background image

The same procedure should be fol lowed  for the 

ground overcurrent circuit as  was  used  for phase A 

input. 

Remove  jum per  from  TP6  and  TP7  on  the 

timer  m odule. 

Control  Timer 

Refer  to  Fig.  4  and  5  or  6  when  repl acing  com­

ponents. 

If components in the control timer circuit have 

been  replaced  or if it is desired  to change the con­
trol  timer  setting  the  same  procedure  should  be 
used  as  described  under  acceptance  test ing. 

Breaker  Failure  ( BF}  Timer 

If the scale appears to 

be 

o ff calibru tion due 

to 

slippage  of the knob  pointer on the  shaft,  this can 

be corrected by rotating the shaft fully 

CCW. 

N ow 

adjust the  k n ob at the  pin  prick mark . This should 

return the k n ob to its  original position on the sha ft 
and bring the scale markings back i nto calibration . 

i f  

components  in  the breaker  failure timer cir­

cuit  have  been  replaced 

it 

may  be  necessary  to 

change  the  scale  plate  and  recalibrate . 

First 

jumper  test  points  TP6  and  TP7.  Using 

a  l cnv 

bounce initiate switch adjust timer k nob until 

25 

ms  time  delay  has  been  obtained .  U se  test 
procedure  described  under  acceptance  testing  for 
measuring time  delay.  N ote the knob  position  for 
25  ms  delay .  Also  note the  k nob  position  for  1 75 
ms  delay .  Loosen  the  set  screw  and  position  the 
k nob  on  the  shaft  so  that  the  25  and  1 75  ms 
locations  are  equidistant  about  the  knob  locking 
tab.  Scribe  lines  at the 25 ms setting and for each 

25  ms  increment  up  to  1 75  ms. 

Indicating  Contactor  Switch  ( I CS) 

Adjust  the  contact  gap  for  approximately 

. 047"  by  adjusting  the  stationary  contacts.  Both 

contacts  should  make  simultaneously. 

Check  to  see that  the  contacts  close  at  rated 

tap  va lue  current.  The  indicating  target  should 

drop  at  or just  prior  to  the  contacts  closing.  The 
targer  should  drop  freely. 

I f  the  target does not drop or does n ot  reset it 

may be necessary to remove the cover and bend the 

tab  on  the  spring  that  supports 

the 

target. 

T R O U B L E  S H O OTI N G  

The  components  i n   the  S B F- 1  relay  are 

operated  wel l  within their rating and normally will 
give  l ong  and  trouble  free  service.  H owever, 

if 

relay  gives  indication  of trouble  in  service  or  dur­

ing  routine  checks  the  fo ll owing  informati on  will 
prove helpful.  All  measurements  are  approximate 
a nd  may  vary  as  much  as  20%.  All  voltages  ar�; 
p•Jsitive with  reference to common  negative ( reluy 

term inal  8 )  except  ac  voltages . 

Timer  Module 

l .   Jumper 

test 

points  TP6  and 

TP7. 

a .   Apply  rated  relay voltage.  Voltage 

at 

l ower 

test j ack = 23 . 5 V  

b .   Rem ove  jumper.  Apply  rated  voltage . 

Voltage  at  l ower  test jack  =  2 3 . 5  

c::c. 

Jumper test  poi nts 

TP6  and 

TD7 

:1 .  

Apply  rated  relay  voltage.  Voltage 

at 

u oper 

test jack = !es'i  than  2 . 5  

Ydc:. 

h. 

Rem ove  jumper.  A pply  r:J�ed  vollage . 

Voltage  at  upper  test  jack = less  t h a n  

2 . 5  

Vdc . 

3 .  

jumper  test  points  TP6 

and  "':P7. 

a.  Apply  rated  voltage.  Voltage  at 

term inal  6 

of  l e i = l 8 . 3 V .  

b.  Rem ove  jumper.  Apply  rated  voltage. 

Voltage  at  terminal  6  o f  

C I  should  be  ap­

proxim ately  0. 1  Vdc  less  than  voltage 
measured  in  section  a. 

4.  Jumper  test  points  TP6  and  TP7. 

a.  Apply  rated  relay  voltage.  Voltage  at  ter­

minal 

of I C J  = 20.8V with timer knob fully 

CW . 

b.  Voltage  at  terminal  7  o f   I C I  = 23 . 8 V   with 

timer  knob  fully  CCW. 

