© 2022 WEINZIERL ENGINEERING GmbH
Seite 25/36
▪
Call scene
With this function, a scene can be sent. A parameter for selecting the scene is displayed.
Group object
Type KNX
Size
Direction
GO 13 Button A0: Additional function
– Call scene
18.001
1 Byte
To KNX
▪
Save scene
With this function, a scene can be saved. A parameter for selecting the scene is displayed.
Group object
Type KNX
Size
Direction
GO 13 Button A0: Additional function
– Save scene
18.001
1 Byte
To KNX
Very long button press after [s]
This parameter is visible only when using the very long actuation, it sets the time to detect a very
long button press.
11.6
Button function “Send value”
If button function send value is selected, the following telegrams can be sent at button press:
▪
1 Byte
– Integer value / Percent
Group object
Type KNX
Size
Direction
GO 11 Button A0: Send integer value (1 Byte)
– Set value
5.001
1 Byte
To KNX
▪
2 Byte
– Integer value
Group object
Type KNX
Size
Direction
GO 11 Button A0: Send integer value (2 Bytes)
– Set value
7.001
2 Byte
To KNX
▪
2 Byte
– Float value
Group object
Type KNX
Size
Direction
GO 11 Button A0: Send float value (2 Bytes)
– Set value
9.001
2 Byte
To KNX