The same procedure should be followed for the
ground overcurrent circuit as was used for phase A
input.
Remove jumper from TP6 and TP7 on the
timer module.
Control Timer
Refer to Fig. 4 and 5 or 6 when replacing com
ponents.
If components in the control timer circuit have
been replaced or if it is desired to change the con
trol timer setting the same procedure should be
used as described under acceptance testing.
Breaker Failure
(B:F)
Timer
If the scale appears to be off calibration due to
slippage of the knob pointer on the shaft, this can
be corrected by rotating the shaft fully CCW. N ow
adjust the knob at the pin prick mark. This should
return the knob to its original position on the shaft
and bring the scale markings back into calibration .
I f components in the breaker failure timer cir
cuit have been replaced it may be necessary to
change the scale plate and recalibrate. First
jumper test points TP6 and TP7. Using a low
bounce initiate switch adjust timer knob until a 25
ms time delay has been obtained. U se test
procedure described under acceptance testing for
mea
s
ur
i
n
g time delay. Note the knob position for
25 ms delay. Also note the knob position for 1 75
ms delay . Loosen the set screw and position the
knob on the shaft so that the 25 and 1 75 ms
locations are equidistant about the knob locking
tab. Scribe lines at the 25 ms setting and for each
25 ms increment up to 1 75 ms.
Indicating Contactor Switch ( I C S)
Adjust the contact gap for approximately
. 047" by adjusting the stationary contacts. Both
contacts should make simultaneously.
Check to see that the contacts close at rated
tap value current. The indicating target should
drop at or just prior to the contacts closing. The
targer should drop freely.
I f the target does not drop or does not reset it
may be necessary to remove the cover and bend the
8
0
tab on the spring that supports the target.
TROU BLE SH OOTI NG
The components in the SBF- 1 relay an!
operated well within their rating and normally will
give long and trouble free service. H owever, if a
relay gives indication of trouble in service or dur
ing routine checks the following information will
prove helpful. All measurements are approximate
and may vary as much as 20% . All voltages are
positive with reference to common negative (relay
terminal 8) except ac voltages.
Timer Module
I . Jumper test points TP6 and TP7.
a. Apply rated relay voltage. Voltage at lower
test jack = 23 . 5 V
b. Remove jumper. Apply rated voltage
Voltage at l ower test jack = 23.5 Vdc.
2. Jumper test points TP6 and TP7
a. Apply rated relay voltage. Voltage at upper
test jack = less than 2.5 V de.
b. Rem ove j u mper. Apply rated voltage.
Voltage at upper test jack = less than 2 . 5
Vdc .
3 . Jumper test points TP6 and TP7.
a . Apply rated voltage. Voltage at terminal
6
of I C 1
=
1 8 .3V.
b. R em ove jumper. Apply rated voltage .
Voltage at terminal 6 of I C I should be ap
proxim ately 0. 1 Vdc less than voltage
measured in section a .
4. Jumper test points TP6 and TP7.
a. Apply rated relay voltage. Voltage at ter
minal 7 of I C I = 20.8V with timer knob fully
CW .
b. Voltage at terminal 7 of IC I = 23 . 8 V with
timer knob fully CCW.
5. Jumper test points TP6 and TP7 .
a. Apply rated relay voltage. Voltage at ter
minal 2 of I C I = l 6.5V.
b. Remove jumper and apply voltage. Voltage
at terminal 2 of IC 1 should be approxi-
www
. ElectricalPartManuals
. com
Содержание KC-4
Страница 2: ...TYP E K C 4 R ELA Y 2 ai 0 lJ w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 22: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 23: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 39: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 63: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 66: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 84: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 86: ... w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 113: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 148: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 149: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 176: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 177: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...