TY P E S B F U STATI C C I RCU I T B R EA K E R FAILU R E R E LAY
switch is c l osed . A lso check all other outputs as
s hown on the l ogic drawing.
C A L I B R A T I O N
Overcurrent U n i t
The overcurrent unit may b e r e c al i brated i f the
phase splitter or feedback potentiom eter adjustm e nt s
have be en distur b e d o r if co mponents have b e e n
repl aced . A s a re sul t, the sc al e mark i n g s may not
track wit h the knob so that it may be n e c e s s ary to
readj u st the knob or r epl ace the sc al e plate with a
new dial .
The ph ase splitter is adj usted with minimum set
ting curr ent applie d , and minimum dial s et t i n g .
Adj ust t h e phase spli t t e r potentiometer R 1 3 s o that
f' qual a-c voltages are measured at the input to the
thre e-phase r e c ti fie r .
(T P 1 , PC
t e rmin al 9 and 1 0 ) .
The dial rheost at i s calibrate d with rated d-e
voltage appl ied . Apply de sired a-c current until a
voltage o f approximately 20
V.
d . c . app ears at the
modul e outputs test points.
The dropout ( fe edback) p otentiometer i s adj usted
by applying p ic k up a-c c urrent after th e feedback
pote ntiometer has been rotated about h al f- way . No w
l ower the a- c current to 95o/c of pickup (or lower i f
desired). I ncreas e the fe edback resi stance by ro
tating the fe edbac k pote ntiom eter clockwise until
the 20 volts d-e at the o utput dro p s to zero .
Adj u stab l e T i mer U n i t
The c ircuit should b e first c h e ck e d t o s e e that
th ere is no compon ent fail ure . Repl ac e ment of a
d efective compon ent m ay or m ay not d i sturb the dial
calibr ation . If it do e s , repositioning of the dial
knob may get the knob to track. I f not , a n e w b lank
s c al e p l at e is re quired. Energize rel ay an d use a
card extender and hookup as in the o verall acc eptan c e
test . Rotate the timing potentiomet er fully c l o ck
wi s e for m axim um tim e d e l ay . Adjust the trimm ing
potentiometer, ( RBU) , so that m aximum d el ay is
approximately 1 0 5% of th e m aximum tim e . Tighte n
k no b so that the m ark er on the knob m ak e s an angle
of approximately 20 d egree s with a vertical l in e .
With t h e k no b rotated ful l y counter- c l o ck w i se , the
timing shoul d b e l e ss than 90o/c o f th e minimum tim e .
The k nob can b e readj u st ed i n order t o balance the
scale mechanically w it h respe ct to t he stops . With
an awl or similar tool , s cri be l i n e s e very . 0 5 , 0 . 1 or
0 . 4 seco n d s , depending on the relay range .
There are no adj u stments required on t h e P o w er
supp l y , breaker logi c , or trip modul e .
R E N E W A L P A R T S
R ep air work can be don e m o st satisfactorily
at the factory. Ho w ever, interchange abl e p arts c an
be furni shed to those c u stom ers who are e quipp e d
for doing repair work . When ordering p art s , al w ays
give the compl ete namepl at e data.
7
www
. ElectricalPartManuals
. com
Содержание KC-4
Страница 2: ...TYP E K C 4 R ELA Y 2 ai 0 lJ w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 22: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 23: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 39: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 63: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 66: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 84: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 86: ... w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 113: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 148: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 149: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 176: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 177: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...