plate transformer T58P during 5-kw emergency operation.
S63P and S64P are contactors which transfer the 460-
volt output of the Plate Regulator between the high-voltage
transformers T53P, T54P, T55P
(
for 50-kw operation
)
and
T58P
(
for 5-kw emergency operation
)
.
These contactors are
located in auxiliary power distri bution cabinet DP51P.
For 50-kw operation, L51P and C51P are the inductive
and capacitive elements of the power-amplifier plate-supply
filter.
PR52P is an oil-immersed thyrite surge arrester,
which under transient conditions absorbs the energy stored
in L51P, thus avoiding destructively high voltages.
Re
sistor R55P prevents C51P from drawing an excessive charg
ing current when high voltage is applied. This resistor is
automatically shorted by contactor S51P after C51P is
charged to the operating voltage.
R56P and R57P are surge
limiting resistors which prevent excessive currents from
flowing under trouble conditions. D57P and D58P are dis
connect switches
•
.Any accumulated dust should occasionally be blown out
of coil L51P by dry compressed air.
The proper oil level
should be maintained by PR52P.
For 5-kw
L52P and C52P form the
high-voltage filter.
R58P is the charging-current limiting
resistor for C52P, and is shorted by contactor S67P after
C52P is fully charged.
D-99119 Rectifier Tube Unit
(
Unit H, Schematic
2
)
Circuit Description
This unit contains the six tubes VlH to V6H inclusive
connected in a three-phase full-wave bridge type rectifier
circuit. The tubes convert the three-phase high-voltage
power furnished by the th ree-phase supply transformers into
10