(1) The dimensioning of the unit’s power cables is the responsibility of the installer, who shall consider: the rating, the maximum working temperature
in the room, the type of insulation and the cable laying, the maximum length of the power supply line.
Technical data
SLH BLN/LN
1202
1402
1602
1802
1902
2002
2202
Nominal voltage
V(%)-ph-Hz
400 ±10% / 3 / 50
Nominal power input
kW
106
126
142
166
173
190
205
Max power input
kW
125
147
167
208
203
236
241
Nominal current
A
191
227
256
290
312
331
370
Max. current (FLA)
A
208
272
304
356
368
392
424
Max. start-up current (LRA)
A
456
391
473
568
645
678
445
External fuses
(A)
315
315
315
400
400
400
500
Wire cross area (1)
mm
2
240
240
240
2x120
2x120
2x120
2x150
SLH BLN/LN
2402
2602
2804
3204
3604
3804
Nominal voltage
V(%)-ph-Hz
400 ±10% / 3 / 50
Nominal power input
kW
220
239
126+126 142+142 166+166 190+166
Max power input
kW
280
281
147+147 167+167 208+208 236+208
Nominal current
A
383
429
227+227 256+256 290+290 331+290
Max. current (FLA)
A
464
482
272+272 304+304 356+356 392+356
Max. start-up current (LRA)
A
497
544
588
693
827
937
External fuses
(A)
500
630
315+315 315+315 400+400 500+400
Wire cross area (1)
mm
2
2x150
2x185
2x240
2x240
2x120+2x120 2x150+2x120
(1) The dimensioning of the unit’s power cables is the responsibility of the installer, who shall consider: the rating, the maximum working temperature
in the room, the type of insulation and the cable laying, the maximum length of the power supply line.
SLH ELN
1202
1402
1602
1802
1902
2002
2202
Nominal voltage
V(%)-ph-Hz
400 ±10% / 3 / 50
Nominal power input
kW
106
121
140
160
167
187
199
Max power input
kW
124
143
165
202
197
233
235
Nominal current
A
189
217
251
276
299
322
356
Max. current (FLA)
A
206
262
298
342
354
383
410
Max. start-up current (LRA)
A
454
381
467
555
631
669
432
External fuses
(A)
315
315
315
400
400
400
500
Wire cross area (1)
mm
2
240
240
240
2x120
2x120
2x120
2x150
SLH ELN
2402
2602
2804
3204
3604
3804
Nominal voltage
V(%)-ph-Hz
400 ±10% / 3 / 50
Nominal power input
kW
217
235
121+121 140+140 160+160 184+160
Max power input
kW
277
277
143+143 165+165 202+202 230+202
Nominal current
A
374
420
217+217 251+251 276+276 318+276
Max. current (FLA)
A
455
473
262+262 298+298 342+342 378+342
Max. start-up current (LRA)
A
488
535
568
682
800
910
External fuses
(A)
500
630
315+315 315+315 400+400 500+400
Wire cross area (1)
mm
2
2x150
2x185
2x240
2x240
2x120+2x120 2x150+2x120
Unit Electrical Data