5.  Jum per  test  points  TP6  and  TP7. 

a .   Apply  rated  relay  voltage.  Voltage  at  ter­

minal  2  o f  I C l  

1 6 . 5 V .  

b .   Remove jumper a n d  apply voltage. Voltage 

at  terminal  2  of  IC 

should  be  approxi-

www 

. ElectricalPartManuals 

. com 

Содержание SBF-1

Страница 1: ...tapped and brought out to a tap block located on the front of the relay Each transformer has three taps which cover the range of pickup The secondary of the transformers are con nected to the input o...

Страница 2: ...as well as the X seal in relay is reset after it times out The circuit operation can be explained by referring to the internal schematic drawing 77588 1 3 Fig 2 and detailed internal schematic 1 3260...

Страница 3: ...ained by using a current source and a precision ammeter CAUTION Since the tap block connector screw carries operating current be sure that the screw is turned tight In order to avoid opening the curre...

Страница 4: ...rrent unit is obtained by means of a tap screw and tap block in conjunc tion with the tap multiplier knob setting located at the front of the overcurrent unit module This per mits a continuous adjustm...

Страница 5: ...ch or equivalent use the 0 2 amp tap For 48 Vdc applications set the unit in the 2 amp I L 41 776 5 t a p and use a type WL relay with a S 304C209G01 coil or equivalent I NSTALLATION The relays should...

Страница 6: ...low state in 1 90 to 210 milliseconds If some other time interval is desired the timer setting may be changed by means of a screw driver adjustment through the access hole on the timer 6 module to a m...

Страница 7: ...t point TP6 and TP7 on the timer board Energize the relay with rated de voltage and apply 0 48 Amps ac current to phase A With the tap in the 0 5 position and the phase multiplier dial knob fully coun...

Страница 8: ...cation of trouble in service or dur ing routine checks the following information will prove helpful All measurements are approximate and may vary as much as 20 All voltages are positive with reference...

Страница 9: ...voltage at terminal 4 should measure 6 4V The voltage at printed circuit board I L 41 776 5 terminal 3 should measure 23 5Vdc before the output relay operates and less than 2 5V after it operates 3 J...

Страница 10: ...Current 4 5A S OA VA 23 28 OHMS 0 1 1 01 1 P F Angle 36 1 8 Saturated Burden Current Lagging Voltage CLOSED 4 5A S OA 16 20 008 008 5 4 OPEN C LOSED SA SA O SA S OA 53 2 1 33 2 2 23 08 1 5 09 63 25 20...

Страница 11: ...5 TABLE 4 I L 41 776 5 0 5 to 1 3 5 Amperes 1 SECOND 250 Amps 250 300 AR CONTACT RATINGS I NTERRUPTING RATING CONTACT CIRCUIT TRIP CARRY RATING RESISTIVE I NDUCTIVE RATING RATING CONTINUOUS L R 005 4...

Страница 12: ...ER TB TRANSFORMER TA Fig 1 Photograph of SBF 1 Relay without case with four overcurrent input Front view 12 SEAL IN RELAY X ICS INDICATING CONTACTOR SWITCH w w w E l e c t r i c a l P a r t M a n u a...

Страница 13: ...right oblique I L 41 776 5 POTENTIOMETER PA POTENTIOMETER PC POTENTIOMETER PG POTENTIOMETER PB TRANSFORMER TG RESISTOR RS 1 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 14: ...MOVE RED LEAD FROM TERMINAL II TO TERMINAL 12 L R LC S RC DENOTE LEFT HAND RIGHT HAND LEFT CENTER S RIGHT CENTER POSITIONS REF DWG 25W RESISTORS 1326DI9 DETAILED SCHEMATIC 1326D31 4 OVERCURRENT UNITS...

Страница 15: ...TED VDC 13 FROM TERM 3 OF 4 OVERCURRENT DETECTOR MODULE RATED VDC 3 52 a TIMER AND O UTPUT MODULE 4 PI IS PANEL MOUNTED 17 7 L TO X RELAY 10 J WHEN USED REPLACED BY FOR GROUPS I Fig 4 Internal SCR w w...

Страница 16: ...RIPTI JN STYLE N0 JUM P R 0 OHM RESISTOR 862A413HO I Jl DESCRIPTI J J STYLE POT 20 0K 501 1 862A406H02 P2 25 0K sow SSOA687H02 PI DESCRIPTHlN STYLE TRANS STOR 2N2905A 762A672H O 01 2 lt 7 1 1 762A585H...

