User Guide
1. Overview
1.8 Ultrastar Data60 Rack Requirements
Warning:
When extended out of the rack on the rail system, the Ultrastar Data60 will be
~630mm / 24.8in. extended outward. This may be a potential tipping hazard depending on
the configuration of the rack. Ensure that leveling feet, anti-tilt, and any other safety features
recommended by the specific rack manufacturers have been deployed before servicing.
The following section provides specific information necessary to install, service, and remove the Ultrastar
Data60. The installation of the Ultrastar Data60 requires two people and a space of 1270mm / 50in. in
front of the installation space. The servicing of the enclosure requires one person and a minimum of
863.6mm / 34in. of space in front of the installation space. The removal of the enclosure requires two
people, 914.4mm / 36in. of space in front of the installation space, and 24in. on either side of the enclosure
for two people to remove the enclosure.
Warning:
The handles on the front of the chassis are not intended to be used to support the
weight of the Ultrastar Data60. Lifting the unit by the chassis handles or trying to support the
unit on the handles can cause them to fail. This can cause serious damage to the unit or serious
bodily harm to those handling the unit. Always team lift the chassis by gripping the underside
of the unit, and never try to lift a chassis that is filled with drives.
Figure 13:
Installation, Servicing, and Removal
Attention:
Do not
install or remove the enclosure while it is populated with drives. The fully
populated enclosure exceeds the amount of weight that a team of two should lift.
1.8.1
Compatible Rack Hardware Configuration
The following table(s) list the approved rack hardware configurations for the Ultrastar Data60:
Table 15:
Compatible Hardware Configuration 1
Parameter
Rack
PDU (Vertical)
PDU Mounting
Bracket
Additional Mounting
Bracket Hardware
Vendor
CRENLO/EMCOR
Server Technology
Server Technology
Various
14