It  can  be  energized  continuously  at  1 1 0%  of 

rated  input  voltage. 

Capacitive  Effect 

The  capacitive  surge  immunity  is  as  follows 

(considering  the  52a  contact input  present): 

Relay Rating 

48 Vdc 

1 25 Vdc 

1 25 Vdc 

250 Vdc 

250 Vdc 

BF Timer Setting 

1 8  

ms 

or 

higher 

1 8  

ms 

or higher 

35 

ms 

or 

higher 

1 8  

ms 

or 

higher 

35 

ms 

or higher 

Capacitance 

1 8   M FD 

6  M FD 

1 3   MFD 

2.5 MFD 

1 3   M FD 

Any  value  of  capacitance  effectively  in  series 

with  the  input  greater  than  that  shown  above 

might  result  in  an  undesired  trip  operation. 

Ordinarily  capacitance  should  not  be  con­

nected from the lead connecting the 52a contact to 

the relay and  ground.  A  value  of 0.5  M F D  could 
cause  the  52a  input  to  stay  on  for  1 . 5  ms  (48 V  
relay), 4.5 ms ( 1 25V relay) and 2 0  ms (250V relay) 

after  the  52a  contact  opened. 

RELAY 

Coil  resistance  is  1 500  ohms  ±5%  and  rated 

for  24Vdc  operation .  The  seal-in  contact  will 

pickup providing the  BFI  (62X, 62Y) initiate con­

tacts are closed for a  minimum of  8  ms. A  second 

contact  is  wired  to  relay  terminal  1 1   and  1 2  to 

provide  a  retrip  feature. 

AR  RELAY 

The coil  resistance  is 630  ohms  ± 5 %  and will 

operate  in  series  with  the  appropriate  resistor 

from  80%  to  1 1 0%  of  rated  voltage. 

The operate speed is 3 to 5  ms at rated voltage. 

The  dropout time is  30  to  45  ms (diode around the 
coil).  There  are  4  n ormally  open  contacts 
available. 

I N DI CATI N G   C ONTACTOR  SWITC H  ( I C S) 

The  coil  resistance  is  approximately  6 . 5  ohms 

on  the 0.2 amp tap  and 0. 1 5  ohms on  the 2.0 amp 
tap. 

TRIP  C I RC U IT 

The  main contacts will safely close 30  amperes 

at 250  Vdc and  the seal-in contacts of the  I CS will 

safely  carry  this current long enough to trip a  cir­
cuit  breaker. 

S ETT I N G S  

OVERC U R RENT D ETECTOR 

The pick up of the overcurrent unit is obtained 

by  means of a  tap  screw  and tap  block in  conjunc­
tion with the tap m ultiplier  knob setting located at 
the front of the overcurrent unit module. This per­
mits a continuous adjustment over the range of 0 . 5  

t o   1 3 .5  amperes.  Each  tap  setting  permits  ad­

justing  the  pickup over  a  3  to  1  range. 

There are 2  or 3  phase inputs depending on the 

relay  style.  Each  one has  its  own tap block .  N or­

mally  all  the  phase settings  should be in  the  same 

tap.  The  operate  point for each  phase  should  be 
within  5%  of  each  other.  There  are  trimpots  for 
each  input  located  on  the  overcurrent  module 
which are factory adjusted but which may be read­

justed if the 5% accuracy m ust be improved at any 

one  pickup  point. 

The ground  unit  pickup  is  obtained  similar 

to 

the  phase  above  and  is  independent  of  the  phase 
pickup. This permits the ground setting to be lower 
than  the  phase  setting. 

The  phase  un its  must  be  set  below  the 

minimum  expected  fault  current  and  the  ground 
unit  set  below  the  minimum  expected  residual 
(310)  current.  Settings  should be made to assure a 
multiple  of  pickup  of  at  least  2  under  minimum 

fault  conditions. 

CONTROL  TI M E R  

The control timer can b e  set b y  use o f  a  screw­

driver  to  adjust  the  trimpot  which  is  accessible 
through  the  hole  in  the  front  plate  of  the  timer 

module.  Clockwise  rotation  will  increase  the  on 

time.  An  oscilloscope  or electronic timing device 
can be connected between the bottom red test jack 

www 

. ElectricalPartManuals 

. com 

Содержание SBF-1

Страница 1: ...tapped and brought out to a tap block located on the front of the relay Each transformer has three taps which cover the range of pickup The secondary of the transformers are con nected to the input o...