Страница 17: ...Pl 2 a Pl 3 I 14 Fig 5 Component Location tor Timer Module 48 or 125Vdc rated relay I L 41 776 5 3517A76 19 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 18: ...WHEN USED 3517A77 Fig 6 Com u e 250Vdc rated relay ponent Location for Timer Mod I 20 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 19: ...o z uot s I d SH U7H7 ki 0 12 lJ SCKIPfiJ TYLI ZE EK 1 751A f 2 J r r n r o1 Z2 1 17j21 JJ Jv 0 I I d c Zl DESCRIPTltlN STYLE NG I POT 500 0 2 00W 10 7o 848A778H04 PA PC PG IO OK 12 5W O lo 836A635HI...

Страница 20: ...3517A78 Fig 8 Component Location for 3 Current Input Overcurrent Detector Module 22 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 21: ...I L 41 776 5 3517A79 Fig 9 Component Location for 4 Current Input Overcurrent Detector Module 23 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 22: ...G X TAP MULTIPLIER r l I TO RH CONTACT OF AR RELAY I t L _ Q J_ 2 4 s a lGND J l L J TO RH CONTACT I OF AR RELAY I l l 9 Qg _j LO BOUNCE SWITCH TO TESTTIMER RATED START VDC TO TESTTIMER COMMON NOTE TO...

Страница 23: ...PPt 62 l 62 l 2 _ _3 r 1 IB WHEN 62 1 16 USED 17 r n 6 Ic f 1 _ Io 6 1 f Jf 1 SPP t rv r rv P J SBF 1 RELAY FOR BREAKER 52 2 r r BACKUP r RELAYS r r JPRIMAR t SPP SURGE PROTECTION CAPACITORS TO BE USE...

Страница 24: ...BR EAKER FAILUR E R ELAY 7nBBI3 1326DI 9 62Xp2 Y BR EAKER FAIL UR E INITIATE CONTACTS 8 6BF BR EAKER FAILUR E LOCKOUT R ELAY 8 6TI TR ANSFOR MER LOCKOUT R ELAY T YPICAL 8 6BF AND OR R E L AY AUX F UNC...

Страница 25: ...EXTERNAL TOOTHED WASHERS 4 375 1 1 1 1 3 1 90 32 SCREW 4 375 SPACERS FOR I l l 1 3 THIN PANELS I L 41 776 5 5 5631 250 DIA 4 HOLES FOR 141 30 6 35 190 32 MTG SCREWS f 1 5707903 Fig 13 Outline and Dri...

Страница 26: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 27: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 28: ...W E S T I N G H O U S E E L E C T R I C C O R P O R A T I O N R E LAY I NST RU M E NT D IVISION CORAL SPRI NGS F L Printed in U S A w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 29: ...tap block located on the front of the relay Each transformer has three taps which cover the range of pickup The secondary of the transformers are con nected to the input of the plug in detector modul...

Страница 30: ...ctor The breaker failure timer controls the fault detector so that after it times out the overcurrent signal if present is connected to the level detector This arrangement keeps the overcurrent input...

Страница 31: ...rent is reduced to zero or up to 95 of pickup current Continuous rating is 1 0 amperes One second rating is 250 amperes The accuracy of the pickup setting is 5 over the full range and 10 from 20 to 55...

Страница 32: ...cts will safely close 30 amperes at 250 Vdc and the seal in contacts of the ICS will safely carry this current long enough to trip a cir cuit breaker SETTINGS OVERCURRENT DETECTOR The pickup of the ov...

Страница 33: ...41 776 5A resistor that is inserted on tripping and the over current fault detectors are set below the resistor current the additional time for this interruption must be included A secure margin for...

Страница 34: ...e will speed up the dropout time longer range timer Use the same test with applying current to BREAKER FAILURE BF i f phase C and also phase B if used Pickup should TIMER be within 5 of the phase A pi...

Страница 35: ...e relay if the relay has been taken apart for repairs or the adjustments have been disturbed This procedure should not be used unless it is apparent that the relay is not in proper working order Overc...

Страница 36: ...ee that the contacts close at rated tap value current The indicating target should drop at or just prior to the contacts closing The targer should drop freely I f the target does not drop or does not...

Страница 37: ...1 posi tion I L 41 776 5A a With 0 4 amp ac current flowing apply rated relay voltage Measure voltage at terminal 5 of I C I to be 6 4V Now increase the current until the output relay operates The vo...

Страница 38: ...OA VA 1 65 75 06 60 63 75 50 60 O H M S 073 03 027 024 03 1 03 024 024 P F Angle 45 36 1 5 1 5 36 36 1 5 1 5 TAP 4 5 TAP MULT 1 4 5A PICKUP 3 1 3 5A PICKUP REED RR CONTACT OPEN CLOSED OPEN C LOSED Cu...

Страница 39: ...T RATINGS I L 41 776 5A I NTERRUPTING RATING CONTACT CIRCUIT TRIP CARRY RATING RESISTIVE I NDUCTIVE RATING RATING CONTINUOUS L R 005 48Vdc 30 Amps 3 Amps 3 75 Amps 1 75 Amps 1 25 30 3 5 35 250 30 3 25...

Страница 40: ...ER TB TRANSFORMER TA Fig 1 Photograph of SBF 1 Relay without case with four overcurrent input Front view 12 SEAL IN RELAY X ICS INDICATING CONTACTOR SWITCH w w w E l e c t r i c a l P a r t M a n u a...

Страница 41: ...right oblique I L 41 776 5A POTENTIOMETER PA POTENT OMETER PC POTENTI OMETER PG _ _ POTENTIOMETER PB TRANSFORMER TG RESISTOR RS 1 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 42: ...R l L Cl RCl DENOTE LEFT HANO RIGHT HAND LEFT CENTER a RIGHT CENTER POSITIONS W RESISTORS VOLTS DC RA RS 1326DI9 DET AILED SCHEMATIC 48 900 n 200 n 1326D31 4 OVERCURRENT UNITS WIRING 1 326 D83 3 OVERC...

Страница 43: ...13 FROM TERM 3 OF 4 OVERCURRENT DETECTOR MODULE RATED VDC 52 a f i 4 TIMER AND OUTPUT MODULE PI IS PAN E L MOUNTED 7 TO X RELAY 10 WHEN USED I I I I 9 I I I REPLACED BY J FOR GROUPS I a 0 Fig 4 Intern...

Страница 44: ...UZ8 70 Q Q IJ 0 37 A 69 JH I 4 matic of Timer Module 1454C81 G02 125 VDC 1454C81 G03 2 50 VOC CAPAC T O R C J C2 Cl D H l U D l 2 03 II A DX l N T CKT I C I JUMPER J l 2 P2 P I P0T TRtu I S I S H J R...

Страница 45: ...Pl 2 a Pl 3 I 14 Fig 5 Component Location for Timer Module 48 or 125Vdc rated relay I L 41 776 5A 3517A76 19 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 46: ...20 Fig 6 Comp anent Location for Timer Mod I u e 250Vdc rated relay WHEN USED 3517A77 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 47: ...l 7 J J Q j Q Q 5 1 7 rl 6 J J 5 R l 5 0 0 00 5 7 6 ll 1 7Yll R l 2 4 5 J Q Q 1 57 J tl 7 A 6 4 3rlJ R l 6 3 9 2 00 o 5 4 6 5A 2 J 7 L l 1 1 3 1 4 J O Q Q 2 00 1t 5 4 J 5f 2 0 7 H 7 5 R9 10 12 UESCRJ...

Страница 48: ...3517A78 Fig 8 Component Location for 3 Current Input Overcurrent Detector Module 2 2 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 49: ...I L 41 776 5A 3517A79 Fig 9 Component Location for 4 Current Input Overcurrent Detector Module 23 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 50: ...I TO RH CONTACT TO RH CONTACT I OF AR RELAY OF AR RELAY I I 1 l i L _ C0_ 2 4 6 l 9 _j L g uc N HCE f JA1 l c1 lGND IOK TO TESTTIMER RATED Y Y f START VDC TOTESTTlMER COMMON NOTE TO TEST FOR OVERCURR...

Страница 51: ...62 2 r SBF I RELAY FOR BREAKER 52 2 rrll l rr x 6 llf f 1 1 1 1 1 l f 6 lc 62 I BACKUP f A vT RELAYS r t 62 1 Io L 7 fs t f I P E t SPP SURGE PROTECTION CAPACITORS TO BE USED WHEN SURGE VOLTAGE MAY E...

Страница 52: ...D ________ _____ I u I CIRCUIT BR IPTION S8F IBREA ERFAILUR R lAY 775 1326 D 1 9 2X 62Y BREAKER FAI L U R E I N I T IAT CO _ N _ TACTS l LBSBF BREA K E R FAILURE LOCKOUT RELAY 86TI TRANSFOR M E R LOC...

Страница 53: ...750 400 05 5 875 149 23 2 938 74 63 PA NEL C U TOUT 8t DR I L L I N G FOR S E M I FLU S H MTG LARGE INT E R N I 5 5 6 a E XT E RNA L _L_ J t TOOTH WASHER r 64 1 16 2 8 S M A LL EXTERNAL TOOTHED WASHER...

Страница 54: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 55: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 56: ...W E S T I N G H O U S E E L E C T R I C C O R P O R A T I O N R E LAY I N ST R U M E NT DIVISION CORAL S P R I N G S FL Printed in U S A w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Отзывы: