General Description
sight glass with humidity indicator, a differential oil
pressure switch. Furthermore, each circuit is
equipped with safety devices in accordance with
PED 97/23/EC: high and low pressure switches,
safety valves providing protection in case of fire or
malfunction of compressors.
7.5 Water heat exchanger
All units, except for SLS 3002 and SLS 3402 - 3802
- 4202, are equipped with refrigerant/water heat
exchangers with brazed plates, of “Dual Circuit”
type. This type of heat exchangers makes it possible
to obtain a high heat exchange efficiency, in spite of
its small overall dimensions.
The SLS 3002 and SLS 3402 - 3802 - 4202 units are
provided with a direct-expansion refrigerant/water
shell and tube heat exchanger with several refrigera-
tion circuits. The tube bundle can be removed for in-
spection or maintenance. The evaporators are insu-
lated with UV ray-proof 19 mm-thick anti-condensate
closed-cell polyethylene material.
The external surface is provided with wire resistors
(130 Watt), which prevent frosting at low tempera-
tures (down to -18°C) when the unit is off.
7.6 Air heat exchanger
Coils are made of copper pipes in staggered rows,
mechanically expanded inside an aluminium finned
pack.
7.7 Fans
The condenser’s fans are of large diameter (800
mm) axial type. They are provided with external dif-
fusers (nozzles), that reduce the aeraulic motor to a
large extent. Each fan is provided with galvanised
steel accident-prevention guard, painted after assem-
bly. Finally, the fans’ motors are completely closed,
protection class IP54, protection thermostat im-
mersed in windings.
SLS - Refrigerant circuit of units with plate exchanger evaporator
6 Coil
7 Liquid cock
8 Filter
9 Sight glass
10 Thermostatic valve
11 Solenoid valve
Components:
1 Screw compressor
2 Screw compressor’s
delivery cock
3 Flexible hose - absorber
4 Silencer
5 Safety valve
Note:
the units are equipped with two refrigeration
circuits. Only one circuit is illustrated for the
sake of simplicity.
Safety devices:
A HP pressure switch
C Transducer
D Differential water pressure switch
Filling/discharge and pressure
intakes Freon
Suction points for vacuum
V
12 Plate-type heat exchanger
13 Nonreturn valve
14 Capillary
15 Thermostat
16 Desuperheater (optional)
Manuale SLS-SLH1 2.8.2005 12:34 Pagina 29