Страница 2: ...as well as the X seal in relay is reset after it times out The circuit operation can be explained by referring to the internal schematic drawing 77588 1 3 Fig 2 and detailed internal schematic 1 3260...

Страница 3: ...ained by using a current source and a precision ammeter CAUTION Since the tap block connector screw carries operating current be sure that the screw is turned tight In order to avoid opening the curre...

Страница 4: ...rrent unit is obtained by means of a tap screw and tap block in conjunc tion with the tap multiplier knob setting located at the front of the overcurrent unit module This per mits a continuous adjustm...

Страница 5: ...ch or equivalent use the 0 2 amp tap For 48 Vdc applications set the unit in the 2 amp I L 41 776 5 t a p and use a type WL relay with a S 304C209G01 coil or equivalent I NSTALLATION The relays should...

Страница 6: ...low state in 1 90 to 210 milliseconds If some other time interval is desired the timer setting may be changed by means of a screw driver adjustment through the access hole on the timer 6 module to a m...

Страница 7: ...t point TP6 and TP7 on the timer board Energize the relay with rated de voltage and apply 0 48 Amps ac current to phase A With the tap in the 0 5 position and the phase multiplier dial knob fully coun...

Страница 8: ...cation of trouble in service or dur ing routine checks the following information will prove helpful All measurements are approximate and may vary as much as 20 All voltages are positive with reference...

Страница 9: ...voltage at terminal 4 should measure 6 4V The voltage at printed circuit board I L 41 776 5 terminal 3 should measure 23 5Vdc before the output relay operates and less than 2 5V after it operates 3 J...

Страница 10: ...Current 4 5A S OA VA 23 28 OHMS 0 1 1 01 1 P F Angle 36 1 8 Saturated Burden Current Lagging Voltage CLOSED 4 5A S OA 16 20 008 008 5 4 OPEN C LOSED SA SA O SA S OA 53 2 1 33 2 2 23 08 1 5 09 63 25 20...

Страница 11: ...5 TABLE 4 I L 41 776 5 0 5 to 1 3 5 Amperes 1 SECOND 250 Amps 250 300 AR CONTACT RATINGS I NTERRUPTING RATING CONTACT CIRCUIT TRIP CARRY RATING RESISTIVE I NDUCTIVE RATING RATING CONTINUOUS L R 005 4...

Страница 12: ...ER TB TRANSFORMER TA Fig 1 Photograph of SBF 1 Relay without case with four overcurrent input Front view 12 SEAL IN RELAY X ICS INDICATING CONTACTOR SWITCH w w w E l e c t r i c a l P a r t M a n u a...

Страница 13: ...right oblique I L 41 776 5 POTENTIOMETER PA POTENTIOMETER PC POTENTIOMETER PG POTENTIOMETER PB TRANSFORMER TG RESISTOR RS 1 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 14: ...MOVE RED LEAD FROM TERMINAL II TO TERMINAL 12 L R LC S RC DENOTE LEFT HAND RIGHT HAND LEFT CENTER S RIGHT CENTER POSITIONS REF DWG 25W RESISTORS 1326DI9 DETAILED SCHEMATIC 1326D31 4 OVERCURRENT UNITS...

Страница 15: ...TED VDC 13 FROM TERM 3 OF 4 OVERCURRENT DETECTOR MODULE RATED VDC 3 52 a TIMER AND O UTPUT MODULE 4 PI IS PANEL MOUNTED 17 7 L TO X RELAY 10 J WHEN USED REPLACED BY FOR GROUPS I Fig 4 Internal SCR w w...

Страница 16: ...RIPTI JN STYLE N0 JUM P R 0 OHM RESISTOR 862A413HO I Jl DESCRIPTI J J STYLE POT 20 0K 501 1 862A406H02 P2 25 0K sow SSOA687H02 PI DESCRIPTHlN STYLE TRANS STOR 2N2905A 762A672H O 01 2 lt 7 1 1 762A585H...

Страница 17: ...Pl 2 a Pl 3 I 14 Fig 5 Component Location tor Timer Module 48 or 125Vdc rated relay I L 41 776 5 3517A76 19 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 18: ...WHEN USED 3517A77 Fig 6 Com u e 250Vdc rated relay ponent Location for Timer Mod I 20 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 19: ...o z uot s I d SH U7H7 ki 0 12 lJ SCKIPfiJ TYLI ZE EK 1 751A f 2 J r r n r o1 Z2 1 17j21 JJ Jv 0 I I d c Zl DESCRIPTltlN STYLE NG I POT 500 0 2 00W 10 7o 848A778H04 PA PC PG IO OK 12 5W O lo 836A635HI...

Страница 20: ...3517A78 Fig 8 Component Location for 3 Current Input Overcurrent Detector Module 22 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 21: ...I L 41 776 5 3517A79 Fig 9 Component Location for 4 Current Input Overcurrent Detector Module 23 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 22: ...G X TAP MULTIPLIER r l I TO RH CONTACT OF AR RELAY I t L _ Q J_ 2 4 s a lGND J l L J TO RH CONTACT I OF AR RELAY I l l 9 Qg _j LO BOUNCE SWITCH TO TESTTIMER RATED START VDC TO TESTTIMER COMMON NOTE TO...

Страница 23: ...PPt 62 l 62 l 2 _ _3 r 1 IB WHEN 62 1 16 USED 17 r n 6 Ic f 1 _ Io 6 1 f Jf 1 SPP t rv r rv P J SBF 1 RELAY FOR BREAKER 52 2 r r BACKUP r RELAYS r r JPRIMAR t SPP SURGE PROTECTION CAPACITORS TO BE USE...

Страница 24: ...BR EAKER FAILUR E R ELAY 7nBBI3 1326DI 9 62Xp2 Y BR EAKER FAIL UR E INITIATE CONTACTS 8 6BF BR EAKER FAILUR E LOCKOUT R ELAY 8 6TI TR ANSFOR MER LOCKOUT R ELAY T YPICAL 8 6BF AND OR R E L AY AUX F UNC...

Страница 25: ...EXTERNAL TOOTHED WASHERS 4 375 1 1 1 1 3 1 90 32 SCREW 4 375 SPACERS FOR I l l 1 3 THIN PANELS I L 41 776 5 5 5631 250 DIA 4 HOLES FOR 141 30 6 35 190 32 MTG SCREWS f 1 5707903 Fig 13 Outline and Dri...

Страница 26: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 27: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 28: ...W E S T I N G H O U S E E L E C T R I C C O R P O R A T I O N R E LAY I NST RU M E NT D IVISION CORAL SPRI NGS F L Printed in U S A w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 29: ...tap block located on the front of the relay Each transformer has three taps which cover the range of pickup The secondary of the transformers are con nected to the input of the plug in detector modul...

Страница 30: ...ctor The breaker failure timer controls the fault detector so that after it times out the overcurrent signal if present is connected to the level detector This arrangement keeps the overcurrent input...

Страница 31: ...rent is reduced to zero or up to 95 of pickup current Continuous rating is 1 0 amperes One second rating is 250 amperes The accuracy of the pickup setting is 5 over the full range and 10 from 20 to 55...

Страница 32: ...cts will safely close 30 amperes at 250 Vdc and the seal in contacts of the ICS will safely carry this current long enough to trip a cir cuit breaker SETTINGS OVERCURRENT DETECTOR The pickup of the ov...

Страница 33: ...41 776 5A resistor that is inserted on tripping and the over current fault detectors are set below the resistor current the additional time for this interruption must be included A secure margin for...

Страница 34: ...e will speed up the dropout time longer range timer Use the same test with applying current to BREAKER FAILURE BF i f phase C and also phase B if used Pickup should TIMER be within 5 of the phase A pi...

Страница 35: ...e relay if the relay has been taken apart for repairs or the adjustments have been disturbed This procedure should not be used unless it is apparent that the relay is not in proper working order Overc...

Страница 36: ...ee that the contacts close at rated tap value current The indicating target should drop at or just prior to the contacts closing The targer should drop freely I f the target does not drop or does not...

Страница 37: ...1 posi tion I L 41 776 5A a With 0 4 amp ac current flowing apply rated relay voltage Measure voltage at terminal 5 of I C I to be 6 4V Now increase the current until the output relay operates The vo...

Страница 38: ...OA VA 1 65 75 06 60 63 75 50 60 O H M S 073 03 027 024 03 1 03 024 024 P F Angle 45 36 1 5 1 5 36 36 1 5 1 5 TAP 4 5 TAP MULT 1 4 5A PICKUP 3 1 3 5A PICKUP REED RR CONTACT OPEN CLOSED OPEN C LOSED Cu...

Страница 39: ...T RATINGS I L 41 776 5A I NTERRUPTING RATING CONTACT CIRCUIT TRIP CARRY RATING RESISTIVE I NDUCTIVE RATING RATING CONTINUOUS L R 005 48Vdc 30 Amps 3 Amps 3 75 Amps 1 75 Amps 1 25 30 3 5 35 250 30 3 25...

Страница 40: ...ER TB TRANSFORMER TA Fig 1 Photograph of SBF 1 Relay without case with four overcurrent input Front view 12 SEAL IN RELAY X ICS INDICATING CONTACTOR SWITCH w w w E l e c t r i c a l P a r t M a n u a...

Страница 41: ...right oblique I L 41 776 5A POTENTIOMETER PA POTENT OMETER PC POTENTI OMETER PG _ _ POTENTIOMETER PB TRANSFORMER TG RESISTOR RS 1 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 42: ...R l L Cl RCl DENOTE LEFT HANO RIGHT HAND LEFT CENTER a RIGHT CENTER POSITIONS W RESISTORS VOLTS DC RA RS 1326DI9 DET AILED SCHEMATIC 48 900 n 200 n 1326D31 4 OVERCURRENT UNITS WIRING 1 326 D83 3 OVERC...

Страница 43: ...13 FROM TERM 3 OF 4 OVERCURRENT DETECTOR MODULE RATED VDC 52 a f i 4 TIMER AND OUTPUT MODULE PI IS PAN E L MOUNTED 7 TO X RELAY 10 WHEN USED I I I I 9 I I I REPLACED BY J FOR GROUPS I a 0 Fig 4 Intern...

Страница 44: ...UZ8 70 Q Q IJ 0 37 A 69 JH I 4 matic of Timer Module 1454C81 G02 125 VDC 1454C81 G03 2 50 VOC CAPAC T O R C J C2 Cl D H l U D l 2 03 II A DX l N T CKT I C I JUMPER J l 2 P2 P I P0T TRtu I S I S H J R...

Страница 45: ...Pl 2 a Pl 3 I 14 Fig 5 Component Location for Timer Module 48 or 125Vdc rated relay I L 41 776 5A 3517A76 19 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 46: ...20 Fig 6 Comp anent Location for Timer Mod I u e 250Vdc rated relay WHEN USED 3517A77 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 47: ...l 7 J J Q j Q Q 5 1 7 rl 6 J J 5 R l 5 0 0 00 5 7 6 ll 1 7Yll R l 2 4 5 J Q Q 1 57 J tl 7 A 6 4 3rlJ R l 6 3 9 2 00 o 5 4 6 5A 2 J 7 L l 1 1 3 1 4 J O Q Q 2 00 1t 5 4 J 5f 2 0 7 H 7 5 R9 10 12 UESCRJ...

Страница 48: ...3517A78 Fig 8 Component Location for 3 Current Input Overcurrent Detector Module 2 2 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 49: ...I L 41 776 5A 3517A79 Fig 9 Component Location for 4 Current Input Overcurrent Detector Module 23 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 50: ...I TO RH CONTACT TO RH CONTACT I OF AR RELAY OF AR RELAY I I 1 l i L _ C0_ 2 4 6 l 9 _j L g uc N HCE f JA1 l c1 lGND IOK TO TESTTIMER RATED Y Y f START VDC TOTESTTlMER COMMON NOTE TO TEST FOR OVERCURR...

Страница 51: ...62 2 r SBF I RELAY FOR BREAKER 52 2 rrll l rr x 6 llf f 1 1 1 1 1 l f 6 lc 62 I BACKUP f A vT RELAYS r t 62 1 Io L 7 fs t f I P E t SPP SURGE PROTECTION CAPACITORS TO BE USED WHEN SURGE VOLTAGE MAY E...

Страница 52: ...D ________ _____ I u I CIRCUIT BR IPTION S8F IBREA ERFAILUR R lAY 775 1326 D 1 9 2X 62Y BREAKER FAI L U R E I N I T IAT CO _ N _ TACTS l LBSBF BREA K E R FAILURE LOCKOUT RELAY 86TI TRANSFOR M E R LOC...

Страница 53: ...750 400 05 5 875 149 23 2 938 74 63 PA NEL C U TOUT 8t DR I L L I N G FOR S E M I FLU S H MTG LARGE INT E R N I 5 5 6 a E XT E RNA L _L_ J t TOOTH WASHER r 64 1 16 2 8 S M A LL EXTERNAL TOOTHED WASHER...

Страница 54: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 55: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 56: ...W E S T I N G H O U S E E L E C T R I C C O R P O R A T I O N R E LAY I N ST R U M E NT DIVISION CORAL S P R I N G S FL Printed in U S A w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Отзывы: