TY P E KC-3
just close. Then back off the stationary contact 2/ 3
of one turn for a g ap of approximately . 0 20 . " The
clamp holding the stationary c ontact housing need
not be loosened for the adjustment since the cl amp
utilizes a spring-type action in holding the stationary
contact in position.
3. The sensitivity adjustment is made by vary
ing the tension of the spiral spring attached to the
moving element assembly. The spring is adjusted by
placing a screwdriver or similar tool into one of the
notches located on the periphery of the spring adjuster
and rotating it. The spring adjuster is loc ated on the
underside of the bridge and is held in place by a
spring type clamp that does not have to be loosened
prior to making the necessary aaj ustments.
Insert the tap screw in the minimum value tap
setting and adj ust the spring such that the contacts
will clo se when energized with the required current .
The pick u p o f the overcurrent unit with the tap screw
in any other tap should be within ± 5% of tap value.
If adju stment of pick-up current in bet ween tap
settings is desired, insert the t ap screw in the next
lowest tap setting and adjust the spring as de scribed.
It should be noted that thi s adj ustment result s in a
slightly different time characteristic curve and burden.
Ground Overc urrent Unit
The core screw which is adj ustable from the top
of the trip unit determines the pickup value. The trip
unit has a nominal ratio of adj ustment of 1 to 4 and
an accuracy within the limits of 10%.
The contact gap should be approximately 5/64"
between the bridging moving contact and the adj ust
able stationary contacts. The bridging moving contact
should touch both stationary contacts simultaneously.
Indicating Contactor Switch (ICS- 1 and ICS- 2)
Close the main relay contacts and p ass sufficient
d-e current through the trip circuit to close the con
tacts of the ICS. This v alue of current should be not
greater than the particular ICS tap setting being used.
The operation indicator target should drop freely.
To increas e the pickup current remove the molded
cover and b e nd the spring s out or away from the cover.
To decrease the pickup c urrent bend the springs in
toward the cover.
The contact g ap should be approximately . 047"
between
th8
bridging m oving contact and the adjust
able stationary contact s. The bridging moving contact
should touch both stationary contacts simultaneously.
Relay ( X)
Block the c ylinder unit contact closed. Apply
rated voltage and see that all the normally op en con
tacts close by means of a neon lamp . Also see that
the normally clo sed co ntacts make a good contact
with the coil d e-energized by noting some deflection
of the contacts. With the relay de-energized check
to see that a good contact is made across the resis
tor in series with the coil by measuring approximately
zero resistance at the resistor terminals.
The contact gap should be approximately . 0 20 " .
The armature res t may be adj usted slightly to achieve
this, but care should be exercised so as not to affect
the normally closed contacts.
The armature re sidual screw may be adjusted to
vary contact follow of the normally open contacts but
the residual g ap should not be less than . 00 2 " .
R E N E W A L P A R T S
Repair work c an be done most satisfactorily at
the factory. However, interchangeable parts can be
furnished to the customers who are equipped for doing
repair work. When o rdering parts , always give the com
plete n ameplate data.
13
www
. ElectricalPartManuals
. com
Содержание KC-4
Страница 2: ...TYP E K C 4 R ELA Y 2 ai 0 lJ w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 22: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 23: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 39: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 63: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 66: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 84: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 86: ... w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 113: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 148: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 149: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 176: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 177: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...