriate  margin.  Where  the  breaker  contains  a 

resistor  that  is  inserted  on  tripping  and  the  over­

current  fault  detectors  are  set  below  the  resistor 

current,  the  additional  time  for  this  interruption 
must be  included. A secure margin  for  the SBF- 1 
is  2  cycles.  (33  ms) 

I N D I CATI NG  CONTACTOR 

SWITC H  (I CS) 

Connect  the  lead  located  in  front  of  the  tap 

block  to the desired setting  by  means  of the con­

necting  screw. 

When the relay energizes a 1 25 or 250 Vdc type 

WL relay switch  or equivalent use the 0.2 amp tap. 
For 48  Vdc  applications  set the unit in the 2 amp 

I.L. 41-776.5 

t a p   a n d   u s e   a  t y p e   WL  r e l a y   w i t h   a 

S#304C209G0 1  coil  or  equivalent. 

I N STALLATIO N  

The relays should be  mounted  on switchboard 

panels  or  their  equivalent  in  a  location  free  from 

dirt,  moistu,re,  excessive  vibration  and  heat. 

Mount  the  relay  vertically  by  means  of  the  rear 

mounting  stud  or studs  for  the  type  FT projection 

case or by means of the four mounting holes on the 

flange  for the semi-flush  type  FT case.  Either the 

stud  or  the  mounting  screws  may  be  utilized  for 
grounding the relay.  External toothed washers are 

provided for use in the locations shown on the out­

line  and  drilling  plan  to  facilitate  making  a  good 
electrical  connection  between  the  relay  case,  its 
mounting  screws  or  studs,  and  the  relay  panel. 
Ground  wires  are  affixed  to  the  mounting  screws 
or  studs  as  required  for  poorly  grounded  or  in­
sulating  panels.  Other  electrical  connections  may 

be  made  directly  to  the  terminals  by  means  of 
screws  for steel panel mounting or to the terminal 
stud furnished with the relay for thick panel moun­
ting. The terminal stud may be easily removed or 

inserted by  locking  two nuts  on the stud and then 

turning  the  proper  nut  with  a  wrench. 

For detail  information on the FT case refer to 

I.L.  4 1 -076. 

ADJU STMENTS A N D  

M AI NTENANCE 

The  proper  adjustment  to  insure  correct 

operation  of this  relay have been  made at the  fac­
tory  and  should  not  be  disturbed. 

Routine  Test 

The  following  check  is recommended to insure 

that the relay is in proper working order. Refer to 

Fig.  1 0  for test  connections. 

Overcurrent  Detector 

Check for correct scale marking by placing  all 

the tap settings in the 0.5 Amp. position and rotate 

the Phase and Ground tap multiplier knob (on the 
overcurrent unit knob) to the X 1  calibration mark. 

Jumper test  point  TP  6  and  TP7  on the timer 

www 

. ElectricalPartManuals 

. com 

Содержание SBF-1

Страница 1: ...tapped and brought out to a tap block located on the front of the relay Each transformer has three taps which cover the range of pickup The secondary of the transformers are con nected to the input o...

Страница 2: ...as well as the X seal in relay is reset after it times out The circuit operation can be explained by referring to the internal schematic drawing 77588 1 3 Fig 2 and detailed internal schematic 1 3260...

Страница 3: ...ained by using a current source and a precision ammeter CAUTION Since the tap block connector screw carries operating current be sure that the screw is turned tight In order to avoid opening the curre...

Страница 4: ...rrent unit is obtained by means of a tap screw and tap block in conjunc tion with the tap multiplier knob setting located at the front of the overcurrent unit module This per mits a continuous adjustm...

Страница 5: ...ch or equivalent use the 0 2 amp tap For 48 Vdc applications set the unit in the 2 amp I L 41 776 5 t a p and use a type WL relay with a S 304C209G01 coil or equivalent I NSTALLATION The relays should...

Страница 6: ...low state in 1 90 to 210 milliseconds If some other time interval is desired the timer setting may be changed by means of a screw driver adjustment through the access hole on the timer 6 module to a m...

