English
Page 45
Technical data
Unit Electrical Data
SLS HET
1202
1402
1602
1802
1902
2002
2202
2402
Nominal voltage
V(%)-ph-Hz
400 ±10% / 3 / 50
Nominal power input
kW
110
126
146
173
173
194
205
224
Max power input
kW
129
147
171
203
203
240
241
284
Nominal current
A
199
227
264
312
312
350
370
404
Max. current (FLA)
A
216
272
312
368
368
400
424
472
Max. start-up current (LRA)
A
464
391
481
645
645
686
445
505
External fuses
(A)
315
315
315
400
400
500
500
500
Wire cross area (1)
mm
2
240
240
240
2x120
2x120
2x150
2x150
2x150
SLS HET
2602
3002
3402
3802
4202
3804
4004
Nominal voltage
V(%)-ph-Hz
400 ±10% / 3 / 50
Nominal power input
kW
243
270
293
321
385
173+173 194+194
Max power input
kW
285
317
341
438
524
203+203 240+240
Nominal current
A
437
488
528
560
671
312+312 350+350
Max. current (FLA)
A
490
538
588
716
804
368+368 400+400
Max. start-up current (LRA)
A
552
594
690
752
909
912
962
External fuses
(A)
630
630
630
800
1000
400+400 500+500
Wire cross area (1)
mm
2
2x185
2x185
2x185
2x300
2x300
2x120+2x120 2x120+2x120
(1) The dimensioning of the unit’s power cables is the responsibility of the installer, who shall consider: the rating, the maximum working temperature
in the room, the type of insulation and the cable laying, the maximum length of the power supply line.
Compressors SLS
1202
1402
1602
1802
1902
2002
2202
2402
Number
n°
2
2
2
2
2
2
2
2
Nominal power input
kW
2x49
2x57
2x65
2x75
2x79
2x87
2x95
2x102
Max power input
kW
2x58
2x68
2x77
2x96
2x94
2x110
2x113
2x132
Nominal current
A
2x87
2x102
2x116
2x134
2x140
2x155
2x169
2x182
Max. current (FLA)
A
2x96
2x124
2x140
2x162
2x168
2x180
2x196
2x216
Max. start-up current (LRA)
A
2x373
2x280
2x351
2x423
2x495
2x520
2x276
2x314
Oil treater power input
W
200
200
200
200
200
300
200
300
Compressors SLS
2602
3002
3402
3802
4202
3804
4004
Number
n°
2
2
2
2
2
4
4
Nominal power input
kW
2x111
2x123
2x135
2x147
2x177
4x79
4x87
Max power input
kW
2x132
2x147
2x158
2x205
2x246
4x94
4x110
Nominal current
A
2x199
2x220
2x240
2x252
2x304
4x140
4x150
Max. current (FLA)
A
2x225
2x245
2x270
2x330
2x370
4x168
4x180
Max. start-up current (LRA)
A
2x354
2x374
2x453
2x465
2x586
4x495
4x520
Oil treater power input
W
275
275
275
300
300
200
300
Compressors Electrical Data
Manuale SLS-SLH2 2.8.2005 12:23 Pagina 45