T Y P E
S ETTINGS
PHASE
&
GROUND OVERCU RRENT U N IT
The pickup current setting is made by means
the connector screw located on the tap plate. By
placing the connector screw in the desired tap, the
relay will just close its contacts at the tap value
current.
CAUTION:
Since the tap block connector screw
carries operating currrent, be sure that the screw
is turned tight.
In order to avoid opening the current trans
former circuits when changing taps under load,
connect the spare tap screw in the desired tap
position before removing the other tap screw
from the original tap position .
I NDICATING CONTACTOR SWITC H (ICS)
Connect the lead located in front of the tap
block to the desired setting by means of the con
necting screw. When the relay energizes a 1 25-or
250-volt de type WL relay switch or equivalent,
use the 0.2 ampere tap; for 48-volt de applications
set in 2 tap and use WL coil S#304C209G0 1 .
I N STALLATION
The relays should be mounted on switch
board panels or their equivalent in a location
free from dirt, moisture, excessive vibration and
heat. Mount the relay vertically by means of the
rear mounting stud or studs for the type FT pro
jection case or by means of the four mounting
holes on the flange for the semi-flush type Ft
case. Either the stud or the mounting screws may
be utilized for grounding the relay. External
toothed washers are provided for use in the
locations shown on the outline and drilling plan
to facilitate making a good electrical connection
between the relay case, its mounting screws or
studs, and the relay panel. Ground wires and
affixed to the mounting screws or studs as required
for poorly grounded or insulating panels. Other
electrical connections may be made directly to the
terminals by means of screws for steel panel
mounting or tg the terminal stud furnished with
the relay for thick panel mounting. The terminal
stud may be easily removed or inserted by locking
two nuts on the stud and then turning the proper
nut with a wrench.
For detail information on the FT case refer to
I.L. 4 1 -076.
ADJUSTMENTS AND MAI NTENANC E
The proper adjustments t o insure correct
operation of this relay have been made at the
factory. Upon receipt of the relay, no customer
adjustments, other than those covered under
"SETTINGS," should be required.
ACC EPTANCE CHECK
The following check is recommended to insure
that the relay is in proper working order:
Phase
&
Ground Overcurrent Unit
1 . Contact Gap - The gap between the
stationary and moving contacts with the relay in
the deenergized position should be approximately
.020."
2. Minimum Trip Current - The pick-up of
the overcurrent unit can be checked by inserting
the tap screw in the desired tap hole and applying
rated tap value current. The contact should close
within
±
5% of tap value current.
Indicating Contactor Switch (ICS)
Close the phase or ground relay contacts and
pass sufficient d-e current through the trip circuit
to close the contacts of the ICS. This value of
current should not be greater than the particular
ICS tap setting being used. The indicator target
should drop freely.
The contact gap should be approximately
.047" between the bridging moving contact and
the adjustable stationary contacts. The bridging
moving contact should touch both stationary con
tacts simultaneously.
ROUTIN E MAI NTENANCE
All relays should be inspected periodically and
the operation should be checked at least once
every year or at such other time intervals as may
be dictated by experience to be suitable to the
particular application.
9
www
. ElectricalPartManuals
. com
Содержание KC-4
Страница 2: ...TYP E K C 4 R ELA Y 2 ai 0 lJ w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 22: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 23: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 39: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 63: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 66: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 84: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 86: ... w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 113: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 148: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 149: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 176: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 177: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...