Страница 7: ...t point TP6 and TP7 on the timer board Energize the relay with rated de voltage and apply 0 48 Amps ac current to phase A With the tap in the 0 5 position and the phase multiplier dial knob fully coun...

Страница 8: ...cation of trouble in service or dur ing routine checks the following information will prove helpful All measurements are approximate and may vary as much as 20 All voltages are positive with reference...

Страница 9: ...voltage at terminal 4 should measure 6 4V The voltage at printed circuit board I L 41 776 5 terminal 3 should measure 23 5Vdc before the output relay operates and less than 2 5V after it operates 3 J...

Страница 10: ...Current 4 5A S OA VA 23 28 OHMS 0 1 1 01 1 P F Angle 36 1 8 Saturated Burden Current Lagging Voltage CLOSED 4 5A S OA 16 20 008 008 5 4 OPEN C LOSED SA SA O SA S OA 53 2 1 33 2 2 23 08 1 5 09 63 25 20...

Страница 11: ...5 TABLE 4 I L 41 776 5 0 5 to 1 3 5 Amperes 1 SECOND 250 Amps 250 300 AR CONTACT RATINGS I NTERRUPTING RATING CONTACT CIRCUIT TRIP CARRY RATING RESISTIVE I NDUCTIVE RATING RATING CONTINUOUS L R 005 4...

Страница 12: ...ER TB TRANSFORMER TA Fig 1 Photograph of SBF 1 Relay without case with four overcurrent input Front view 12 SEAL IN RELAY X ICS INDICATING CONTACTOR SWITCH w w w E l e c t r i c a l P a r t M a n u a...

Страница 13: ...right oblique I L 41 776 5 POTENTIOMETER PA POTENTIOMETER PC POTENTIOMETER PG POTENTIOMETER PB TRANSFORMER TG RESISTOR RS 1 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 14: ...MOVE RED LEAD FROM TERMINAL II TO TERMINAL 12 L R LC S RC DENOTE LEFT HAND RIGHT HAND LEFT CENTER S RIGHT CENTER POSITIONS REF DWG 25W RESISTORS 1326DI9 DETAILED SCHEMATIC 1326D31 4 OVERCURRENT UNITS...

Страница 15: ...TED VDC 13 FROM TERM 3 OF 4 OVERCURRENT DETECTOR MODULE RATED VDC 3 52 a TIMER AND O UTPUT MODULE 4 PI IS PANEL MOUNTED 17 7 L TO X RELAY 10 J WHEN USED REPLACED BY FOR GROUPS I Fig 4 Internal SCR w w...

Страница 16: ...RIPTI JN STYLE N0 JUM P R 0 OHM RESISTOR 862A413HO I Jl DESCRIPTI J J STYLE POT 20 0K 501 1 862A406H02 P2 25 0K sow SSOA687H02 PI DESCRIPTHlN STYLE TRANS STOR 2N2905A 762A672H O 01 2 lt 7 1 1 762A585H...

Страница 17: ...Pl 2 a Pl 3 I 14 Fig 5 Component Location tor Timer Module 48 or 125Vdc rated relay I L 41 776 5 3517A76 19 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 18: ...WHEN USED 3517A77 Fig 6 Com u e 250Vdc rated relay ponent Location for Timer Mod I 20 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 19: ...o z uot s I d SH U7H7 ki 0 12 lJ SCKIPfiJ TYLI ZE EK 1 751A f 2 J r r n r o1 Z2 1 17j21 JJ Jv 0 I I d c Zl DESCRIPTltlN STYLE NG I POT 500 0 2 00W 10 7o 848A778H04 PA PC PG IO OK 12 5W O lo 836A635HI...

Страница 20: ...3517A78 Fig 8 Component Location for 3 Current Input Overcurrent Detector Module 22 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 21: ...I L 41 776 5 3517A79 Fig 9 Component Location for 4 Current Input Overcurrent Detector Module 23 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 22: ...G X TAP MULTIPLIER r l I TO RH CONTACT OF AR RELAY I t L _ Q J_ 2 4 s a lGND J l L J TO RH CONTACT I OF AR RELAY I l l 9 Qg _j LO BOUNCE SWITCH TO TESTTIMER RATED START VDC TO TESTTIMER COMMON NOTE TO...

Страница 23: ...PPt 62 l 62 l 2 _ _3 r 1 IB WHEN 62 1 16 USED 17 r n 6 Ic f 1 _ Io 6 1 f Jf 1 SPP t rv r rv P J SBF 1 RELAY FOR BREAKER 52 2 r r BACKUP r RELAYS r r JPRIMAR t SPP SURGE PROTECTION CAPACITORS TO BE USE...

Страница 24: ...BR EAKER FAILUR E R ELAY 7nBBI3 1326DI 9 62Xp2 Y BR EAKER FAIL UR E INITIATE CONTACTS 8 6BF BR EAKER FAILUR E LOCKOUT R ELAY 8 6TI TR ANSFOR MER LOCKOUT R ELAY T YPICAL 8 6BF AND OR R E L AY AUX F UNC...

Страница 25: ...EXTERNAL TOOTHED WASHERS 4 375 1 1 1 1 3 1 90 32 SCREW 4 375 SPACERS FOR I l l 1 3 THIN PANELS I L 41 776 5 5 5631 250 DIA 4 HOLES FOR 141 30 6 35 190 32 MTG SCREWS f 1 5707903 Fig 13 Outline and Dri...

Страница 26: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 27: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 28: ...W E S T I N G H O U S E E L E C T R I C C O R P O R A T I O N R E LAY I NST RU M E NT D IVISION CORAL SPRI NGS F L Printed in U S A w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 29: ...tap block located on the front of the relay Each transformer has three taps which cover the range of pickup The secondary of the transformers are con nected to the input of the plug in detector modul...

Страница 30: ...ctor The breaker failure timer controls the fault detector so that after it times out the overcurrent signal if present is connected to the level detector This arrangement keeps the overcurrent input...

Страница 31: ...rent is reduced to zero or up to 95 of pickup current Continuous rating is 1 0 amperes One second rating is 250 amperes The accuracy of the pickup setting is 5 over the full range and 10 from 20 to 55...

Страница 32: ...cts will safely close 30 amperes at 250 Vdc and the seal in contacts of the ICS will safely carry this current long enough to trip a cir cuit breaker SETTINGS OVERCURRENT DETECTOR The pickup of the ov...

Страница 33: ...41 776 5A resistor that is inserted on tripping and the over current fault detectors are set below the resistor current the additional time for this interruption must be included A secure margin for...

Страница 34: ...e will speed up the dropout time longer range timer Use the same test with applying current to BREAKER FAILURE BF i f phase C and also phase B if used Pickup should TIMER be within 5 of the phase A pi...

Страница 35: ...e relay if the relay has been taken apart for repairs or the adjustments have been disturbed This procedure should not be used unless it is apparent that the relay is not in proper working order Overc...

Страница 36: ...ee that the contacts close at rated tap value current The indicating target should drop at or just prior to the contacts closing The targer should drop freely I f the target does not drop or does not...

Страница 37: ...1 posi tion I L 41 776 5A a With 0 4 amp ac current flowing apply rated relay voltage Measure voltage at terminal 5 of I C I to be 6 4V Now increase the current until the output relay operates The vo...

Страница 38: ...OA VA 1 65 75 06 60 63 75 50 60 O H M S 073 03 027 024 03 1 03 024 024 P F Angle 45 36 1 5 1 5 36 36 1 5 1 5 TAP 4 5 TAP MULT 1 4 5A PICKUP 3 1 3 5A PICKUP REED RR CONTACT OPEN CLOSED OPEN C LOSED Cu...

Страница 39: ...T RATINGS I L 41 776 5A I NTERRUPTING RATING CONTACT CIRCUIT TRIP CARRY RATING RESISTIVE I NDUCTIVE RATING RATING CONTINUOUS L R 005 48Vdc 30 Amps 3 Amps 3 75 Amps 1 75 Amps 1 25 30 3 5 35 250 30 3 25...

Страница 40: ...ER TB TRANSFORMER TA Fig 1 Photograph of SBF 1 Relay without case with four overcurrent input Front view 12 SEAL IN RELAY X ICS INDICATING CONTACTOR SWITCH w w w E l e c t r i c a l P a r t M a n u a...

Страница 41: ...right oblique I L 41 776 5A POTENTIOMETER PA POTENT OMETER PC POTENTI OMETER PG _ _ POTENTIOMETER PB TRANSFORMER TG RESISTOR RS 1 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 42: ...R l L Cl RCl DENOTE LEFT HANO RIGHT HAND LEFT CENTER a RIGHT CENTER POSITIONS W RESISTORS VOLTS DC RA RS 1326DI9 DET AILED SCHEMATIC 48 900 n 200 n 1326D31 4 OVERCURRENT UNITS WIRING 1 326 D83 3 OVERC...

Страница 43: ...13 FROM TERM 3 OF 4 OVERCURRENT DETECTOR MODULE RATED VDC 52 a f i 4 TIMER AND OUTPUT MODULE PI IS PAN E L MOUNTED 7 TO X RELAY 10 WHEN USED I I I I 9 I I I REPLACED BY J FOR GROUPS I a 0 Fig 4 Intern...

Страница 44: ...UZ8 70 Q Q IJ 0 37 A 69 JH I 4 matic of Timer Module 1454C81 G02 125 VDC 1454C81 G03 2 50 VOC CAPAC T O R C J C2 Cl D H l U D l 2 03 II A DX l N T CKT I C I JUMPER J l 2 P2 P I P0T TRtu I S I S H J R...

Страница 45: ...Pl 2 a Pl 3 I 14 Fig 5 Component Location for Timer Module 48 or 125Vdc rated relay I L 41 776 5A 3517A76 19 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 46: ...20 Fig 6 Comp anent Location for Timer Mod I u e 250Vdc rated relay WHEN USED 3517A77 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 47: ...l 7 J J Q j Q Q 5 1 7 rl 6 J J 5 R l 5 0 0 00 5 7 6 ll 1 7Yll R l 2 4 5 J Q Q 1 57 J tl 7 A 6 4 3rlJ R l 6 3 9 2 00 o 5 4 6 5A 2 J 7 L l 1 1 3 1 4 J O Q Q 2 00 1t 5 4 J 5f 2 0 7 H 7 5 R9 10 12 UESCRJ...

Страница 48: ...3517A78 Fig 8 Component Location for 3 Current Input Overcurrent Detector Module 2 2 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 49: ...I L 41 776 5A 3517A79 Fig 9 Component Location for 4 Current Input Overcurrent Detector Module 23 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 50: ...I TO RH CONTACT TO RH CONTACT I OF AR RELAY OF AR RELAY I I 1 l i L _ C0_ 2 4 6 l 9 _j L g uc N HCE f JA1 l c1 lGND IOK TO TESTTIMER RATED Y Y f START VDC TOTESTTlMER COMMON NOTE TO TEST FOR OVERCURR...

Страница 51: ...62 2 r SBF I RELAY FOR BREAKER 52 2 rrll l rr x 6 llf f 1 1 1 1 1 l f 6 lc 62 I BACKUP f A vT RELAYS r t 62 1 Io L 7 fs t f I P E t SPP SURGE PROTECTION CAPACITORS TO BE USED WHEN SURGE VOLTAGE MAY E...

Страница 52: ...D ________ _____ I u I CIRCUIT BR IPTION S8F IBREA ERFAILUR R lAY 775 1326 D 1 9 2X 62Y BREAKER FAI L U R E I N I T IAT CO _ N _ TACTS l LBSBF BREA K E R FAILURE LOCKOUT RELAY 86TI TRANSFOR M E R LOC...

Страница 53: ...750 400 05 5 875 149 23 2 938 74 63 PA NEL C U TOUT 8t DR I L L I N G FOR S E M I FLU S H MTG LARGE INT E R N I 5 5 6 a E XT E RNA L _L_ J t TOOTH WASHER r 64 1 16 2 8 S M A LL EXTERNAL TOOTHED WASHER...

Страница 54: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 55: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 56: ...W E S T I N G H O U S E E L E C T R I C C O R P O R A T I O N R E LAY I N ST R U M E NT DIVISION CORAL S P R I N G S FL Printed in U S A w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Отзывы: