The time for detection of a long button press can be set in the general parameters and is valid for
all buttons.
Scene position 1
– 8
For each position, scene 1
– 64 can be activated.
If only one scene position is activated, it is sent on short button press. If several scene positions
are used, the activated positions are switched through with each short button press.
The behavior for selecting and sending the scene positions can be determined by the following
parameter.
Reset scene position
The following options are available:
▪
Never
Starting with the first scene position, the next position of the list is sent with each short
button press, after the last scene position has been sent, the list starts again from the
beginning.
▪
After execution
This selection enables the parameter
Time until execution
.
Beginning with the first scene position, each short button press switches the position by one
position within the execution delay, at the end of the execution delay, the current scene
position is sent.
▪
5 s
– 10 Min.
On each button press the configured delay time is started.
Starting with the first scene position, the next position of the list is sent with each short
button press, after the last scene position has been sent, the list starts again from the
beginning.
After the delay time has expired, the list starts again at the first scene position on the next
short button press.
Condition on long button press
Condition on very long button press
It is also possible to select how a long and very long button press should be handled:
▪
No reaction
▪
Reset position
This function is used to override the behavior as set in the parameter
Reset scene
position
.
▪
Call scene
The scene configured in the appearing parameter is sent.
▪
Save last scene
A telegram for “save scene” with the last sent scene is triggered.
▪
Additional function