Page 48
Compressors Electrical Data
Technical data
Unit Electrical Data
(1) The dimensioning of the unit’s power cables is the responsibility of the installer, who shall consider: the rating, the maximum working temperature
in the room, the type of insulation and the cable laying, the maximum length of the power supply line.
SLH HET
1202
1402
1602
1802
1902
2002
2202
Nominal voltage
V(%)-ph-Hz
400 ±10% / 3 / 50
Nominal power input
kW
110
126
146
166
173
194
205
Max power input
kW
129
147
171
208
203
240
241
Nominal current
A
199
227
264
290
312
339
370
Max. current (FLA)
A
216
272
312
356
368
400
424
Max. start-up current (LRA)
A
464
391
481
568
645
686
445
External fuses
(A)
315
315
315
400
400
500
500
Wire cross area (1)
mm
2
240
240
240
2x120
2x120
2x150
2x150
Compressors SLH
1202
1402
1602
1802
1902
2002
2202
Number
n°
2
2
2
2
2
2
2
Nominal power input
kW
2x49
2x57
2x65
2x75
2x79
2x87
2x95
Max power input
kW
2x58
2x68
2x77
2x96
2x94
2x110
2x113
Nominal current
A
2x87
2x102
2x116
2x129
2x140
2x150
2x169
Max. current (FLA)
A
2x96
2x124
2x140
2x162
2x168
2x180
2x196
Max. start-up current (LRA)
A
2x373
2x280
2x351
2x423
2x495
2x520
2x276
Oil treater power input
W
200
200
200
200
200
300
200
SLH HET
2402
2602
2804
3204
3604
3804
Nominal voltage
V(%)-ph-Hz
400 ±10% / 3 / 50
Nominal power input
kW
224
243
126+126 146+146 173+173 194+194
Max power input
kW
284
285
147+147 171+171 203+203 240+240
Nominal current
A
391
437
227+227 264+264 312+312 350+250
Max. current (FLA)
A
472
490
272+272 312+312 368+368 400+400
Max. start-up current (LRA)
A
505
552
588
709
827
937
External fuses
(A)
500
630
2x315
315+315 400+400 500+400
Wire cross area (1)
mm
2
2x150
2x185
2x240
2x240
2x120+2x120 2x150+2x120
Compressors SLH
2402
2602
2804
3204
3604
3804
Number
n°
2
2
4
4
4
4
Nominal power input
kW
2x102
2x111
4x57
4x65
4x75
2x75+2x87
Max power input
kW
2x132
2x132
4x68
4x77
4x96
2x96+2x110
Nominal current
A
2x175
2x199
4x102
4x116
4x129
2x129+2x150
Max. current (FLA)
A
2x216
2x225
4x124
4x140
4x162
2x162+2x180
Max. start-up current (LRA)
A
2x314
2x354
4x280
4x351
4x423
2x423+2x520
Oil treater power input
W
300
275
200
200
200
300/200
Manuale SLS-SLH2 2.8.2005 12:23 Pagina 48